Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| MCL | Health-based | Resolved | 2006-10-01 → 2006-12-31 |
| MCL | Health-based | Resolved | 2006-10-01 → 2006-12-31 |
| MCL | Health-based | Resolved | 2006-10-01 → 2006-12-31 |
| MCL | Health-based | Resolved | 2006-10-01 → 2006-12-31 |
| MCL | Health-based | Resolved | 2006-07-01 → 2006-09-30 |
| MCL | Health-based | Resolved | 2006-07-01 → 2006-09-30 |
| MCL | Health-based | Resolved | 2006-07-01 → 2006-09-30 |
| MCL | Health-based | Resolved | 2006-07-01 → 2006-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 866 µg/L 67% of the EPA limit 1300 µg/L
worst single sample: 2750 µg/L | 76/99 | SYR4 | 2012–2018 |
| Total Haloacetic Acids (HAA5) | 28.25 µg/L 47% of the EPA limit 60 µg/L
worst single sample: 56 µg/L | 76/84 | SYR4 | 2012–2019 |
| TTHM | 40.6 µg/L 51% of the EPA limit 80 µg/L
worst single sample: 72 µg/L | 73/81 | SYR4 | 2012–2019 |
| Chloroform | 27.238 µg/L No EPA limit set
worst single sample: 41.47 µg/L | 64/72 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 17.55 µg/L No EPA limit set
worst single sample: 27 µg/L | 64/72 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 13.2 µg/L No EPA limit set
worst single sample: 29 µg/L | 58/72 | SYR4 | 2013–2019 |
| Lead | 24.1 µg/L 161% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 48 µg/L | 39/99 | SYR4 | 2012–2018 |
| Bromodichloromethane | 18.486 µg/L No EPA limit set
worst single sample: 24.96 µg/L | 37/72 | SYR4 | 2013–2019 |
| Lead | 0.0100 mg/L 67% of the EPA limit 0.0150 mg/L | 21/21 | LCR | 2025 |
| Monobromoacetic Acid | 3.2 µg/L No EPA limit set
worst single sample: 7 µg/L | 20/72 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 2.9 µg/L No EPA limit set
worst single sample: 5 µg/L | 15/72 | SYR4 | 2013–2019 |
| Dibromochloromethane | 7.0156 µg/L No EPA limit set
worst single sample: 7.052 µg/L | 15/72 | SYR4 | 2013–2019 |
| Fluoride | 680 µg/L 17% of the EPA limit 4000 µg/L
worst single sample: 810 µg/L | 14/14 | SYR4 | 2012–2018 |
| Monochloroacetic Acid | 6.35 µg/L No EPA limit set
worst single sample: 8 µg/L | 12/72 | SYR4 | 2013–2019 |
| Nitrate | 1336 µg/L 13% of the EPA limit 10000 µg/L | 8/62 | SYR4 | 2012–2019 |
| Lithium | 38.5 µg/L No EPA limit set | 7/8 | UCMR-5 | 2023 |
| Nitrate-Nitrite | 1311.4 µg/L 13% of the EPA limit 10000 µg/L
worst single sample: 1336 µg/L | 3/28 | SYR4 | 2012–2019 |
| Chromium | 25.4325 µg/L 25% of the EPA limit 100 µg/L
worst single sample: 25.55 µg/L | 2/14 | SYR4 | 2012–2018 |
| Bromoform | 4 µg/L No EPA limit set | 1/72 | SYR4 | 2013–2019 |
| Gross Beta Particle Activity | 6.3 pCi/L No EPA limit set | 1/1 | SYR4 | 2015 |
89 contaminants tested, none detected
Utility contact
Frequently asked questions about Pamlico County Water
Is Pamlico County Water tap water safe to drink?
EPA monitoring detected 20 contaminants in Pamlico County Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Pamlico County Water's water?
EPA monitoring detected Copper, Total Haloacetic Acids (HAA5), TTHM, Chloroform, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Pamlico County Water serve?
Pamlico County Water reports serving 19,665 people in North Carolina, per its EPA record.
Has Pamlico County Water had any water quality violations?
The EPA has 147 violations on file for Pamlico County Water, of which 66 are health-based (a contaminant limit or required treatment was breached) and 4 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.