Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2022-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Fluoride | 1425 µg/L 36% of the EPA limit 4000 µg/L
worst single sample: 1500 µg/L | 16/16 | SYR4 | 2013–2019 |
| Barium | 23.95 µg/L 1.2% of the EPA limit 2000 µg/L
worst single sample: 35 µg/L | 14/17 | SYR4 | 2013–2019 |
| Lead | 0.0057 mg/L 38% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2025 |
| Gross Alpha, Excl. Radon And U | 11.36 pCi/L 76% of the EPA limit 15 pCi/L
worst single sample: 15.1 pCi/L | 12/26 | SYR4 | 2013–2019 |
| TTHM | 40.74 µg/L 51% of the EPA limit 80 µg/L
worst single sample: 51.5 µg/L | 9/12 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 6.255 pCi/L No EPA limit set
worst single sample: 6.5 pCi/L | 8/19 | SYR4 | 2013–2018 |
| Bromoform | 20.32 µg/L No EPA limit set
worst single sample: 23.8 µg/L | 7/13 | SYR4 | 2012–2015 |
| Combined Radium (-226 And -228) | 1.11 pCi/L 22% of the EPA limit 5 pCi/L
worst single sample: 1.2 pCi/L | 7/20 | SYR4 | 2014–2019 |
| Dibromochloromethane | 17.24 µg/L No EPA limit set
worst single sample: 17.7 µg/L | 5/13 | SYR4 | 2012–2015 |
| Chloroform | 21.65 µg/L No EPA limit set
worst single sample: 25.1 µg/L | 4/13 | SYR4 | 2012–2015 |
| Chromium | 4.685 µg/L 4.7% of the EPA limit 100 µg/L
worst single sample: 4.7 µg/L | 4/17 | SYR4 | 2013–2019 |
| Lithium | 16.4 µg/L No EPA limit set | 4/8 | UCMR-5 | 2025 |
| Bromodichloromethane | 11.5 µg/L No EPA limit set
worst single sample: 11.9 µg/L | 3/13 | SYR4 | 2012–2015 |
| Dibromoacetic Acid | 6.84 µg/L No EPA limit set
worst single sample: 7 µg/L | 2/7 | SYR4 | 2012–2014 |
| Nitrate | 100 µg/L 1% of the EPA limit 10000 µg/L | 2/54 | SYR4 | 2012–2018 |
| Total Haloacetic Acids (HAA5) | 8.995 µg/L 15% of the EPA limit 60 µg/L
worst single sample: 9.2 µg/L | 2/12 | SYR4 | 2012–2019 |
| Dichloromethane | 3.3 µg/L 66% of the EPA limit 5 µg/L | 1/18 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 1.3 µg/L No EPA limit set | 1/7 | SYR4 | 2012–2014 |
| Monobromoacetic Acid | 1.1 µg/L No EPA limit set | 1/7 | SYR4 | 2012–2014 |
| Selenium | 13 µg/L 26% of the EPA limit 50 µg/L | 1/17 | SYR4 | 2013–2019 |
| Toluene | 7.1 µg/L 0.7% of the EPA limit 1000 µg/L | 1/18 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 1.1 µg/L No EPA limit set | 1/7 | SYR4 | 2012–2014 |
82 contaminants tested, none detected
Utility contact
Frequently asked questions about Naval Support Facility, Indian Head
Is Naval Support Facility, Indian Head tap water safe to drink?
EPA monitoring detected 22 contaminants in Naval Support Facility, Indian Head's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Naval Support Facility, Indian Head's water?
EPA monitoring detected Fluoride, Barium, Lead, Gross Alpha, Excl. Radon And U, TTHM, and others. The full list with the level and data source for each is above.
How many people does Naval Support Facility, Indian Head serve?
Naval Support Facility, Indian Head reports serving 3,321 people in Maryland, per its EPA record.
Has Naval Support Facility, Indian Head had any water quality violations?
The EPA has 58 violations on file for Naval Support Facility, Indian Head, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.