← Maryland

Tap water quality report

Town of Hurlock

EPA monitoring tested this supplier for 71 contaminants and detected 16. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

71
contaminants tested
16
detected
2,150
people served
6
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Dorchester

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

6
health-based violations
20
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-10-17
MCL Health-based Resolved 2009-11-01 → 2009-11-30
MCL Health-based Resolved 2009-11-01 → 2009-11-30
MCL Health-based Resolved 2009-11-01 → 2009-11-30
MCL Health-based Resolved 2009-11-01 → 2009-11-30
MCL Health-based Archived 1988-06-02 → 1989-03-30
RPT Monitoring Resolved 2024-10-17
MR Monitoring Resolved 2015-01-01 → 2017-12-31
MR Monitoring Resolved 2015-01-01 → 2017-12-31
MR Monitoring Resolved 2015-01-01 → 2017-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
7672 µg/L 77%
of the EPA limit 10000 µg/L
worst single sample: 7690 µg/L
24/24 SYR4 2012–2019
Lead
0.0067 mg/L 45%
of the EPA limit 0.0150 mg/L
13/13 LCR 2023
TTHM
34.667 µg/L 43%
of the EPA limit 80 µg/L
worst single sample: 42.78 µg/L
8/8 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
14.101 µg/L 24%
of the EPA limit 60 µg/L
worst single sample: 16.57 µg/L
7/8 SYR4 2013–2019
Chloroform
14.7 µg/L
No EPA limit set
worst single sample: 17.4 µg/L
5/6 SYR4 2013–2018
Bromodichloromethane
11.325 µg/L
No EPA limit set
worst single sample: 12.6 µg/L
4/5 SYR4 2013–2018
Bromoform
1.508 µg/L
No EPA limit set
worst single sample: 1.58 µg/L
4/6 SYR4 2013–2018
Dibromochloromethane
10.12 µg/L
No EPA limit set
worst single sample: 11.2 µg/L
4/5 SYR4 2013–2018
Dibromoacetic Acid
1.443 µg/L
No EPA limit set
worst single sample: 1.46 µg/L
3/4 SYR4 2013–2015
Dichloroacetic Acid
1.973 µg/L
No EPA limit set
worst single sample: 2.03 µg/L
3/4 SYR4 2013–2015
Trichloroacetic Acid
1.782 µg/L
No EPA limit set
worst single sample: 1.85 µg/L
3/4 SYR4 2013–2015
Monobromoacetic Acid
1.676 µg/L
No EPA limit set
worst single sample: 1.69 µg/L
2/4 SYR4 2013–2015
Monochloroacetic Acid
2.94 µg/L
No EPA limit set
worst single sample: 3 µg/L
2/5 SYR4 2013–2015
Chromium
1.2 µg/L 1.2%
of the EPA limit 100 µg/L
1/2 SYR4 2014–2018
Fluoride
520 µg/L 13%
of the EPA limit 4000 µg/L
1/2 SYR4 2014–2018
Gross Beta Particle Activity
5.4 pCi/L
No EPA limit set
1/1 SYR4 2017
55 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
GOULD, MICHAEL
Phone
410-943-3401
Email
[email protected]

Frequently asked questions about Town of Hurlock

Is Town of Hurlock tap water safe to drink?

EPA monitoring detected 16 contaminants in Town of Hurlock's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Town of Hurlock's water?

EPA monitoring detected Nitrate, Lead, TTHM, Total Haloacetic Acids (HAA5), Chloroform, and others. The full list with the level and data source for each is above.

How many people does Town of Hurlock serve?

Town of Hurlock reports serving 2,150 people in Maryland, per its EPA record.

Has Town of Hurlock had any water quality violations?

The EPA has 20 violations on file for Town of Hurlock, of which 6 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.