Compliance record
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Lead | 5.2 µg/L 35% of the EPA limit 15 µg/L
worst single sample: 30 µg/L | 53/66 | SYR4 | 2012–2019 |
| Copper | 665 µg/L 51% of the EPA limit 1300 µg/L
worst single sample: 1000 µg/L | 30/66 | SYR4 | 2012–2019 |
| Chloroform | 24.8 µg/L No EPA limit set
worst single sample: 25.1 µg/L | 13/14 | SYR4 | 2013–2019 |
| TTHM | 43.2 µg/L 54% of the EPA limit 80 µg/L
worst single sample: 44.7 µg/L | 13/14 | SYR4 | 2013–2019 |
| Bromodichloromethane | 12.715 µg/L No EPA limit set
worst single sample: 13.1 µg/L | 12/14 | SYR4 | 2013–2019 |
| Dibromochloromethane | 5.3035 µg/L No EPA limit set
worst single sample: 5.43 µg/L | 12/14 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 28.13 µg/L 47% of the EPA limit 60 µg/L
worst single sample: 31.1 µg/L | 12/14 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 14.45 µg/L No EPA limit set
worst single sample: 15.8 µg/L | 11/14 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 11.945 µg/L No EPA limit set
worst single sample: 12.8 µg/L | 10/14 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 2.192 µg/L No EPA limit set
worst single sample: 2.52 µg/L | 9/14 | SYR4 | 2013–2019 |
| Fluoride | 600 µg/L 15% of the EPA limit 4000 µg/L | 9/9 | SYR4 | 2013–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2024 |
| Lithium | 26.4 µg/L No EPA limit set | 8/8 | UCMR-5 | 2023 |
| Bromoform | 1.958 µg/L No EPA limit set
worst single sample: 2 µg/L | 7/14 | SYR4 | 2013–2019 |
| Gross Beta Particle Activity | 2.672 pCi/L No EPA limit set
worst single sample: 2.78 pCi/L | 4/9 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 100 µg/L 1% of the EPA limit 10000 µg/L | 4/48 | SYR4 | 2012–2019 |
| Arsenic | 1.095 µg/L 11% of the EPA limit 10 µg/L
worst single sample: 1.1 µg/L | 2/9 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 1.0747 pCi/L 21% of the EPA limit 5 pCi/L
worst single sample: 1.12 pCi/L | 2/6 | SYR4 | 2016–2019 |
| Barium | 35 µg/L 1.8% of the EPA limit 2000 µg/L | 1/9 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 1 µg/L No EPA limit set | 1/14 | SYR4 | 2013–2019 |
| Pentachlorophenol | 0.3960 µg/L 40% of the EPA limit 1 µg/L | 1/9 | SYR4 | 2013–2019 |
| Selenium | 0.8400 µg/L 1.7% of the EPA limit 50 µg/L | 1/9 | SYR4 | 2013–2019 |
90 contaminants tested, none detected
Utility contact
Frequently asked questions about East Central Vernon Water
Is East Central Vernon Water tap water safe to drink?
EPA monitoring detected 22 contaminants in East Central Vernon Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in East Central Vernon Water's water?
EPA monitoring detected Lead, Copper, Chloroform, TTHM, Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does East Central Vernon Water serve?
East Central Vernon Water reports serving 6,363 people in Louisiana, per its EPA record.
Has East Central Vernon Water had any water quality violations?
The EPA has no formal drinking-water violations on file for East Central Vernon Water.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.