Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Archived | 2026-03-01 → 2026-03-31 |
| TT | Health-based | Archived | 2026-02-01 → 2026-02-28 |
| TT | Health-based | Archived | 2026-02-01 → 2026-02-28 |
| TT | Health-based | Archived | 2026-01-01 → 2026-01-31 |
| TT | Health-based | Archived | 2026-01-01 → 2026-01-31 |
| TT | Health-based | Archived | 2025-12-01 → 2025-12-31 |
| TT | Health-based | Archived | 2025-12-01 → 2025-12-31 |
| TT | Health-based | Archived | 2025-11-01 → 2025-11-30 |
| TT | Health-based | Archived | 2025-11-01 → 2025-11-30 |
| TT | Health-based | Resolved | 2025-11-01 → 2025-11-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 124.8 µg/L No EPA limit set
worst single sample: 144 µg/L | 57/61 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 68.12 µg/L No EPA limit set
worst single sample: 85 µg/L | 57/60 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 178.24 µg/L 297% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 203.7 µg/L | 57/60 | SYR4 | 2012–2019 |
| Bromodichloromethane | 32.18 µg/L No EPA limit set
worst single sample: 34.9 µg/L | 55/61 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 102.6 µg/L No EPA limit set
worst single sample: 141 µg/L | 55/60 | SYR4 | 2012–2019 |
| TTHM | 157.93 µg/L 197% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 185.2 µg/L | 54/58 | SYR4 | 2012–2019 |
| Dibromochloromethane | 7.865 µg/L No EPA limit set
worst single sample: 9.08 µg/L | 50/61 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.59 µg/L No EPA limit set
worst single sample: 5.4 µg/L | 35/60 | SYR4 | 2012–2019 |
| Copper | 1075 µg/L 83% of the EPA limit 1300 µg/L
worst single sample: 1600 µg/L | 16/25 | SYR4 | 2014–2019 |
| Monochloroacetic Acid | 37.2 µg/L No EPA limit set
worst single sample: 39.9 µg/L | 16/60 | SYR4 | 2012–2019 |
| Lead | 43.8 µg/L 292% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 118 µg/L | 15/25 | SYR4 | 2014–2019 |
| Dalapon | 32.2326 µg/L 16% of the EPA limit 200 µg/L
worst single sample: 36.29 µg/L | 12/13 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 160 µg/L 1.6% of the EPA limit 10000 µg/L | 10/16 | SYR4 | 2012–2019 |
| Lead | 0.0022 mg/L 15% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2025 |
| Monobromoacetic Acid | 1.74 µg/L No EPA limit set
worst single sample: 1.8 µg/L | 7/60 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 0.8600 µg/L 14% of the EPA limit 6 µg/L | 6/14 | SYR4 | 2012–2019 |
| Arsenic | 1.8 µg/L 18% of the EPA limit 10 µg/L
worst single sample: 2 µg/L | 5/8 | SYR4 | 2012–2019 |
| Barium | 54 µg/L 2.7% of the EPA limit 2000 µg/L
worst single sample: 55 µg/L | 5/8 | SYR4 | 2012–2019 |
| Fluoride | 98 µg/L 2.5% of the EPA limit 4000 µg/L
worst single sample: 100 µg/L | 5/8 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 4.652 pCi/L No EPA limit set
worst single sample: 5 pCi/L | 4/8 | SYR4 | 2012–2019 |
| Bromoform | 2.052 µg/L No EPA limit set
worst single sample: 2.1 µg/L | 2/61 | SYR4 | 2012–2019 |
| Carbon Tetrachloride | 0.7400 µg/L 15% of the EPA limit 5 µg/L | 1/11 | SYR4 | 2012–2019 |
| Ethylbenzene | 0.5200 µg/L 0.1% of the EPA limit 700 µg/L | 1/11 | SYR4 | 2012–2019 |
| Hexachlorobenzene | 2.632 µg/L 263% of the EPA limit, at the 95th percentile of samples — 1 µg/L | 1/15 | SYR4 | 2012–2019 |
| Hexachlorocyclopentadiene | 0.0530 µg/L 0.1% of the EPA limit 50 µg/L | 1/15 | SYR4 | 2012–2019 |
| Xylenes, Total | 1.52 µg/L 0% of the EPA limit 10000 µg/L | 1/11 | SYR4 | 2012–2019 |
56 contaminants tested, none detected
Utility contact
Frequently asked questions about Pendleton Water Association
Is Pendleton Water Association tap water safe to drink?
EPA monitoring detected 26 contaminants in Pendleton Water Association's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Pendleton Water Association's water?
EPA monitoring detected Chloroform, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Bromodichloromethane, Trichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Pendleton Water Association serve?
Pendleton Water Association reports serving 2,634 people in Louisiana, per its EPA record.
Has Pendleton Water Association had any water quality violations?
The EPA has 1217 violations on file for Pendleton Water Association, of which 1015 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.