← New York

Tap water quality report

Four Corners Water Company

EPA monitoring tested this supplier for 48 contaminants and detected 18. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

48
contaminants tested
18
detected
750
people served
0
health-based violations
Water source
Ground water under surface influence
Ownership
Local government
Counties served
Dutchess

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
155
violations on file
0
still open
ViolationTypeStatusPeriod
Other Monitoring Resolved 2015-07-01
Other Monitoring Resolved 2015-07-01
Other Monitoring Resolved 2015-07-01
Other Monitoring Resolved 2015-07-01
Other Monitoring Resolved 2015-07-01
Other Monitoring Resolved 2015-07-01
Other Monitoring Resolved 2015-07-01
MR Monitoring Resolved 2011-07-01 → 2011-09-30
MR Monitoring Resolved 2011-07-01 → 2011-09-30
MR Monitoring Resolved 2011-07-01 → 2011-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
2200 µg/L 22%
of the EPA limit 10000 µg/L
worst single sample: 2310 µg/L
56/56 SYR4 2012–2019
Dichloroacetic Acid
6.611 µg/L
No EPA limit set
worst single sample: 8.27 µg/L
15/15 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
10.697 µg/L 18%
of the EPA limit 60 µg/L
worst single sample: 12.79 µg/L
15/15 SYR4 2012–2019
Bromodichloromethane
6.3155 µg/L
No EPA limit set
worst single sample: 6.53 µg/L
14/15 SYR4 2012–2019
Chloroform
12.365 µg/L
No EPA limit set
worst single sample: 14.9 µg/L
14/15 SYR4 2012–2019
Dibromochloromethane
3.94 µg/L
No EPA limit set
worst single sample: 4.2 µg/L
14/15 SYR4 2012–2019
TTHM
20.925 µg/L 26%
of the EPA limit 80 µg/L
worst single sample: 24.5 µg/L
14/15 SYR4 2012–2019
Barium
23.8 µg/L 1.2%
of the EPA limit 2000 µg/L
worst single sample: 26 µg/L
12/12 SYR4 2012–2019
Lead
0.0060 mg/L 40%
of the EPA limit 0.0150 mg/L
10/10 LCR 2026
Trichloroacetic Acid
3.611 µg/L
No EPA limit set
worst single sample: 4.52 µg/L
10/14 SYR4 2012–2019
Combined Uranium
3.47848 µg/L 12%
of the EPA limit 30 µg/L
worst single sample: 3.59 µg/L
6/6 SYR4 2012–2016
Chromium
20.02 µg/L 20%
of the EPA limit 100 µg/L
worst single sample: 22 µg/L
5/12 SYR4 2012–2019
Dibromoacetic Acid
1.36 µg/L
No EPA limit set
worst single sample: 1.4 µg/L
5/15 SYR4 2012–2019
Gross Beta Particle Activity
3.15 pCi/L
No EPA limit set
worst single sample: 3.32 pCi/L
5/6 SYR4 2012–2016
Combined Radium (-226 And -228)
1.3995 pCi/L 28%
of the EPA limit 5 pCi/L
worst single sample: 1.44 pCi/L
4/5 SYR4 2012–2016
Bromoform
0.5930 µg/L
No EPA limit set
worst single sample: 0.6000 µg/L
3/15 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
1.807 pCi/L 12%
of the EPA limit 15 pCi/L
worst single sample: 1.83 pCi/L
3/3 SYR4 2012
Monobromoacetic Acid
2.95 µg/L
No EPA limit set
worst single sample: 3 µg/L
2/15 SYR4 2012–2019
30 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalArsenicBenzeneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideDichloromethaneEthylbenzeneFluorideMercuryMonochloroacetic AcidSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
TOWN OF EAST FISHKILL
Phone
845-221-4303
Email
[email protected]

Frequently asked questions about Four Corners Water Company

Is Four Corners Water Company tap water safe to drink?

EPA monitoring detected 18 contaminants in Four Corners Water Company's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Four Corners Water Company's water?

EPA monitoring detected Nitrate, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.

How many people does Four Corners Water Company serve?

Four Corners Water Company reports serving 750 people in New York, per its EPA record.

Has Four Corners Water Company had any water quality violations?

The EPA has 155 violations on file for Four Corners Water Company, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.