Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2024-10-01 → 2024-12-31 |
| MCL | Health-based | Archived | 2024-10-01 → 2024-12-31 |
| MCL | Health-based | Archived | 2024-10-01 → 2024-12-31 |
| MCL | Health-based | Archived | 2024-07-01 → 2024-09-30 |
| MCL | Health-based | Archived | 2024-07-01 → 2024-09-30 |
| MCL | Health-based | Archived | 2024-07-01 → 2024-09-30 |
| MCL | Health-based | Archived | 2024-04-01 → 2024-06-30 |
| MCL | Health-based | Archived | 2024-04-01 → 2024-06-30 |
| MCL | Health-based | Archived | 2024-04-01 → 2024-06-30 |
| MCL | Health-based | Archived | 2024-01-01 → 2024-03-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 282.51 µg/L 353% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 298.4 µg/L | 55/56 | SYR4 | 2013–2019 |
| Copper | 600 µg/L 46% of the EPA limit 1300 µg/L
worst single sample: 800 µg/L | 54/76 | SYR4 | 2013–2019 |
| Chloroform | 91.94 µg/L No EPA limit set
worst single sample: 164 µg/L | 53/56 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 19.89 µg/L No EPA limit set
worst single sample: 21.6 µg/L | 52/56 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 77.96 µg/L 130% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 169.4 µg/L | 52/56 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 35.45 µg/L No EPA limit set
worst single sample: 89.8 µg/L | 52/56 | SYR4 | 2013–2019 |
| Dibromochloromethane | 102 µg/L No EPA limit set
worst single sample: 114 µg/L | 51/56 | SYR4 | 2013–2019 |
| Bromodichloromethane | 98.385 µg/L No EPA limit set
worst single sample: 103 µg/L | 50/56 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 33.665 µg/L No EPA limit set
worst single sample: 77.8 µg/L | 50/56 | SYR4 | 2013–2019 |
| Bromoform | 50.48 µg/L No EPA limit set
worst single sample: 78.8 µg/L | 49/56 | SYR4 | 2013–2019 |
| Lead | 9 µg/L 60% of the EPA limit 15 µg/L
worst single sample: 17 µg/L | 45/76 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 38.85 µg/L 0.4% of the EPA limit 10000 µg/L
worst single sample: 39 µg/L | 24/114 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 5.84 µg/L No EPA limit set
worst single sample: 7.1 µg/L | 19/56 | SYR4 | 2013–2019 |
| Fluoride | 1600 µg/L 40% of the EPA limit 4000 µg/L | 15/15 | SYR4 | 2012–2017 |
| Monochloroacetic Acid | 4.73 µg/L No EPA limit set
worst single sample: 7.2 µg/L | 14/56 | SYR4 | 2013–2019 |
| Lead | 0.0030 mg/L 20% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2025 |
| Di(2-ethylhexyl) Phthalate | 0.8760 µg/L 15% of the EPA limit 6 µg/L
worst single sample: 0.9600 µg/L | 8/15 | SYR4 | 2012–2017 |
| Lithium | 10.9 µg/L No EPA limit set | 8/12 | UCMR-5 | 2024 |
| Barium | 19.3 µg/L 1% of the EPA limit 2000 µg/L
worst single sample: 22 µg/L | 7/15 | SYR4 | 2012–2017 |
| Dalapon | 1.72 µg/L 0.9% of the EPA limit 200 µg/L | 6/17 | SYR4 | 2012–2017 |
| Arsenic | 0.9795 µg/L 9.8% of the EPA limit 10 µg/L
worst single sample: 1 µg/L | 2/15 | SYR4 | 2012–2017 |
| Combined Radium (-226 And -228) | 0.7284 pCi/L 15% of the EPA limit 5 pCi/L
worst single sample: 0.7350 pCi/L | 2/7 | SYR4 | 2017 |
| Gross Beta Particle Activity | 2.1545 pCi/L No EPA limit set
worst single sample: 2.19 pCi/L | 2/14 | SYR4 | 2012–2017 |
87 contaminants tested, none detected
Utility contact
Frequently asked questions about Southwest Ouachita Waterworks, Inc
Is Southwest Ouachita Waterworks, Inc tap water safe to drink?
EPA monitoring detected 23 contaminants in Southwest Ouachita Waterworks, Inc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Southwest Ouachita Waterworks, Inc's water?
EPA monitoring detected TTHM, Copper, Chloroform, Dibromoacetic Acid, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Southwest Ouachita Waterworks, Inc serve?
Southwest Ouachita Waterworks, Inc reports serving 10,725 people in Louisiana, per its EPA record.
Has Southwest Ouachita Waterworks, Inc had any water quality violations?
The EPA has 418 violations on file for Southwest Ouachita Waterworks, Inc, of which 408 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.