Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Unaddressed | 2024-01-20 |
| TT | Health-based | Unaddressed | 2024-01-20 |
| TT | Health-based | Unaddressed | 2024-01-20 |
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Arsenic | 49.45 µg/L 495% of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 64 µg/L | 38/38 | SYR4 | 2012–2019 |
| Barium | 1000 µg/L 50% of the EPA limit 2000 µg/L | 15/18 | SYR4 | 2014–2017 |
| Chloroform | 7.06 µg/L No EPA limit set
worst single sample: 7.2 µg/L | 15/15 | SYR4 | 2012–2019 |
| TTHM | 9.53 µg/L 12% of the EPA limit 80 µg/L
worst single sample: 10.3 µg/L | 15/15 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 24.53 µg/L 41% of the EPA limit 60 µg/L
worst single sample: 32.2 µg/L | 14/15 | SYR4 | 2012–2019 |
| Bromodichloromethane | 2.28 µg/L No EPA limit set
worst single sample: 2.4 µg/L | 13/15 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 9.84 µg/L No EPA limit set
worst single sample: 21 µg/L | 13/15 | SYR4 | 2012–2019 |
| Nitrate | 700 µg/L 7% of the EPA limit 10000 µg/L | 10/10 | SYR4 | 2019 |
| Nitrate-Nitrite | 2000 µg/L 20% of the EPA limit 10000 µg/L | 10/17 | SYR4 | 2012–2019 |
| Lead | 0.0130 mg/L 87% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2023 |
| Lead | 3.7 µg/L 25% of the EPA limit 15 µg/L
worst single sample: 4 µg/L | 7/18 | SYR4 | 2012–2017 |
| Dibromoacetic Acid | 1.625 µg/L No EPA limit set
worst single sample: 1.7 µg/L | 6/15 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 8.9 µg/L No EPA limit set
worst single sample: 9.5 µg/L | 6/15 | SYR4 | 2012–2019 |
| Fluoride | 200 µg/L 5% of the EPA limit 4000 µg/L | 6/6 | SYR4 | 2014–2017 |
| Gross Beta Particle Activity | 5.5475 pCi/L No EPA limit set
worst single sample: 5.64 pCi/L | 6/7 | SYR4 | 2014–2017 |
| Dibromochloromethane | 0.7520 µg/L No EPA limit set
worst single sample: 0.7700 µg/L | 4/15 | SYR4 | 2012–2019 |
| Chromium | 10 µg/L 10% of the EPA limit 100 µg/L | 3/6 | SYR4 | 2014–2017 |
| Dalapon | 1.179 µg/L 0.6% of the EPA limit 200 µg/L | 3/6 | SYR4 | 2014–2017 |
| Monochloroacetic Acid | 12.64 µg/L No EPA limit set
worst single sample: 12.8 µg/L | 3/15 | SYR4 | 2012–2019 |
| Nitrite | 310 µg/L 31% of the EPA limit 1000 µg/L | 3/5 | SYR4 | 2019 |
| Combined Radium (-226 And -228) | 1.3618 pCi/L 27% of the EPA limit 5 pCi/L
worst single sample: 1.39 pCi/L | 2/3 | SYR4 | 2017 |
| Copper | 100 µg/L 7.7% of the EPA limit 1300 µg/L | 1/18 | SYR4 | 2012–2017 |
60 contaminants tested, none detected
Utility contact
Frequently asked questions about St Martin Industrial Park Water
Is St Martin Industrial Park Water tap water safe to drink?
EPA monitoring detected 22 contaminants in St Martin Industrial Park Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in St Martin Industrial Park Water's water?
EPA monitoring detected Arsenic, Barium, Chloroform, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does St Martin Industrial Park Water serve?
St Martin Industrial Park Water reports serving 150 people in Louisiana, per its EPA record.
Has St Martin Industrial Park Water had any water quality violations?
The EPA has 239 violations on file for St Martin Industrial Park Water, of which 208 are health-based (a contaminant limit or required treatment was breached) and 7 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.