Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Unaddressed | 2024-10-17 |
| MCL | Health-based | Archived | 2004-08-01 → 2004-08-31 |
| MCL | Health-based | Archived | 2004-08-01 → 2004-08-31 |
| MCL | Health-based | Archived | 1998-12-01 → 1998-12-31 |
| MCL | Health-based | Archived | 1998-11-01 → 1998-11-30 |
| MR | Monitoring | Archived | 2025-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2025-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2025-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2025-01-01 → 2025-12-31 |
| RPT | Monitoring | Resolved | 2024-10-17 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 1800 µg/L 18% of the EPA limit 10000 µg/L
worst single sample: 2000 µg/L | 44/44 | SYR4 | 2012–2019 |
| Copper | 132 µg/L 10% of the EPA limit 1300 µg/L
worst single sample: 220 µg/L | 17/18 | SYR4 | 2012–2019 |
| Lead | 0.00077 mg/L 5.1% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2024 |
| Combined Uranium | 19 µg/L 63% of the EPA limit 30 µg/L | 10/10 | SYR4 | 2012–2018 |
| Fluoride | 1600 µg/L 40% of the EPA limit 4000 µg/L
worst single sample: 1800 µg/L | 9/9 | SYR4 | 2012–2018 |
| Nitrate-Nitrite | 1230 µg/L 12% of the EPA limit 10000 µg/L
worst single sample: 1300 µg/L | 8/8 | SYR4 | 2012–2018 |
| Gross Beta Particle Activity | 10.94 pCi/L No EPA limit set
worst single sample: 11 pCi/L | 7/7 | SYR4 | 2012–2016 |
| Arsenic | 12.25 µg/L 123% of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 13 µg/L | 6/7 | SYR4 | 2012–2018 |
| Combined Radium (-226 And -228) | 2.0625 pCi/L 41% of the EPA limit 5 pCi/L
worst single sample: 2.16 pCi/L | 6/6 | SYR4 | 2012–2015 |
| Total Haloacetic Acids (HAA5) | 19.8 µg/L 33% of the EPA limit 60 µg/L
worst single sample: 21 µg/L | 5/8 | SYR4 | 2012–2019 |
| Barium | 70.85 µg/L 3.5% of the EPA limit 2000 µg/L
worst single sample: 71 µg/L | 4/4 | SYR4 | 2012–2018 |
| Bromoform | 65.8 µg/L No EPA limit set
worst single sample: 70 µg/L | 4/15 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 13.04 µg/L No EPA limit set
worst single sample: 14 µg/L | 4/8 | SYR4 | 2012–2019 |
| TTHM | 73.8 µg/L 92% of the EPA limit 80 µg/L
worst single sample: 78 µg/L | 4/15 | SYR4 | 2012–2019 |
| Bromodichloromethane | 1.38 µg/L No EPA limit set
worst single sample: 1.4 µg/L | 3/15 | SYR4 | 2012–2019 |
| Chromium | 2.9 µg/L 2.9% of the EPA limit 100 µg/L
worst single sample: 3 µg/L | 3/4 | SYR4 | 2012–2018 |
| Dibromochloromethane | 6.79 µg/L No EPA limit set
worst single sample: 6.8 µg/L | 3/15 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 1.2 µg/L No EPA limit set | 2/8 | SYR4 | 2012–2019 |
| Selenium | 12.7 µg/L 25% of the EPA limit 50 µg/L
worst single sample: 13 µg/L | 2/4 | SYR4 | 2012–2018 |
| Lead | 3 µg/L 20% of the EPA limit 15 µg/L | 1/14 | SYR4 | 2012–2019 |
| Thallium, Total | 0.5000 µg/L 25% of the EPA limit 2 µg/L | 1/5 | SYR4 | 2012–2018 |
| Trichloroacetic Acid | 21 µg/L No EPA limit set | 1/8 | SYR4 | 2012–2019 |
61 contaminants tested, none detected
Utility contact
Frequently asked questions about Walker Lake Gid
Is Walker Lake Gid tap water safe to drink?
EPA monitoring detected 22 contaminants in Walker Lake Gid's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Walker Lake Gid's water?
EPA monitoring detected Nitrate, Copper, Lead, Combined Uranium, Fluoride, and others. The full list with the level and data source for each is above.
How many people does Walker Lake Gid serve?
Walker Lake Gid reports serving 450 people in Nevada, per its EPA record.
Has Walker Lake Gid had any water quality violations?
The EPA has 66 violations on file for Walker Lake Gid, of which 5 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.