Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Unaddressed | 2025-01-31 |
| TT | Health-based | Unaddressed | 2025-01-31 |
| TT | Health-based | Addressed | 2024-10-17 |
| TT | Health-based | Resolved | 2022-07-02 |
| TT | Health-based | Resolved | 2022-07-02 |
| TT | Health-based | Resolved | 2022-07-02 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-07-31 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-07-31 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-07-31 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-07-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 45.325 µg/L No EPA limit set
worst single sample: 56.4 µg/L | 56/56 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 18.625 µg/L No EPA limit set
worst single sample: 24.4 µg/L | 56/56 | SYR4 | 2012–2019 |
| TTHM | 60.05 µg/L 75% of the EPA limit 80 µg/L
worst single sample: 71.5 µg/L | 56/56 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 40.95 µg/L 68% of the EPA limit 60 µg/L
worst single sample: 56.6 µg/L | 56/56 | SYR4 | 2012–2019 |
| Bromodichloromethane | 12.02 µg/L No EPA limit set
worst single sample: 13.4 µg/L | 54/56 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 18.41 µg/L No EPA limit set
worst single sample: 22.8 µg/L | 54/56 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.96 µg/L No EPA limit set
worst single sample: 3.4 µg/L | 49/56 | SYR4 | 2012–2019 |
| Lead | 3.1 µg/L 21% of the EPA limit 15 µg/L
worst single sample: 4 µg/L | 19/34 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.24 µg/L No EPA limit set
worst single sample: 5.2 µg/L | 17/56 | SYR4 | 2012–2019 |
| Copper | 500 µg/L 38% of the EPA limit 1300 µg/L | 13/34 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 22.23 µg/L No EPA limit set
worst single sample: 35.1 µg/L | 10/56 | SYR4 | 2012–2019 |
| Lead | 0.0030 mg/L 20% of the EPA limit 0.0150 mg/L | 8/8 | LCR | 2023 |
| Fluoride | 707.5 µg/L 18% of the EPA limit 4000 µg/L
worst single sample: 710 µg/L | 6/6 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 3.655 µg/L No EPA limit set
worst single sample: 3.7 µg/L | 4/56 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 28 µg/L 0.3% of the EPA limit 10000 µg/L | 4/24 | SYR4 | 2012–2019 |
| Barium | 9.36 µg/L 0.5% of the EPA limit 2000 µg/L
worst single sample: 9.4 µg/L | 3/6 | SYR4 | 2013–2019 |
| Di(2-ethylhexyl) Phthalate | 9.81 µg/L 164% of the EPA limit, at the 95th percentile of samples — 6 µg/L
worst single sample: 10.7 µg/L | 3/13 | SYR4 | 2013–2019 |
| Bromoform | 0.9600 µg/L No EPA limit set | 1/56 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Adipate | 0.4100 µg/L 0.1% of the EPA limit 400 µg/L | 1/7 | SYR4 | 2013–2019 |
| Gross Beta Particle Activity | 1.94 pCi/L No EPA limit set | 1/6 | SYR4 | 2013–2019 |
62 contaminants tested, none detected
Utility contact
Frequently asked questions about Central Water
Is Central Water tap water safe to drink?
EPA monitoring detected 20 contaminants in Central Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Central Water's water?
EPA monitoring detected Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does Central Water serve?
Central Water reports serving 558 people in Louisiana, per its EPA record.
Has Central Water had any water quality violations?
The EPA has 130 violations on file for Central Water, of which 30 are health-based (a contaminant limit or required treatment was breached) and 15 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.