Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 1996-01-01 → 2004-12-31 |
| MR | Monitoring | Resolved | 1996-01-01 → 2004-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 2960 µg/L 30% of the EPA limit 10000 µg/L | 18/18 | SYR4 | 2012–2019 |
| Lead | 0.0022 mg/L 15% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2023 |
| Bromodichloromethane | 9.204 µg/L No EPA limit set
worst single sample: 10.2 µg/L | 5/5 | SYR4 | 2013–2019 |
| Chloroform | 33.16 µg/L No EPA limit set
worst single sample: 34.9 µg/L | 5/5 | SYR4 | 2013–2019 |
| Dibromochloromethane | 3.098 µg/L No EPA limit set
worst single sample: 3.18 µg/L | 5/5 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 2.996 µg/L No EPA limit set
worst single sample: 3 µg/L | 5/5 | SYR4 | 2013–2019 |
| TTHM | 44.3 µg/L 55% of the EPA limit 80 µg/L
worst single sample: 47.9 µg/L | 5/5 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 4.62 µg/L 7.7% of the EPA limit 60 µg/L
worst single sample: 4.72 µg/L | 5/5 | SYR4 | 2013–2019 |
| Barium | 31.81 µg/L 1.6% of the EPA limit 2000 µg/L
worst single sample: 31.9 µg/L | 3/3 | SYR4 | 2014–2017 |
| Trichloroacetic Acid | 1.94 µg/L No EPA limit set
worst single sample: 2.02 µg/L | 3/5 | SYR4 | 2013–2019 |
| Combined Uranium | 1.20892 µg/L 4% of the EPA limit 30 µg/L
worst single sample: 1.22 µg/L | 2/2 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 2.677 pCi/L 18% of the EPA limit 15 pCi/L
worst single sample: 2.68 pCi/L | 2/2 | SYR4 | 2013–2019 |
| Bromoform | 0.6230 µg/L No EPA limit set | 1/5 | SYR4 | 2013–2019 |
| Chromium | 14 µg/L 14% of the EPA limit 100 µg/L | 1/3 | SYR4 | 2014–2017 |
| Combined Radium (-226 And -228) | 0.3660 pCi/L 7.3% of the EPA limit 5 pCi/L | 1/2 | SYR4 | 2013–2019 |
| Gross Beta Particle Activity | 1.11 pCi/L No EPA limit set | 1/2 | SYR4 | 2013–2019 |
| Selenium | 3.76 µg/L 7.5% of the EPA limit 50 µg/L | 1/3 | SYR4 | 2014–2017 |
32 contaminants tested, none detected
Utility contact
Frequently asked questions about Hopewell Gardens
Is Hopewell Gardens tap water safe to drink?
EPA monitoring detected 17 contaminants in Hopewell Gardens's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Hopewell Gardens's water?
EPA monitoring detected Nitrate, Lead, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Hopewell Gardens serve?
Hopewell Gardens reports serving 300 people in New York, per its EPA record.
Has Hopewell Gardens had any water quality violations?
The EPA has 2 violations on file for Hopewell Gardens, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.