← Louisiana

Tap water quality report

Bogue-Lusa Water Works District

EPA monitoring tested this supplier for 110 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

110
contaminants tested
20
detected
4,200
people served
29
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Washington Parish

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

29
health-based violations
37
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2005-11-01 → 2005-11-30
MCL Health-based Archived 2005-11-01 → 2005-11-30
MCL Health-based Archived 2005-11-01 → 2005-11-30
MCL Health-based Archived 2005-08-01 → 2005-08-31
MCL Health-based Archived 2005-08-01 → 2005-08-31
MCL Health-based Archived 2004-01-01 → 2004-01-31
MCL Health-based Archived 2004-01-01 → 2004-01-31
MCL Health-based Archived 2004-01-01 → 2004-01-31
MCL Health-based Archived 2004-01-01 → 2004-01-31
MCL Health-based Archived 2002-02-15 → 2002-03-14

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
3.05 µg/L 20%
of the EPA limit 15 µg/L
worst single sample: 26 µg/L
60/68 SYR4 2013–2019
Bromodichloromethane
5.205 µg/L
No EPA limit set
worst single sample: 5.4 µg/L
14/14 SYR4 2013–2019
Chloroform
10.35 µg/L
No EPA limit set
worst single sample: 11 µg/L
14/14 SYR4 2013–2019
Dichloroacetic Acid
6.005 µg/L
No EPA limit set
worst single sample: 7.5 µg/L
14/14 SYR4 2013–2019
TTHM
17.92 µg/L 22%
of the EPA limit 80 µg/L
worst single sample: 18.7 µg/L
14/14 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
9.995 µg/L 17%
of the EPA limit 60 µg/L
worst single sample: 12.4 µg/L
14/14 SYR4 2013–2019
Trichloroacetic Acid
3.22 µg/L
No EPA limit set
worst single sample: 4 µg/L
14/14 SYR4 2013–2019
Lead
0.0016 mg/L 11%
of the EPA limit 0.0150 mg/L
12/12 LCR 2025
Dibromochloromethane
2.45 µg/L
No EPA limit set
worst single sample: 2.6 µg/L
11/14 SYR4 2013–2019
Fluoride
420 µg/L 11%
of the EPA limit 4000 µg/L
worst single sample: 440 µg/L
11/11 SYR4 2013–2019
Copper
160 µg/L 12%
of the EPA limit 1300 µg/L
worst single sample: 200 µg/L
9/68 SYR4 2013–2019
Dibromoacetic Acid
0.9210 µg/L
No EPA limit set
worst single sample: 0.9300 µg/L
7/14 SYR4 2013–2019
Nitrate-Nitrite
28 µg/L 0.3%
of the EPA limit 10000 µg/L
4/38 SYR4 2012–2019
Combined Radium (-226 And -228)
1.1975 pCi/L 24%
of the EPA limit 5 pCi/L
worst single sample: 1.23 pCi/L
3/8 SYR4 2016–2019
Di(2-ethylhexyl) Phthalate
0.8400 µg/L 14%
of the EPA limit 6 µg/L
worst single sample: 0.8500 µg/L
3/11 SYR4 2013–2019
Arsenic
0.9990 µg/L 10%
of the EPA limit 10 µg/L
worst single sample: 1 µg/L
2/11 SYR4 2013–2019
Combined Uranium
1.442 µg/L 4.8%
of the EPA limit 30 µg/L
worst single sample: 1.49 µg/L
2/11 SYR4 2013–2019
Gross Alpha, Excl. Radon And U
5.41 pCi/L 36%
of the EPA limit 15 pCi/L
2/6 SYR4 2013–2016
Gross Beta Particle Activity
2.01 pCi/L
No EPA limit set
1/11 SYR4 2013–2019
Lithium
12.9 µg/L
No EPA limit set
1/2 UCMR-5 2025
90 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ADAMS, MARY
Phone
985-735-1669
Email
[email protected]

Frequently asked questions about Bogue-Lusa Water Works District

Is Bogue-Lusa Water Works District tap water safe to drink?

EPA monitoring detected 20 contaminants in Bogue-Lusa Water Works District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Bogue-Lusa Water Works District's water?

EPA monitoring detected Lead, Bromodichloromethane, Chloroform, Dichloroacetic Acid, TTHM, and others. The full list with the level and data source for each is above.

How many people does Bogue-Lusa Water Works District serve?

Bogue-Lusa Water Works District reports serving 4,200 people in Louisiana, per its EPA record.

Has Bogue-Lusa Water Works District had any water quality violations?

The EPA has 37 violations on file for Bogue-Lusa Water Works District, of which 29 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.