Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2015-10-01 → 2015-12-31 |
| MCL | Health-based | Resolved | 2015-10-01 → 2015-12-31 |
| MCL | Health-based | Resolved | 2015-10-01 → 2015-12-31 |
| MCL | Health-based | Resolved | 2015-10-01 → 2015-12-31 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-09-30 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-09-30 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-09-30 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-09-30 |
| MCL | Health-based | Resolved | 2015-04-01 → 2015-06-30 |
| MCL | Health-based | Resolved | 2015-04-01 → 2015-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Arsenic | 30 µg/L 300% of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 44 µg/L | 120/120 | SYR4 | 2012–2019 |
| Combined Uranium | 37.1755 µg/L 124% of the EPA limit, at the 95th percentile of samples — 30 µg/L
worst single sample: 42.167 µg/L | 46/46 | SYR4 | 2012–2019 |
| Fluoride | 1395 µg/L 35% of the EPA limit 4000 µg/L
worst single sample: 2200 µg/L | 22/22 | SYR4 | 2012–2019 |
| Nitrate | 49000 µg/L 490% of the EPA limit, at the 95th percentile of samples — 10000 µg/L | 18/62 | SYR4 | 2012–2019 |
| Copper | 256 µg/L 20% of the EPA limit 1300 µg/L
worst single sample: 270 µg/L | 15/26 | SYR4 | 2012–2019 |
| Lead | 22.745 µg/L 152% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 57 µg/L | 14/22 | SYR4 | 2016–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2024 |
| Combined Radium (-226 And -228) | 2.27 pCi/L 45% of the EPA limit 5 pCi/L
worst single sample: 2.3 pCi/L | 7/13 | SYR4 | 2012–2019 |
| Barium | 107.2 µg/L 5.4% of the EPA limit 2000 µg/L
worst single sample: 110 µg/L | 5/5 | SYR4 | 2012–2018 |
| Gross Alpha, Excl. Radon And U | 3.075 pCi/L 21% of the EPA limit 15 pCi/L
worst single sample: 3.3 pCi/L | 4/11 | SYR4 | 2012–2014 |
| Nitrate-Nitrite | 1250 µg/L 13% of the EPA limit 10000 µg/L
worst single sample: 1300 µg/L | 2/9 | SYR4 | 2012–2018 |
| Chromium | 0.2900 µg/L 0.3% of the EPA limit 100 µg/L | 1/5 | SYR4 | 2012–2018 |
| Gross Beta Particle Activity | 11.5 pCi/L No EPA limit set | 1/1 | SYR4 | 2012 |
65 contaminants tested, none detected
Utility contact
Frequently asked questions about Alamo Sewer and Water Gid
Is Alamo Sewer and Water Gid tap water safe to drink?
EPA monitoring detected 13 contaminants in Alamo Sewer and Water Gid's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Alamo Sewer and Water Gid's water?
EPA monitoring detected Arsenic, Combined Uranium, Fluoride, Nitrate, Copper, and others. The full list with the level and data source for each is above.
How many people does Alamo Sewer and Water Gid serve?
Alamo Sewer and Water Gid reports serving 900 people in Nevada, per its EPA record.
Has Alamo Sewer and Water Gid had any water quality violations?
The EPA has 477 violations on file for Alamo Sewer and Water Gid, of which 65 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.