← New York

Tap water quality report

Hopewell Services Inc

EPA monitoring tested this supplier for 76 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

76
contaminants tested
17
detected
500
people served
0
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Dutchess

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
90
violations on file
5
still open
ViolationTypeStatusPeriod
Other Monitoring Resolved 2019-01-01
Other Monitoring Resolved 2019-01-01
MR Monitoring Archived 2012-07-01 → 2012-09-30
MR Monitoring Archived 2012-07-01 → 2012-09-30
MR Monitoring Archived 2012-07-01 → 2012-09-30
MR Monitoring Archived 2012-07-01 → 2012-09-30
MR Monitoring Resolved 2011-07-01
MR Monitoring Resolved 2011-07-01
MR Monitoring Resolved 2010-01-01 → 2012-12-31
MR Monitoring Resolved 2010-01-01 → 2012-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
3300 µg/L 33%
of the EPA limit 10000 µg/L
20/20 SYR4 2012–2019
Lead
0.0018 mg/L 12%
of the EPA limit 0.0150 mg/L
18/18 LCR 2023
Combined Uranium
5.46085 µg/L 18%
of the EPA limit 30 µg/L
worst single sample: 5.7514 µg/L
6/6 SYR4 2012–2019
Combined Radium (-226 And -228)
1.784 pCi/L 36%
of the EPA limit 5 pCi/L
worst single sample: 1.83 pCi/L
5/6 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
3.808 pCi/L 25%
of the EPA limit 15 pCi/L
worst single sample: 4.17 pCi/L
5/6 SYR4 2012–2019
Arsenic
3.768 µg/L 38%
of the EPA limit 10 µg/L
worst single sample: 3.81 µg/L
4/4 SYR4 2013–2019
Barium
106.21 µg/L 5.3%
of the EPA limit 2000 µg/L
worst single sample: 109 µg/L
4/4 SYR4 2013–2019
Bromoform
1.399 µg/L
No EPA limit set
worst single sample: 1.4 µg/L
3/3 SYR4 2014–2019
Dibromochloromethane
1.437 µg/L
No EPA limit set
worst single sample: 1.5 µg/L
3/3 SYR4 2014–2019
Gross Beta Particle Activity
4.662 pCi/L
No EPA limit set
worst single sample: 4.9 pCi/L
3/6 SYR4 2012–2019
TTHM
2.836 µg/L 3.5%
of the EPA limit 80 µg/L
worst single sample: 2.9 µg/L
3/3 SYR4 2014–2019
Nitrate-Nitrite
688.55 µg/L 6.9%
of the EPA limit 10000 µg/L
worst single sample: 700 µg/L
2/2 SYR4 2012–2013
Dibromoacetic Acid
1.3 µg/L
No EPA limit set
1/3 SYR4 2014–2019
Fluoride
130 µg/L 3.3%
of the EPA limit 4000 µg/L
1/4 SYR4 2013–2019
Nitrite
21 µg/L 2.1%
of the EPA limit 1000 µg/L
1/2 SYR4 2012–2013
Selenium
3.29 µg/L 6.6%
of the EPA limit 50 µg/L
1/4 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
1.3 µg/L 2.2%
of the EPA limit 60 µg/L
1/3 SYR4 2014–2019
59 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromodichloromethaneChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChloroformChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDichloroacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
TOWN OF EAST FISHKILL
Phone
845-221-4303
Email
[email protected]

Frequently asked questions about Hopewell Services Inc

Is Hopewell Services Inc tap water safe to drink?

EPA monitoring detected 17 contaminants in Hopewell Services Inc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Hopewell Services Inc's water?

EPA monitoring detected Nitrate, Lead, Combined Uranium, Combined Radium (-226 And -228), Gross Alpha, Excl. Radon And U, and others. The full list with the level and data source for each is above.

How many people does Hopewell Services Inc serve?

Hopewell Services Inc reports serving 500 people in New York, per its EPA record.

Has Hopewell Services Inc had any water quality violations?

The EPA has 90 violations on file for Hopewell Services Inc, of which 0 are health-based (a contaminant limit or required treatment was breached) and 5 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.