← New York

Tap water quality report

Wa of Great Neck North

EPA monitoring tested this supplier for 112 contaminants and detected 34. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

112
contaminants tested
34
detected
31,400
people served
2
health-based violations
Water source
Ground water
Ownership
Mixed public/private

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

2
health-based violations
13
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 1994-11-01 → 1994-11-30
MCL Health-based Archived 1994-07-01 → 1994-07-31
MR Monitoring Resolved 2012-10-01 → 2012-12-31
MR Monitoring Resolved 2012-10-01 → 2012-12-31
MR Monitoring Resolved 2012-10-01 → 2012-12-31
MR Monitoring Resolved 2012-10-01 → 2012-12-31
MR Monitoring Resolved 2003-01-01 → 2003-12-31
MR Monitoring Resolved 2003-01-01 → 2003-12-31
MR Monitoring Resolved 2003-01-01 → 2003-12-31
MR Monitoring Resolved 2002-11-01 → 2002-11-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Trichloroethylene
5.909 µg/L 118%
of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 8.6 µg/L
395/1161 SYR4 2012–2019
Tetrachloroethylene
14.68 µg/L 294%
of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 19 µg/L
357/1160 SYR4 2012–2019
cis-1,2-Dichloroethylene
8.125 µg/L 12%
of the EPA limit 70 µg/L
worst single sample: 20.9 µg/L
296/1161 SYR4 2012–2019
Nitrate
3677.5 µg/L 37%
of the EPA limit 10000 µg/L
worst single sample: 7300 µg/L
196/202 SYR4 2012–2019
1,1-Dichloroethylene
0.9100 µg/L 13%
of the EPA limit 7 µg/L
worst single sample: 1.2 µg/L
121/1161 SYR4 2012–2019
Nitrate-Nitrite
3652 µg/L 37%
of the EPA limit 10000 µg/L
worst single sample: 4400 µg/L
99/99 SYR4 2012–2019
Barium
66.33 µg/L 3.3%
of the EPA limit 2000 µg/L
worst single sample: 70 µg/L
98/99 SYR4 2012–2019
Bromoform
5.399 µg/L
No EPA limit set
worst single sample: 9 µg/L
84/434 SYR4 2012–2019
TTHM
8.388 µg/L 10%
of the EPA limit 80 µg/L
worst single sample: 59 µg/L
77/403 SYR4 2012–2019
Dibromochloromethane
2.796 µg/L
No EPA limit set
worst single sample: 6.9 µg/L
49/434 SYR4 2012–2019
Copper
54.6 µg/L 4.2%
of the EPA limit 1300 µg/L
worst single sample: 74 µg/L
29/100 SYR4 2012–2019
Combined Uranium
1.39017 µg/L 4.6%
of the EPA limit 30 µg/L
worst single sample: 1.40805 µg/L
17/20 SYR4 2013–2019
Gross Beta Particle Activity
2.9315 pCi/L
No EPA limit set
worst single sample: 2.99 pCi/L
14/14 SYR4 2016–2019
Fluoride
220 µg/L 5.5%
of the EPA limit 4000 µg/L
13/100 SYR4 2012–2019
Bromodichloromethane
1.9745 µg/L
No EPA limit set
worst single sample: 2.6 µg/L
10/433 SYR4 2012–2019
Lead
0.0030 mg/L 20%
of the EPA limit 0.0150 mg/L
10/10 LCR 2025
Arsenic
17.6 µg/L 176%
of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 18 µg/L
9/124 SYR4 2012–2019
Lead
1.82 µg/L 12%
of the EPA limit 15 µg/L
worst single sample: 2 µg/L
7/101 SYR4 2012–2019
Combined Radium (-226 And -228)
2.055 pCi/L 41%
of the EPA limit 5 pCi/L
worst single sample: 2.24 pCi/L
6/20 SYR4 2013–2019
Toluene
1.325 µg/L 0.1%
of the EPA limit 1000 µg/L
worst single sample: 1.4 µg/L
6/1161 SYR4 2012–2019
Chloroform
0.5520 µg/L
No EPA limit set
worst single sample: 0.5600 µg/L
5/434 SYR4 2012–2019
1,1,2-Trichloroethane
0.6685 µg/L 13%
of the EPA limit 5 µg/L
worst single sample: 0.6700 µg/L
4/1161 SYR4 2012–2019
Carbon Tetrachloride
0.8790 µg/L 18%
of the EPA limit 5 µg/L
worst single sample: 0.9100 µg/L
3/1161 SYR4 2012–2019
Heptachlor Epoxide
0.0273 µg/L 14%
of the EPA limit 0.2000 µg/L
worst single sample: 0.0280 µg/L
3/102 SYR4 2012–2019
1,1,1-Trichloroethane
0.5000 µg/L 0.3%
of the EPA limit 200 µg/L
2/1161 SYR4 2012–2019
Nitrite
2473 µg/L 247%
of the EPA limit, at the 95th percentile of samples — 1000 µg/L
worst single sample: 2480 µg/L
2/99 SYR4 2012–2019
Selenium
5.815 µg/L 12%
of the EPA limit 50 µg/L
worst single sample: 6 µg/L
2/100 SYR4 2012–2019
Beryllium, Total
10 µg/L 250%
of the EPA limit, at the 95th percentile of samples — 4 µg/L
1/100 SYR4 2012–2019
Cyanide
16.8 µg/L 8.4%
of the EPA limit 200 µg/L
1/100 SYR4 2012–2019
Chlordane
0.2100 µg/L 11%
of the EPA limit 2 µg/L
1/99 SYR4 2012–2019
Di(2-ethylhexyl) Phthalate
0.6000 µg/L 10%
of the EPA limit 6 µg/L
1/90 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
0.2010 pCi/L 1.3%
of the EPA limit 15 pCi/L
1/18 SYR4 2013–2019
Mercury
0.5900 µg/L 30%
of the EPA limit 2 µg/L
1/100 SYR4 2012–2019
Vinyl Chloride
1.1 µg/L 55%
of the EPA limit 2 µg/L
1/1161 SYR4 2012–2019
78 contaminants tested, none detected
1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneChlorobenzeneCadmiumCarbofuranChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDibromoacetic AcidDichloroacetic AcidDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHexachlorocyclopentadieneLassoMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneThallium, TotalTotal Haloacetic Acids (HAA5)Total Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
GRAZIANO, GREG
Phone
516-487-7973
Email
[email protected]

Frequently asked questions about Wa of Great Neck North

Is Wa of Great Neck North tap water safe to drink?

EPA monitoring detected 34 contaminants in Wa of Great Neck North's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Wa of Great Neck North's water?

EPA monitoring detected Trichloroethylene, Tetrachloroethylene, cis-1,2-Dichloroethylene, Nitrate, 1,1-Dichloroethylene, and others. The full list with the level and data source for each is above.

How many people does Wa of Great Neck North serve?

Wa of Great Neck North reports serving 31,400 people in New York, per its EPA record.

Has Wa of Great Neck North had any water quality violations?

The EPA has 13 violations on file for Wa of Great Neck North, of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.