Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2005-10-01 → 2005-12-31 |
| MCL | Health-based | Resolved | 2005-10-01 → 2005-12-31 |
| MCL | Health-based | Resolved | 2005-10-01 → 2005-12-31 |
| MCL | Health-based | Resolved | 2005-10-01 → 2005-12-31 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-04-01 → 2005-06-30 |
| MCL | Health-based | Resolved | 2005-04-01 → 2005-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 12.024 µg/L No EPA limit set
worst single sample: 18.73 µg/L | 57/57 | SYR4 | 2012–2019 |
| Chloroform | 16.32 µg/L No EPA limit set
worst single sample: 21.69 µg/L | 57/57 | SYR4 | 2012–2019 |
| Dibromochloromethane | 8.526 µg/L No EPA limit set
worst single sample: 13.81 µg/L | 57/57 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 9.776 µg/L No EPA limit set
worst single sample: 14.1 µg/L | 57/57 | SYR4 | 2012–2019 |
| TTHM | 33.868 µg/L 42% of the EPA limit 80 µg/L
worst single sample: 49.97 µg/L | 57/57 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 16.776 µg/L 28% of the EPA limit 60 µg/L
worst single sample: 21.95 µg/L | 57/57 | SYR4 | 2012–2019 |
| Copper | 200.25 µg/L 15% of the EPA limit 1300 µg/L
worst single sample: 467 µg/L | 52/60 | SYR4 | 2012–2018 |
| Dibromoacetic Acid | 4.073 µg/L No EPA limit set
worst single sample: 4.89 µg/L | 52/57 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 5.415 µg/L No EPA limit set
worst single sample: 6.42 µg/L | 40/57 | SYR4 | 2012–2019 |
| Bromoform | 1.8225 µg/L No EPA limit set
worst single sample: 2.03 µg/L | 36/57 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 18/18 | LCR | 2024 |
| Lead | 10.2945 µg/L 69% of the EPA limit 15 µg/L
worst single sample: 12.7 µg/L | 18/60 | SYR4 | 2012–2018 |
| Nitrate-Nitrite | 555.5 µg/L 5.6% of the EPA limit 10000 µg/L
worst single sample: 560 µg/L | 10/10 | SYR4 | 2012–2019 |
| Nitrate | 460 µg/L 4.6% of the EPA limit 10000 µg/L | 4/4 | SYR4 | 2016–2019 |
| Lithium | 32 µg/L No EPA limit set | 4/4 | UCMR-5 | 2024 |
| Monochloroacetic Acid | 2.271 µg/L No EPA limit set
worst single sample: 2.28 µg/L | 2/57 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 1.486 µg/L 30% of the EPA limit 5 µg/L
worst single sample: 1.53 µg/L | 2/9 | SYR4 | 2012–2018 |
| Barium | 6.63 µg/L 0.3% of the EPA limit 2000 µg/L | 1/1 | SYR4 | 2018 |
| Combined Uranium | 1 µg/L 3.3% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2018 |
| Fluoride | 763 µg/L 19% of the EPA limit 4000 µg/L | 1/1 | SYR4 | 2018 |
| Nitrite | 19 µg/L 1.9% of the EPA limit 1000 µg/L | 1/2 | SYR4 | 2016–2019 |
| Trichloroethylene | 1 µg/L 20% of the EPA limit 5 µg/L | 1/8 | SYR4 | 2012–2018 |
| cis-1,2-Dichloroethylene | 1.14 µg/L 1.6% of the EPA limit 70 µg/L | 1/8 | SYR4 | 2012–2018 |
74 contaminants tested, none detected
Utility contact
Frequently asked questions about Valley City City of
Is Valley City City of tap water safe to drink?
EPA monitoring detected 23 contaminants in Valley City City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Valley City City of's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, Dichloroacetic Acid, TTHM, and others. The full list with the level and data source for each is above.
How many people does Valley City City of serve?
Valley City City of reports serving 6,585 people in North Dakota, per its EPA record.
Has Valley City City of had any water quality violations?
The EPA has 27 violations on file for Valley City City of, of which 27 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.