Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 1994-09-01 → 1994-09-30 |
| MR | Monitoring | Resolved | 1996-01-01 |
| MR | Monitoring | Resolved | 1996-01-01 |
| MR | Monitoring | Resolved | 1994-04-01 → 1994-06-30 |
| MR | Monitoring | Resolved | 1994-04-01 → 1994-06-30 |
| MR | Monitoring | Resolved | 1994-04-01 → 1994-06-30 |
| MR | Monitoring | Resolved | 1994-04-01 → 1994-06-30 |
| MR | Monitoring | Resolved | 1994-04-01 → 1994-06-30 |
| MR | Monitoring | Resolved | 1994-04-01 → 1994-06-30 |
| MR | Monitoring | Resolved | 1994-04-01 → 1994-06-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 6335 µg/L 63% of the EPA limit 10000 µg/L
worst single sample: 8400 µg/L | 394/406 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 6200 µg/L 62% of the EPA limit 10000 µg/L
worst single sample: 7600 µg/L | 82/92 | SYR4 | 2012–2019 |
| Barium | 39 µg/L 2% of the EPA limit 2000 µg/L
worst single sample: 40.4 µg/L | 80/82 | SYR4 | 2012–2019 |
| cis-1,2-Dichloroethylene | 1.182 µg/L 1.7% of the EPA limit 70 µg/L
worst single sample: 1.2 µg/L | 37/477 | SYR4 | 2012–2019 |
| Copper | 224 µg/L 17% of the EPA limit 1300 µg/L
worst single sample: 590 µg/L | 35/77 | SYR4 | 2012–2019 |
| Trichloroethylene | 0.9700 µg/L 19% of the EPA limit 5 µg/L
worst single sample: 1.2 µg/L | 31/479 | SYR4 | 2012–2019 |
| Lead | 7.1 µg/L 47% of the EPA limit 15 µg/L
worst single sample: 9.4 µg/L | 27/84 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 2.2355 pCi/L No EPA limit set
worst single sample: 3.37 pCi/L | 22/23 | SYR4 | 2013–2019 |
| Tetrachloroethylene | 19.95 µg/L 399% of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 20 µg/L | 22/450 | SYR4 | 2012–2019 |
| Combined Uranium | 2.07525 µg/L 6.9% of the EPA limit 30 µg/L
worst single sample: 5.08 µg/L | 18/21 | SYR4 | 2013–2019 |
| Ethylene Dibromide | 0.0200 µg/L 40% of the EPA limit 0.0500 µg/L | 17/174 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2023 |
| Combined Radium (-226 And -228) | 2.0395 pCi/L 41% of the EPA limit 5 pCi/L
worst single sample: 2.11 pCi/L | 4/28 | SYR4 | 2013–2019 |
| 1,1-Dichloroethylene | 0.5950 µg/L 8.5% of the EPA limit 7 µg/L
worst single sample: 0.6000 µg/L | 3/479 | SYR4 | 2012–2019 |
| Chromium | 7.095 µg/L 7.1% of the EPA limit 100 µg/L
worst single sample: 7.4 µg/L | 2/86 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 2.0315 pCi/L 14% of the EPA limit 15 pCi/L
worst single sample: 2.05 pCi/L | 2/20 | SYR4 | 2013–2019 |
| Antimony, Total | 0.6500 µg/L 11% of the EPA limit 6 µg/L | 1/80 | SYR4 | 2012–2019 |
| Arsenic | 3.2 µg/L 32% of the EPA limit 10 µg/L | 1/82 | SYR4 | 2012–2019 |
| TTHM | 6.74 µg/L 8.4% of the EPA limit 80 µg/L | 1/147 | SYR4 | 2012–2019 |
| Toluene | 0.9000 µg/L 0.1% of the EPA limit 1000 µg/L | 1/479 | SYR4 | 2012–2019 |
86 contaminants tested, none detected
Utility contact
Frequently asked questions about Roslyn Wd
Is Roslyn Wd tap water safe to drink?
EPA monitoring detected 22 contaminants in Roslyn Wd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Roslyn Wd's water?
EPA monitoring detected Nitrate, Nitrate-Nitrite, Barium, cis-1,2-Dichloroethylene, Copper, and others. The full list with the level and data source for each is above.
How many people does Roslyn Wd serve?
Roslyn Wd reports serving 17,000 people in New York, per its EPA record.
Has Roslyn Wd had any water quality violations?
The EPA has 56 violations on file for Roslyn Wd, of which 1 is health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.