← New York

Tap water quality report

Long Beach City

EPA monitoring tested this supplier for 112 contaminants and detected 19. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

112
contaminants tested
19
detected
35,000
people served
12
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Nassau

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

12
health-based violations
20
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2019-06-01 → 2019-06-30
MCL Health-based Resolved 2019-06-01 → 2019-06-30
MCL Health-based Resolved 2019-06-01 → 2019-06-30
MCL Health-based Resolved 2019-06-01 → 2019-06-30
MCL Health-based Resolved 2014-07-01 → 2014-07-31
MCL Health-based Resolved 2014-07-01 → 2014-07-31
MCL Health-based Resolved 2014-07-01 → 2014-07-31
MCL Health-based Resolved 2014-07-01 → 2014-07-31
MCL Health-based Resolved 2004-06-01 → 2004-06-30
MCL Health-based Resolved 2004-06-01 → 2004-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Beryllium, Total
2.2245 µg/L 56%
of the EPA limit 4 µg/L
worst single sample: 6.64 µg/L
532/625 SYR4 2012–2019
Barium
50.95 µg/L 2.5%
of the EPA limit 2000 µg/L
worst single sample: 100 µg/L
48/50 SYR4 2012–2019
Copper
52.1 µg/L 4%
of the EPA limit 1300 µg/L
worst single sample: 53.2 µg/L
30/53 SYR4 2012–2019
Chloroform
2.642 µg/L
No EPA limit set
worst single sample: 2.88 µg/L
18/21 SYR4 2013–2019
Combined Uranium
1.158 µg/L 3.9%
of the EPA limit 30 µg/L
worst single sample: 1.2 µg/L
13/14 SYR4 2013–2016
Bromodichloromethane
1.85 µg/L
No EPA limit set
worst single sample: 1.9 µg/L
11/21 SYR4 2013–2019
Dibromochloromethane
1.35 µg/L
No EPA limit set
worst single sample: 1.5 µg/L
11/21 SYR4 2013–2019
Lead
0.0011 mg/L 7.3%
of the EPA limit 0.0150 mg/L
9/9 LCR 2023
Gross Beta Particle Activity
4.555 pCi/L
No EPA limit set
worst single sample: 4.94 pCi/L
6/8 SYR4 2016
TTHM
5.8 µg/L 7.2%
of the EPA limit 80 µg/L
worst single sample: 6 µg/L
6/6 SYR4 2017–2019
Lead
2.07 µg/L 14%
of the EPA limit 15 µg/L
worst single sample: 2.1 µg/L
5/52 SYR4 2012–2019
Nitrate
100 µg/L 1%
of the EPA limit 10000 µg/L
4/112 SYR4 2012–2019
Bromoform
1.28 µg/L
No EPA limit set
worst single sample: 1.3 µg/L
3/21 SYR4 2013–2019
Fluoride
119 µg/L 3%
of the EPA limit 4000 µg/L
worst single sample: 120 µg/L
2/50 SYR4 2012–2019
Pentachlorophenol
0.1165 µg/L 12%
of the EPA limit 1 µg/L
worst single sample: 0.1200 µg/L
2/34 SYR4 2012–2018
Lithium
28.4 µg/L
No EPA limit set
2/2 UCMR-5 2024
Combined Radium (-226 And -228)
1.08 pCi/L 22%
of the EPA limit 5 pCi/L
1/14 SYR4 2013–2016
Nitrate-Nitrite
100 µg/L 1%
of the EPA limit 10000 µg/L
1/34 SYR4 2012–2016
Thallium, Total
0.3720 µg/L 19%
of the EPA limit 2 µg/L
1/50 SYR4 2012–2019
93 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDichloroacetic AcidDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPicloramSeleniumSimazineStyreneTetrachloroethyleneTolueneTotal Haloacetic Acids (HAA5)Total Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BERNOWICH, CHARLES
Phone
516-431-5288
Email
[email protected]

Frequently asked questions about Long Beach City

Is Long Beach City tap water safe to drink?

EPA monitoring detected 19 contaminants in Long Beach City's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Long Beach City's water?

EPA monitoring detected Beryllium, Total, Barium, Copper, Chloroform, Combined Uranium, and others. The full list with the level and data source for each is above.

How many people does Long Beach City serve?

Long Beach City reports serving 35,000 people in New York, per its EPA record.

Has Long Beach City had any water quality violations?

The EPA has 20 violations on file for Long Beach City, of which 12 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.