Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2023-04-01 → 2023-06-30 |
| MCL | Health-based | Resolved | 2023-04-01 → 2023-06-30 |
| MCL | Health-based | Resolved | 2023-04-01 → 2023-06-30 |
| MCL | Health-based | Resolved | 2023-04-01 → 2023-06-30 |
| TT | Health-based | Resolved | 2023-02-14 |
| TT | Health-based | Resolved | 2023-02-14 |
| TT | Health-based | Resolved | 2023-02-14 |
| TT | Health-based | Resolved | 2023-02-14 |
| TT | Health-based | Resolved | 2023-02-14 |
| TT | Health-based | Resolved | 2023-02-14 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 12.325 µg/L No EPA limit set
worst single sample: 16 µg/L | 112/112 | SYR4 | 2012–2019 |
| Bromoform | 43.09 µg/L No EPA limit set
worst single sample: 62 µg/L | 112/112 | SYR4 | 2012–2019 |
| Chloroform | 6.8 µg/L No EPA limit set
worst single sample: 9 µg/L | 112/112 | SYR4 | 2012–2019 |
| Dibromochloromethane | 28.45 µg/L No EPA limit set
worst single sample: 34 µg/L | 112/112 | SYR4 | 2012–2019 |
| TTHM | 88.18 µg/L 110% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 107 µg/L | 112/112 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 26.35 µg/L 44% of the EPA limit 60 µg/L
worst single sample: 30.1 µg/L | 111/112 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 15.13 µg/L No EPA limit set
worst single sample: 17.1 µg/L | 108/112 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 3.8 µg/L No EPA limit set
worst single sample: 4.7 µg/L | 108/112 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 6.09 µg/L No EPA limit set
worst single sample: 7.6 µg/L | 103/112 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 2.4 µg/L No EPA limit set
worst single sample: 3.9 µg/L | 68/112 | SYR4 | 2012–2019 |
| Lead | 8 µg/L 53% of the EPA limit 15 µg/L
worst single sample: 26 µg/L | 45/67 | SYR4 | 2014–2018 |
| Copper | 300 µg/L 23% of the EPA limit 1300 µg/L
worst single sample: 600 µg/L | 44/67 | SYR4 | 2014–2018 |
| Nitrate-Nitrite | 570 µg/L 5.7% of the EPA limit 10000 µg/L | 16/94 | SYR4 | 2012–2019 |
| Fluoride | 592 µg/L 15% of the EPA limit 4000 µg/L
worst single sample: 1000 µg/L | 13/13 | SYR4 | 2014–2018 |
| Lead | 0.0010 mg/L 6.7% of the EPA limit 0.0150 mg/L | 11/11 | LCR | 2023 |
| Monochloroacetic Acid | 5.8 µg/L No EPA limit set | 9/112 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 0.9920 pCi/L 20% of the EPA limit 5 pCi/L
worst single sample: 1.01 pCi/L | 5/7 | SYR4 | 2017–2018 |
| Dalapon | 9.039 µg/L 4.5% of the EPA limit 200 µg/L | 5/13 | SYR4 | 2014–2018 |
| Barium | 12.34 µg/L 0.6% of the EPA limit 2000 µg/L
worst single sample: 13 µg/L | 4/13 | SYR4 | 2014–2018 |
| Di(2-ethylhexyl) Phthalate | 1.312 µg/L 22% of the EPA limit 6 µg/L
worst single sample: 1.33 µg/L | 2/9 | SYR4 | 2014–2018 |
| Gross Beta Particle Activity | 1.4925 pCi/L No EPA limit set
worst single sample: 1.51 pCi/L | 2/13 | SYR4 | 2014–2018 |
| Xylenes, Total | 2.7455 µg/L 0% of the EPA limit 10000 µg/L
worst single sample: 2.8 µg/L | 2/13 | SYR4 | 2014–2018 |
| Lithium | 10.6 µg/L No EPA limit set | 2/10 | UCMR-5 | 2024 |
| Arsenic | 1 µg/L 10% of the EPA limit 10 µg/L | 1/13 | SYR4 | 2014–2018 |
88 contaminants tested, none detected
Utility contact
Frequently asked questions about West Monroe Water
Is West Monroe Water tap water safe to drink?
EPA monitoring detected 24 contaminants in West Monroe Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in West Monroe Water's water?
EPA monitoring detected Bromodichloromethane, Bromoform, Chloroform, Dibromochloromethane, TTHM, and others. The full list with the level and data source for each is above.
How many people does West Monroe Water serve?
West Monroe Water reports serving 16,005 people in Louisiana, per its EPA record.
Has West Monroe Water had any water quality violations?
The EPA has 200 violations on file for West Monroe Water, of which 167 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.