← Louisiana

Tap water quality report

Vermilion Waterworks District 1

EPA monitoring tested this supplier for 110 contaminants and detected 24. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

110
contaminants tested
24
detected
24,132
people served
52
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Vermilion Parish

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

52
health-based violations
72
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2024-04-01 → 2024-06-30
MCL Health-based Resolved 2024-04-01 → 2024-06-30
MCL Health-based Resolved 2024-04-01 → 2024-06-30
MCL Health-based Resolved 2024-04-01 → 2024-06-30
MCL Health-based Resolved 2024-01-01 → 2024-03-31
MCL Health-based Resolved 2024-01-01 → 2024-03-31
MCL Health-based Resolved 2024-01-01 → 2024-03-31
MCL Health-based Resolved 2024-01-01 → 2024-03-31
MCL Health-based Resolved 2023-10-01 → 2023-12-31
MCL Health-based Resolved 2023-10-01 → 2023-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
26.335 µg/L
No EPA limit set
worst single sample: 39.9 µg/L
114/114 SYR4 2012–2019
Chloroform
24.555 µg/L
No EPA limit set
worst single sample: 38.8 µg/L
114/114 SYR4 2012–2019
Dibromochloromethane
28.57 µg/L
No EPA limit set
worst single sample: 34.7 µg/L
114/114 SYR4 2012–2019
TTHM
82.44 µg/L 103%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 117.6 µg/L
114/114 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
34.895 µg/L 58%
of the EPA limit 60 µg/L
worst single sample: 59.4 µg/L
114/114 SYR4 2012–2019
Bromoform
12 µg/L
No EPA limit set
worst single sample: 16 µg/L
112/114 SYR4 2012–2019
Trichloroacetic Acid
10.15 µg/L
No EPA limit set
worst single sample: 13.7 µg/L
111/114 SYR4 2012–2019
Dibromoacetic Acid
7.765 µg/L
No EPA limit set
worst single sample: 16 µg/L
110/114 SYR4 2012–2019
Dichloroacetic Acid
11.22 µg/L
No EPA limit set
worst single sample: 16.5 µg/L
105/114 SYR4 2012–2019
Copper
620 µg/L 48%
of the EPA limit 1300 µg/L
worst single sample: 2100 µg/L
77/97 SYR4 2013–2019
Lead
4 µg/L 27%
of the EPA limit 15 µg/L
worst single sample: 55 µg/L
77/97 SYR4 2013–2019
Monochloroacetic Acid
31.5 µg/L
No EPA limit set
worst single sample: 40.3 µg/L
36/114 SYR4 2012–2019
Barium
1000 µg/L 50%
of the EPA limit 2000 µg/L
32/40 SYR4 2012–2019
Monobromoacetic Acid
5.3 µg/L
No EPA limit set
worst single sample: 5.4 µg/L
21/114 SYR4 2012–2019
Fluoride
300 µg/L 7.5%
of the EPA limit 4000 µg/L
16/16 SYR4 2012–2019
Nitrate-Nitrite
200 µg/L 2%
of the EPA limit 10000 µg/L
12/74 SYR4 2012–2019
Combined Radium (-226 And -228)
2.892 pCi/L 58%
of the EPA limit 5 pCi/L
worst single sample: 3.1 pCi/L
9/10 SYR4 2016–2019
Lead
0.0023 mg/L 15%
of the EPA limit 0.0150 mg/L
9/9 LCR 2025
Arsenic
1 µg/L 10%
of the EPA limit 10 µg/L
7/16 SYR4 2012–2019
Di(2-ethylhexyl) Phthalate
0.8090 µg/L 13%
of the EPA limit 6 µg/L
worst single sample: 0.8600 µg/L
7/15 SYR4 2012–2019
Lithium
35.8 µg/L
No EPA limit set
6/6 UCMR-5 2023
Gross Beta Particle Activity
4.6 pCi/L
No EPA limit set
worst single sample: 4.79 pCi/L
5/13 SYR4 2012–2019
Dalapon
0.9100 µg/L 0.5%
of the EPA limit 200 µg/L
2/18 SYR4 2012–2019
P-Dichlorobenzene
0.7995 µg/L 1.1%
of the EPA limit 75 µg/L
worst single sample: 0.8000 µg/L
2/16 SYR4 2012–2019
86 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
FAULK, HUBERT
Phone
337-898-8345
Email
[email protected]

Frequently asked questions about Vermilion Waterworks District 1

Is Vermilion Waterworks District 1 tap water safe to drink?

EPA monitoring detected 24 contaminants in Vermilion Waterworks District 1's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Vermilion Waterworks District 1's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Vermilion Waterworks District 1 serve?

Vermilion Waterworks District 1 reports serving 24,132 people in Louisiana, per its EPA record.

Has Vermilion Waterworks District 1 had any water quality violations?

The EPA has 72 violations on file for Vermilion Waterworks District 1, of which 52 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.