Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| MCL | Health-based | Archived | 2024-10-01 → 2024-12-31 |
| MCL | Health-based | Archived | 2024-10-01 → 2024-12-31 |
| MCL | Health-based | Archived | 2024-07-01 → 2024-09-30 |
| MCL | Health-based | Archived | 2024-07-01 → 2024-09-30 |
| MCL | Health-based | Archived | 2024-04-01 → 2024-06-30 |
| MCL | Health-based | Archived | 2024-04-01 → 2024-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 140 µg/L 1.4% of the EPA limit 10000 µg/L | 10/16 | SYR4 | 2012–2019 |
| Lead | 0.00090 mg/L 6% of the EPA limit 0.0150 mg/L | 7/7 | LCR | 2027 |
| Gross Beta Particle Activity | 7.724 pCi/L No EPA limit set
worst single sample: 8 pCi/L | 3/4 | SYR4 | 2013–2019 |
| Barium | 19.95 µg/L 1% of the EPA limit 2000 µg/L
worst single sample: 20 µg/L | 2/2 | SYR4 | 2014–2017 |
| Copper | 2.299 µg/L 0.2% of the EPA limit 1300 µg/L
worst single sample: 2.37 µg/L | 2/2 | SYR4 | 2017 |
| Combined Radium (-226 And -228) | 5.8135 pCi/L 116% of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 6.1 pCi/L | 2/4 | SYR4 | 2013–2019 |
| Combined Uranium | 7.44479 µg/L 25% of the EPA limit 30 µg/L
worst single sample: 7.49 µg/L | 2/3 | SYR4 | 2013–2019 |
| Arsenic | 0.6000 µg/L 6% of the EPA limit 10 µg/L | 1/2 | SYR4 | 2014–2017 |
| Bromoform | 1.3 µg/L No EPA limit set | 1/1 | SYR4 | 2014 |
| Chromium | 4 µg/L 4% of the EPA limit 100 µg/L | 1/2 | SYR4 | 2014–2017 |
| Dibromochloromethane | 1.5 µg/L No EPA limit set | 1/1 | SYR4 | 2014 |
| Gross Alpha, Excl. Radon And U | 5.62 pCi/L 37% of the EPA limit 15 pCi/L | 1/2 | SYR4 | 2013–2019 |
| Lead | 0.1500 µg/L 1% of the EPA limit 15 µg/L | 1/2 | SYR4 | 2017 |
| Selenium | 0.4000 µg/L 0.8% of the EPA limit 50 µg/L | 1/2 | SYR4 | 2014–2017 |
| TTHM | 2.8 µg/L 3.5% of the EPA limit 80 µg/L | 1/1 | SYR4 | 2014 |
| Total Haloacetic Acids (HAA5) | 19 µg/L 32% of the EPA limit 60 µg/L | 1/1 | SYR4 | 2014 |
| Trichloroacetic Acid | 19 µg/L No EPA limit set | 1/1 | SYR4 | 2014 |
58 contaminants tested, none detected
Utility contact
Frequently asked questions about Schreiber Water Works
Is Schreiber Water Works tap water safe to drink?
EPA monitoring detected 17 contaminants in Schreiber Water Works's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Schreiber Water Works's water?
EPA monitoring detected Nitrate, Lead, Gross Beta Particle Activity, Barium, Copper, and others. The full list with the level and data source for each is above.
How many people does Schreiber Water Works serve?
Schreiber Water Works reports serving 80 people in New York, per its EPA record.
Has Schreiber Water Works had any water quality violations?
The EPA has 41 violations on file for Schreiber Water Works, of which 22 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.