EPA monitoring tested this supplier for 75 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

75
contaminants tested
20
detected
187
people served
10
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Dutchess

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

10
health-based violations
61
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2009-04-01 → 2009-06-30
MCL Health-based Resolved 2009-04-01 → 2009-06-30
MCL Health-based Resolved 2009-04-01 → 2009-06-30
MCL Health-based Resolved 2008-11-01 → 2008-11-30
MCL Health-based Resolved 2008-11-01 → 2008-11-30
MCL Health-based Resolved 2008-11-01 → 2008-11-30
MCL Health-based Resolved 2007-11-01 → 2007-11-30
MCL Health-based Resolved 2007-11-01 → 2007-11-30
MCL Health-based Resolved 1994-07-01 → 1994-09-30
MCL Health-based Resolved 1994-07-01 → 1994-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
6060 µg/L 61%
of the EPA limit 10000 µg/L
worst single sample: 6110 µg/L
54/56 SYR4 2012–2019
Lead
0.0017 mg/L 11%
of the EPA limit 0.0150 mg/L
20/20 LCR 2025
Gross Alpha, Excl. Radon And U
15.985 pCi/L 107%
of the EPA limit, at the 95th percentile of samples — 15 pCi/L
worst single sample: 19.03 pCi/L
15/18 SYR4 2012–2019
Combined Uranium
6.77131 µg/L 23%
of the EPA limit 30 µg/L
worst single sample: 7.4202 µg/L
14/18 SYR4 2012–2019
Combined Radium (-226 And -228)
7.173 pCi/L 143%
of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 8.13 pCi/L
12/18 SYR4 2012–2019
Nitrate-Nitrite
4730 µg/L 47%
of the EPA limit 10000 µg/L
worst single sample: 4800 µg/L
11/12 SYR4 2012–2014
Gross Beta Particle Activity
10.258 pCi/L
No EPA limit set
worst single sample: 11.25 pCi/L
9/16 SYR4 2012–2019
Barium
78.5 µg/L 3.9%
of the EPA limit 2000 µg/L
worst single sample: 82 µg/L
8/8 SYR4 2012–2015
Bromodichloromethane
2.625 µg/L
No EPA limit set
worst single sample: 2.7 µg/L
4/6 SYR4 2013–2019
Dibromochloromethane
3.115 µg/L
No EPA limit set
worst single sample: 3.4 µg/L
4/6 SYR4 2013–2019
TTHM
7.27 µg/L 9.1%
of the EPA limit 80 µg/L
worst single sample: 7.3 µg/L
4/6 SYR4 2013–2019
Dibromoacetic Acid
2.14 µg/L
No EPA limit set
worst single sample: 2.2 µg/L
3/6 SYR4 2013–2019
Fluoride
212 µg/L 5.3%
of the EPA limit 4000 µg/L
worst single sample: 220 µg/L
3/8 SYR4 2012–2015
Total Haloacetic Acids (HAA5)
2.92 µg/L 4.9%
of the EPA limit 60 µg/L
worst single sample: 3 µg/L
3/6 SYR4 2013–2019
Bromoform
1.6645 µg/L
No EPA limit set
worst single sample: 1.7 µg/L
2/6 SYR4 2013–2019
Arsenic
0.5000 µg/L 5%
of the EPA limit 10 µg/L
1/8 SYR4 2012–2015
Chloroform
2.9 µg/L
No EPA limit set
1/6 SYR4 2013–2019
Di(2-ethylhexyl) Phthalate
1.1 µg/L 18%
of the EPA limit 6 µg/L
1/7 SYR4 2013–2016
Dichloroacetic Acid
1 µg/L
No EPA limit set
1/6 SYR4 2013–2019
Trichloroacetic Acid
1 µg/L
No EPA limit set
1/6 SYR4 2013–2019
55 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
FAZZONE, THOMAS
Phone
845-373-9511
Email
[email protected]

Frequently asked questions about Maplebrook School

Is Maplebrook School tap water safe to drink?

EPA monitoring detected 20 contaminants in Maplebrook School's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Maplebrook School's water?

EPA monitoring detected Nitrate, Lead, Gross Alpha, Excl. Radon And U, Combined Uranium, Combined Radium (-226 And -228), and others. The full list with the level and data source for each is above.

How many people does Maplebrook School serve?

Maplebrook School reports serving 187 people in New York, per its EPA record.

Has Maplebrook School had any water quality violations?

The EPA has 61 violations on file for Maplebrook School, of which 10 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.