Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2007-10-01 → 2007-12-31 |
| MCL | Health-based | Resolved | 2007-10-01 → 2007-12-31 |
| MCL | Health-based | Resolved | 2007-10-01 → 2007-12-31 |
| MCL | Health-based | Resolved | 2007-10-01 → 2007-12-31 |
| MCL | Health-based | Resolved | 2007-10-01 → 2007-12-31 |
| MCL | Health-based | Resolved | 2007-10-01 → 2007-12-31 |
| MCL | Health-based | Resolved | 2007-10-01 → 2007-12-31 |
| MCL | Health-based | Resolved | 2007-10-01 → 2007-12-31 |
| MCL | Health-based | Resolved | 2007-10-01 → 2007-12-31 |
| MCL | Health-based | Resolved | 2007-10-01 → 2007-12-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 7400 µg/L 74% of the EPA limit 10000 µg/L
worst single sample: 8400 µg/L | 680/752 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 7400 µg/L 74% of the EPA limit 10000 µg/L
worst single sample: 8400 µg/L | 340/376 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 5.2 pCi/L 104% of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 7.9 pCi/L | 64/119 | SYR4 | 2012–2019 |
| Heptachlor Epoxide | 0.0461 µg/L 23% of the EPA limit 0.2000 µg/L
worst single sample: 0.0660 µg/L | 51/141 | SYR4 | 2012–2019 |
| Copper | 728.7 µg/L 56% of the EPA limit 1300 µg/L
worst single sample: 1320 µg/L | 40/93 | SYR4 | 2013–2019 |
| Tetrachloroethylene | 4.42 µg/L 88% of the EPA limit 5 µg/L
worst single sample: 6.7 µg/L | 30/100 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 10.7 pCi/L No EPA limit set
worst single sample: 15.1 pCi/L | 26/36 | SYR4 | 2012–2018 |
| cis-1,2-Dichloroethylene | 1.5 µg/L 2.1% of the EPA limit 70 µg/L
worst single sample: 2.8 µg/L | 23/100 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2024 |
| TTHM | 7.05 µg/L 8.8% of the EPA limit 80 µg/L
worst single sample: 9.1 µg/L | 11/38 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.24 µg/L No EPA limit set
worst single sample: 2.8 µg/L | 8/30 | SYR4 | 2013–2019 |
| Lead | 20.55 µg/L 137% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 21 µg/L | 7/93 | SYR4 | 2013–2019 |
| Bromodichloromethane | 2.86 µg/L No EPA limit set
worst single sample: 3.2 µg/L | 5/30 | SYR4 | 2013–2019 |
| 1,2-DIBROMO-3-CHLOROPROPANE | 0.0414 µg/L 21% of the EPA limit 0.2000 µg/L
worst single sample: 0.0420 µg/L | 4/86 | SYR4 | 2014–2019 |
| Chloroform | 2.385 µg/L No EPA limit set
worst single sample: 2.4 µg/L | 4/30 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 2.525 µg/L No EPA limit set
worst single sample: 2.6 µg/L | 4/30 | SYR4 | 2013–2019 |
| Fluoride | 398.5 µg/L 10% of the EPA limit 4000 µg/L
worst single sample: 400 µg/L | 4/62 | SYR4 | 2012–2018 |
| Total Haloacetic Acids (HAA5) | 2.55 µg/L 4.3% of the EPA limit 60 µg/L
worst single sample: 2.6 µg/L | 3/38 | SYR4 | 2012–2019 |
| Antimony, Total | 4.78 µg/L 80% of the EPA limit 6 µg/L
worst single sample: 4.87 µg/L | 2/62 | SYR4 | 2012–2018 |
| Di(2-ethylhexyl) Phthalate | 3.04 µg/L 51% of the EPA limit 6 µg/L
worst single sample: 3.1 µg/L | 2/90 | SYR4 | 2014–2017 |
| Xylenes, Total | 1.2645 µg/L 0% of the EPA limit 10000 µg/L
worst single sample: 1.3 µg/L | 2/100 | SYR4 | 2012–2019 |
| Trichloroethylene | 0.5600 µg/L 11% of the EPA limit 5 µg/L | 1/100 | SYR4 | 2012–2019 |
79 contaminants tested, none detected
Utility contact
Frequently asked questions about Brookwood Comm Wtr
Is Brookwood Comm Wtr tap water safe to drink?
EPA monitoring detected 30 contaminants in Brookwood Comm Wtr's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Brookwood Comm Wtr's water?
EPA monitoring detected Nitrate, Nitrate-Nitrite, Combined Radium (-226 And -228), Heptachlor Epoxide, Copper, and others. The full list with the level and data source for each is above.
How many people does Brookwood Comm Wtr serve?
Brookwood Comm Wtr reports serving 15,380 people in North Carolina, per its EPA record.
Has Brookwood Comm Wtr had any water quality violations?
The EPA has 1508 violations on file for Brookwood Comm Wtr, of which 1342 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.