Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2010-01-01 |
| MR | Monitoring | Resolved | 2010-01-01 |
| MR | Monitoring | Resolved | 2009-07-01 |
| MR | Monitoring | Resolved | 2009-07-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 340 µg/L 3.4% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Lead | 0.0015 mg/L 10% of the EPA limit 0.0150 mg/L | 8/8 | LCR | 2024 |
| Bromodichloromethane | 5.07 µg/L No EPA limit set
worst single sample: 5.1 µg/L | 3/3 | SYR4 | 2013–2019 |
| Bromoform | 6.86 µg/L No EPA limit set
worst single sample: 7.5 µg/L | 3/3 | SYR4 | 2013–2019 |
| Chloroform | 3.98 µg/L No EPA limit set
worst single sample: 4 µg/L | 3/3 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 4.53 µg/L No EPA limit set
worst single sample: 4.8 µg/L | 3/3 | SYR4 | 2013–2019 |
| Dibromochloromethane | 10.85 µg/L No EPA limit set
worst single sample: 11.5 µg/L | 3/3 | SYR4 | 2013–2019 |
| TTHM | 23.28 µg/L 29% of the EPA limit 80 µg/L
worst single sample: 24.2 µg/L | 3/3 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 8.04 µg/L 13% of the EPA limit 60 µg/L
worst single sample: 8.4 µg/L | 3/3 | SYR4 | 2013–2019 |
| Barium | 231.9 µg/L 12% of the EPA limit 2000 µg/L
worst single sample: 232 µg/L | 2/2 | SYR4 | 2014–2017 |
| Dichloroacetic Acid | 2.165 µg/L No EPA limit set
worst single sample: 2.2 µg/L | 2/3 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 1.785 µg/L No EPA limit set
worst single sample: 1.8 µg/L | 2/3 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 3.4 pCi/L 68% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2017 |
| Combined Uranium | 3.4 µg/L 11% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2017 |
| Gross Alpha, Excl. Radon And U | 1.1 pCi/L 7.3% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2017 |
| Gross Beta Particle Activity | 5.9 pCi/L No EPA limit set | 1/1 | SYR4 | 2017 |
57 contaminants tested, none detected
Utility contact
Frequently asked questions about Sackett Lake Estates
Is Sackett Lake Estates tap water safe to drink?
EPA monitoring detected 16 contaminants in Sackett Lake Estates's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Sackett Lake Estates's water?
EPA monitoring detected Nitrate, Lead, Bromodichloromethane, Bromoform, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Sackett Lake Estates serve?
Sackett Lake Estates reports serving 80 people in New York, per its EPA record.
Has Sackett Lake Estates had any water quality violations?
The EPA has 4 violations on file for Sackett Lake Estates, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.