← New York

Tap water quality report

Emerald Green Lake Louise Marie Wc

EPA monitoring tested this supplier for 73 contaminants and detected 15. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

73
contaminants tested
15
detected
2,400
people served
0
health-based violations
Water source
Surface water
Ownership
Private
Counties served
Sullivan

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
451
violations on file
0
still open
ViolationTypeStatusPeriod
MON Monitoring Archived 2022-11-01 → 2022-11-30
MR Monitoring Archived 2020-04-01 → 2020-06-30
MR Monitoring Archived 2020-01-01 → 2020-03-31
MON Monitoring Resolved 2019-10-01 → 2019-10-31
MON Monitoring Resolved 2019-10-01 → 2019-10-31
MON Monitoring Resolved 2019-10-01 → 2019-10-31
MON Monitoring Resolved 2019-09-01 → 2019-09-30
MON Monitoring Resolved 2019-09-01 → 2019-09-30
MON Monitoring Resolved 2019-08-01 → 2019-08-31
MON Monitoring Resolved 2019-08-01 → 2019-08-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
16.7 µg/L
No EPA limit set
worst single sample: 17 µg/L
43/44 SYR4 2012–2019
Chloroform
52.9 µg/L
No EPA limit set
worst single sample: 65 µg/L
43/44 SYR4 2012–2019
Dibromochloromethane
4.36 µg/L
No EPA limit set
worst single sample: 5.2 µg/L
43/44 SYR4 2012–2019
Dichloroacetic Acid
18 µg/L
No EPA limit set
worst single sample: 29 µg/L
43/43 SYR4 2012–2019
TTHM
73.4 µg/L 92%
of the EPA limit 80 µg/L
worst single sample: 86 µg/L
43/44 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
35.9 µg/L 60%
of the EPA limit 60 µg/L
worst single sample: 57 µg/L
43/43 SYR4 2012–2019
Trichloroacetic Acid
16.89 µg/L
No EPA limit set
worst single sample: 28 µg/L
43/43 SYR4 2012–2019
Lead
0.0027 mg/L 18%
of the EPA limit 0.0150 mg/L
17/17 LCR 2023
Nitrate
150 µg/L 1.5%
of the EPA limit 10000 µg/L
12/28 SYR4 2012–2019
Barium
43.2 µg/L 2.2%
of the EPA limit 2000 µg/L
worst single sample: 44 µg/L
9/9 SYR4 2012–2019
Monochloroacetic Acid
3.34 µg/L
No EPA limit set
worst single sample: 3.5 µg/L
5/43 SYR4 2012–2019
Arsenic
0.6900 µg/L 6.9%
of the EPA limit 10 µg/L
worst single sample: 0.7000 µg/L
2/9 SYR4 2012–2019
Dibromoacetic Acid
1.9275 µg/L
No EPA limit set
worst single sample: 2 µg/L
2/43 SYR4 2012–2019
Gross Beta Particle Activity
1.5 pCi/L
No EPA limit set
1/2 SYR4 2017–2019
Monobromoacetic Acid
0.5600 µg/L
No EPA limit set
1/43 SYR4 2012–2019
58 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined Radium (-226 And -228)Combined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneFluorideGross Alpha, Excl. Radon And UHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
WOERNER, NICK
Phone
845-706-7991
Email
[email protected]

Frequently asked questions about Emerald Green Lake Louise Marie Wc

Is Emerald Green Lake Louise Marie Wc tap water safe to drink?

EPA monitoring detected 15 contaminants in Emerald Green Lake Louise Marie Wc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Emerald Green Lake Louise Marie Wc's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, Dichloroacetic Acid, TTHM, and others. The full list with the level and data source for each is above.

How many people does Emerald Green Lake Louise Marie Wc serve?

Emerald Green Lake Louise Marie Wc reports serving 2,400 people in New York, per its EPA record.

Has Emerald Green Lake Louise Marie Wc had any water quality violations?

The EPA has 451 violations on file for Emerald Green Lake Louise Marie Wc, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.