← Ohio

Tap water quality report

Delaware City

EPA monitoring tested this supplier for 84 contaminants and detected 25. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

84
contaminants tested
25
detected
43,895
people served
13
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Delaware

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

13
health-based violations
20
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2014-04-01 → 2014-06-30
MCL Health-based Resolved 2014-04-01 → 2014-06-30
MCL Health-based Resolved 2014-04-01 → 2014-06-30
MCL Health-based Resolved 2014-04-01 → 2014-06-30
MCL Health-based Resolved 2014-01-01 → 2014-03-31
MCL Health-based Resolved 2014-01-01 → 2014-03-31
MCL Health-based Resolved 2014-01-01 → 2014-03-31
MCL Health-based Resolved 2014-01-01 → 2014-03-31
MCL Health-based Resolved 2013-10-01 → 2013-12-31
MCL Health-based Resolved 2013-10-01 → 2013-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
110 µg/L 8.5%
of the EPA limit 1300 µg/L
worst single sample: 860 µg/L
240/260 SYR4 2012–2018
Bromodichloromethane
17.945 µg/L
No EPA limit set
worst single sample: 21.8 µg/L
154/154 SYR4 2012–2019
Chloroform
83.94 µg/L
No EPA limit set
worst single sample: 105.5 µg/L
154/154 SYR4 2012–2019
Nitrate
4400 µg/L 44%
of the EPA limit 10000 µg/L
worst single sample: 5200 µg/L
154/206 SYR4 2012–2019
Dibromochloromethane
5.8 µg/L
No EPA limit set
worst single sample: 7.1 µg/L
152/152 SYR4 2012–2019
Dichloroacetic Acid
24.345 µg/L
No EPA limit set
worst single sample: 33 µg/L
152/152 SYR4 2012–2019
TTHM
103.36 µg/L 129%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 127.6 µg/L
152/152 SYR4 2012–2019
Trichloroacetic Acid
13.2 µg/L
No EPA limit set
worst single sample: 16.8 µg/L
149/151 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
43.01 µg/L 72%
of the EPA limit 60 µg/L
worst single sample: 47.8 µg/L
119/152 SYR4 2012–2019
Nitrate-Nitrite
4400 µg/L 44%
of the EPA limit 10000 µg/L
worst single sample: 5200 µg/L
77/103 SYR4 2012–2019
Dibromoacetic Acid
2.3 µg/L
No EPA limit set
worst single sample: 2.4 µg/L
41/149 SYR4 2012–2019
Monochloroacetic Acid
4.66 µg/L
No EPA limit set
worst single sample: 11.8 µg/L
29/152 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
23/23 LCR 2024
Lead
20.7 µg/L 138%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 27 µg/L
19/260 SYR4 2012–2018
Atrazine
4.1 µg/L 137%
of the EPA limit, at the 95th percentile of samples — 3 µg/L
worst single sample: 6.7 µg/L
14/31 SYR4 2012–2019
Fluoride
1339 µg/L 33%
of the EPA limit 4000 µg/L
worst single sample: 1430 µg/L
14/14 SYR4 2012–2019
Bromoform
0.6000 µg/L
No EPA limit set
12/154 SYR4 2012–2019
Barium
66 µg/L 3.3%
of the EPA limit 2000 µg/L
worst single sample: 68 µg/L
11/14 SYR4 2012–2019
Simazine
0.8050 µg/L 20%
of the EPA limit 4 µg/L
worst single sample: 1.2 µg/L
11/31 SYR4 2012–2019
Arsenic
3.095 µg/L 31%
of the EPA limit 10 µg/L
worst single sample: 3.1 µg/L
2/14 SYR4 2012–2019
Gross Beta Particle Activity
25 pCi/L
No EPA limit set
1/6 SYR4 2012–2014
Nitrite
180 µg/L 18%
of the EPA limit 1000 µg/L
1/82 SYR4 2012–2018
Toluene
1.2 µg/L 0.1%
of the EPA limit 1000 µg/L
1/14 SYR4 2012–2019
Xylenes, Total
0.6900 µg/L 0%
of the EPA limit 10000 µg/L
1/14 SYR4 2012–2019
Lithium
15.4 µg/L
No EPA limit set
1/4 UCMR-5 2024
59 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalBenzeneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideChromiumCombined Radium (-226 And -228)DichloromethaneEthylbenzeneHfpo-DaLassoMercuryMonobromoacetic AcidNetfosaaNfdhaNmefosaaPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaSeleniumStyreneTetrachloroethyleneThallium, TotalTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
HINSON, THOMAS
Phone
740-203-1926
Email
[email protected]

Frequently asked questions about Delaware City

Is Delaware City tap water safe to drink?

EPA monitoring detected 25 contaminants in Delaware City's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Delaware City's water?

EPA monitoring detected Copper, Bromodichloromethane, Chloroform, Nitrate, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Delaware City serve?

Delaware City reports serving 43,895 people in Ohio, per its EPA record.

Has Delaware City had any water quality violations?

The EPA has 20 violations on file for Delaware City, of which 13 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.