Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
| TT | Health-based | Resolved | 2022-05-24 |
| TT | Health-based | Resolved | 2022-05-24 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 1900 µg/L 146% of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 2500 µg/L | 310/377 | SYR4 | 2012–2019 |
| Lead | 8 µg/L 53% of the EPA limit 15 µg/L
worst single sample: 38 µg/L | 201/377 | SYR4 | 2012–2019 |
| Arsenic | 35.8 µg/L 358% of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 37 µg/L | 42/42 | SYR4 | 2012–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 22/22 | LCR | 2023 |
| Barium | 512.5 µg/L 26% of the EPA limit 2000 µg/L
worst single sample: 1000 µg/L | 14/20 | SYR4 | 2014–2018 |
| Bromodichloromethane | 16.555 µg/L No EPA limit set
worst single sample: 21.3 µg/L | 14/14 | SYR4 | 2013–2019 |
| Chloroform | 44.835 µg/L No EPA limit set
worst single sample: 46.2 µg/L | 14/14 | SYR4 | 2013–2019 |
| TTHM | 63.415 µg/L 79% of the EPA limit 80 µg/L
worst single sample: 74.4 µg/L | 14/14 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 42.869 µg/L 71% of the EPA limit 60 µg/L
worst single sample: 46.6 µg/L | 14/14 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 25.7 µg/L No EPA limit set
worst single sample: 27 µg/L | 14/14 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 25.4 µg/L No EPA limit set
worst single sample: 33.5 µg/L | 13/14 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 1.016 µg/L No EPA limit set
worst single sample: 1.1 µg/L | 8/14 | SYR4 | 2013–2019 |
| Dibromochloromethane | 5.88 µg/L No EPA limit set
worst single sample: 6.9 µg/L | 7/14 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 36 µg/L 0.4% of the EPA limit 10000 µg/L | 6/22 | SYR4 | 2012–2019 |
| Fluoride | 200 µg/L 5% of the EPA limit 4000 µg/L | 4/4 | SYR4 | 2014–2017 |
| Chromium | 10 µg/L 10% of the EPA limit 100 µg/L | 2/4 | SYR4 | 2014–2017 |
| Combined Radium (-226 And -228) | 1.1172 pCi/L 22% of the EPA limit 5 pCi/L
worst single sample: 1.15 pCi/L | 2/2 | SYR4 | 2017 |
| Di(2-ethylhexyl) Phthalate | 3.2485 µg/L 54% of the EPA limit 6 µg/L
worst single sample: 3.37 µg/L | 2/6 | SYR4 | 2014–2017 |
| Monochloroacetic Acid | 0.7490 µg/L No EPA limit set
worst single sample: 0.7600 µg/L | 2/14 | SYR4 | 2013–2019 |
| Gross Beta Particle Activity | 3.15 pCi/L No EPA limit set | 1/4 | SYR4 | 2014–2017 |
| Lithium | 11.2 µg/L No EPA limit set | 1/2 | UCMR-5 | 2025 |
89 contaminants tested, none detected
Utility contact
Frequently asked questions about United Water
Is United Water tap water safe to drink?
EPA monitoring detected 21 contaminants in United Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in United Water's water?
EPA monitoring detected Copper, Lead, Arsenic, Lead, Barium, and others. The full list with the level and data source for each is above.
How many people does United Water serve?
United Water reports serving 4,446 people in Louisiana, per its EPA record.
Has United Water had any water quality violations?
The EPA has 213 violations on file for United Water, of which 182 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.