Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2007-05-01 → 2007-05-31 |
| MCL | Health-based | Resolved | 2007-05-01 → 2007-05-31 |
| MCL | Health-based | Resolved | 2007-05-01 → 2007-05-31 |
| MCL | Health-based | Resolved | 2007-05-01 → 2007-05-31 |
| RPT | Monitoring | Resolved | 2024-10-17 |
| MR | Monitoring | Resolved | 2016-01-01 |
| MR | Monitoring | Resolved | 2016-01-01 |
| MR | Monitoring | Resolved | 2016-01-01 |
| MR | Monitoring | Resolved | 2016-01-01 |
| MR | Monitoring | Resolved | 2012-10-01 → 2012-12-31 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| PFOS | 0.0047 µg/L | 1/4 | 2024 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Tetrachloroethylene | 14.425 µg/L 289% of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 19.7 µg/L | 146/595 | SYR4 | 2012–2019 |
| Trichloroethylene | 17.02 µg/L 340% of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 19.6 µg/L | 139/600 | SYR4 | 2012–2019 |
| cis-1,2-Dichloroethylene | 4 µg/L 5.7% of the EPA limit 70 µg/L
worst single sample: 5.8 µg/L | 106/607 | SYR4 | 2012–2019 |
| Nitrate | 1933 µg/L 19% of the EPA limit 10000 µg/L
worst single sample: 2700 µg/L | 80/152 | SYR4 | 2012–2019 |
| Barium | 16 µg/L 0.8% of the EPA limit 2000 µg/L
worst single sample: 18 µg/L | 73/74 | SYR4 | 2012–2019 |
| 1,1-Dichloroethylene | 3.132 µg/L 45% of the EPA limit 7 µg/L
worst single sample: 4.5 µg/L | 70/607 | SYR4 | 2012–2019 |
| Copper | 70.4 µg/L 5.4% of the EPA limit 1300 µg/L
worst single sample: 577 µg/L | 59/76 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 1966 µg/L 20% of the EPA limit 10000 µg/L
worst single sample: 2700 µg/L | 39/74 | SYR4 | 2012–2019 |
| 1,1,1-Trichloroethane | 3.515 µg/L 1.8% of the EPA limit 200 µg/L
worst single sample: 3.7 µg/L | 38/607 | SYR4 | 2012–2019 |
| Lead | 6.17 µg/L 41% of the EPA limit 15 µg/L
worst single sample: 49.7 µg/L | 27/73 | SYR4 | 2012–2019 |
| Vinyl Chloride | 2.2 µg/L 110% of the EPA limit, at the 95th percentile of samples — 2 µg/L
worst single sample: 2.3 µg/L | 26/607 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 4.158 pCi/L 83% of the EPA limit 5 pCi/L
worst single sample: 4.28 pCi/L | 25/36 | SYR4 | 2013–2019 |
| Combined Uranium | 5.81353 µg/L 19% of the EPA limit 30 µg/L
worst single sample: 6.0643 µg/L | 22/34 | SYR4 | 2013–2019 |
| Gross Beta Particle Activity | 4.47 pCi/L No EPA limit set
worst single sample: 4.72 pCi/L | 21/21 | SYR4 | 2013–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 18/18 | LCR | 2025 |
| Thallium, Total | 0.6320 µg/L 32% of the EPA limit 2 µg/L
worst single sample: 0.7600 µg/L | 9/73 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 5.587 pCi/L 37% of the EPA limit 15 pCi/L
worst single sample: 6.1 pCi/L | 7/38 | SYR4 | 2013–2019 |
| Benzene | 0.6670 µg/L 13% of the EPA limit 5 µg/L
worst single sample: 0.6700 µg/L | 4/607 | SYR4 | 2012–2019 |
| 1,1,2-Trichloroethane | 1.1 µg/L 22% of the EPA limit 5 µg/L | 1/607 | SYR4 | 2012–2019 |
| Arsenic | 1.5 µg/L 15% of the EPA limit 10 µg/L | 1/75 | SYR4 | 2012–2019 |
| Carbon Tetrachloride | 0.5000 µg/L 10% of the EPA limit 5 µg/L | 1/607 | SYR4 | 2012–2019 |
| Selenium | 2 µg/L 4% of the EPA limit 50 µg/L | 1/75 | SYR4 | 2012–2019 |
88 contaminants tested, none detected
Utility contact
Frequently asked questions about Hempstead
Is Hempstead tap water safe to drink?
EPA monitoring detected 23 contaminants in Hempstead's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Hempstead's water?
EPA monitoring detected Tetrachloroethylene, Trichloroethylene, cis-1,2-Dichloroethylene, Nitrate, Barium, and others. The full list with the level and data source for each is above.
How many people does Hempstead serve?
Hempstead reports serving 56,000 people in New York, per its EPA record.
Has Hempstead had any water quality violations?
The EPA has 229 violations on file for Hempstead, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.