← North Carolina

Tap water quality report

Hoke Co Regional Water

EPA monitoring tested this supplier for 109 contaminants and detected 33. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
33
detected
36,640
people served
28
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Hoke

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

28
health-based violations
1,522
violations on file
4
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-10-17
TT Health-based Resolved 2024-10-17
MCL Health-based Resolved 2005-10-01 → 2005-12-31
MCL Health-based Resolved 2005-10-01 → 2005-12-31
MCL Health-based Resolved 2005-10-01 → 2005-12-31
MCL Health-based Resolved 2005-10-01 → 2005-12-31
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFBS 0.0045 µg/L 5/26 2025
PFHXS 0.0032 µg/L 2/26 2025
PFOS 0.0048 µg/L 2/26 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
3085.7 µg/L 31%
of the EPA limit 10000 µg/L
worst single sample: 3545.8 µg/L
148/190 SYR4 2012–2019
Combined Radium (-226 And -228)
3.78 pCi/L 76%
of the EPA limit 5 pCi/L
worst single sample: 5.5 pCi/L
43/57 SYR4 2013–2019
TTHM
27.725 µg/L 35%
of the EPA limit 80 µg/L
worst single sample: 75 µg/L
36/93 SYR4 2012–2019
Dichloroacetic Acid
24.16 µg/L
No EPA limit set
worst single sample: 34 µg/L
25/72 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
38.48 µg/L 64%
of the EPA limit 60 µg/L
worst single sample: 59 µg/L
25/93 SYR4 2012–2019
Chloroform
41.486 µg/L
No EPA limit set
worst single sample: 49.25 µg/L
24/73 SYR4 2013–2019
Bromodichloromethane
17.03 µg/L
No EPA limit set
worst single sample: 19.47 µg/L
21/73 SYR4 2013–2019
Dibromochloromethane
5.64575 µg/L
No EPA limit set
worst single sample: 7.574 µg/L
16/73 SYR4 2013–2019
Gross Alpha, Excl. Radon And U
8.06 pCi/L 54%
of the EPA limit 15 pCi/L
worst single sample: 8.9 pCi/L
13/39 SYR4 2013–2019
Fluoride
451.1 µg/L 11%
of the EPA limit 4000 µg/L
worst single sample: 451.2 µg/L
11/38 SYR4 2013–2019
Nitrate-Nitrite
2865 µg/L 29%
of the EPA limit 10000 µg/L
worst single sample: 2920 µg/L
11/21 SYR4 2013–2019
Copper
71.23 µg/L 5.5%
of the EPA limit 1300 µg/L
worst single sample: 87.7 µg/L
10/60 SYR4 2014–2017
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
9/9 LCR 2025
Dibromoacetic Acid
4.925 µg/L
No EPA limit set
worst single sample: 6.5 µg/L
8/71 SYR4 2013–2019
Monobromoacetic Acid
2.27 µg/L
No EPA limit set
worst single sample: 2.3 µg/L
7/72 SYR4 2013–2019
Trichloroacetic Acid
20.6 µg/L
No EPA limit set
worst single sample: 23 µg/L
7/72 SYR4 2013–2019
Xylenes, Total
53.21 µg/L 0.5%
of the EPA limit 10000 µg/L
worst single sample: 65.2 µg/L
5/117 SYR4 2012–2019
Barium
26.55 µg/L 1.3%
of the EPA limit 2000 µg/L
worst single sample: 27 µg/L
4/37 SYR4 2013–2019
Nitrite
83.31 µg/L 8.3%
of the EPA limit 1000 µg/L
worst single sample: 85.2 µg/L
4/21 SYR4 2013–2019
Cyanide
7.76 µg/L 3.9%
of the EPA limit 200 µg/L
worst single sample: 7.8 µg/L
3/37 SYR4 2013–2019
Gross Beta Particle Activity
5.39 pCi/L
No EPA limit set
worst single sample: 5.5 pCi/L
3/14 SYR4 2013–2019
Monochloroacetic Acid
4.08 µg/L
No EPA limit set
worst single sample: 4.2 µg/L
3/72 SYR4 2013–2019
Atrazine
0.1323 µg/L 4.4%
of the EPA limit 3 µg/L
worst single sample: 0.1340 µg/L
2/101 SYR4 2013–2019
Ethylbenzene
8.10255 µg/L 1.2%
of the EPA limit 700 µg/L
worst single sample: 8.48 µg/L
2/117 SYR4 2012–2019
Lithium
12 µg/L
No EPA limit set
2/26 UCMR-5 2024
Bromoform
0.6600 µg/L
No EPA limit set
1/73 SYR4 2013–2019
Chromium
2.0053 µg/L 2%
of the EPA limit 100 µg/L
1/38 SYR4 2013–2019
Combined Uranium
1.49 µg/L 5%
of the EPA limit 30 µg/L
1/54 SYR4 2013–2019
Lead
4 µg/L 27%
of the EPA limit 15 µg/L
1/60 SYR4 2014–2017
Pentachlorophenol
0.0670 µg/L 6.7%
of the EPA limit 1 µg/L
1/99 SYR4 2013–2019
76 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfbaPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPfmbaPfmpaPFNAPFOAPfpeaPfpesPftaPftrdaPfunaPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
MCQUEEN, JAMES
Phone
910-848-0385
Email
[email protected]

Frequently asked questions about Hoke Co Regional Water

Is Hoke Co Regional Water tap water safe to drink?

EPA monitoring detected 33 contaminants in Hoke Co Regional Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Hoke Co Regional Water's water?

EPA monitoring detected Nitrate, Combined Radium (-226 And -228), TTHM, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Hoke Co Regional Water serve?

Hoke Co Regional Water reports serving 36,640 people in North Carolina, per its EPA record.

Has Hoke Co Regional Water had any water quality violations?

The EPA has 1522 violations on file for Hoke Co Regional Water, of which 28 are health-based (a contaminant limit or required treatment was breached) and 4 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.