EPA monitoring tested this supplier for 110 contaminants and detected 22. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

110
contaminants tested
22
detected
9,210
people served
130
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Ouachita Parish

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

130
health-based violations
138
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2021-01-01
TT Health-based Resolved 2021-01-01
TT Health-based Resolved 2021-01-01
TT Health-based Resolved 2021-01-01
TT Health-based Resolved 2021-01-01
MCL Health-based Archived 2014-04-01 → 2014-04-30
MCL Health-based Archived 2014-04-01 → 2014-04-30
MCL Health-based Archived 2014-04-01 → 2014-04-30
MCL Health-based Resolved 2010-01-01 → 2010-03-31
MCL Health-based Resolved 2010-01-01 → 2010-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
3 µg/L 20%
of the EPA limit 15 µg/L
worst single sample: 6 µg/L
53/63 SYR4 2012–2018
Copper
400 µg/L 31%
of the EPA limit 1300 µg/L
worst single sample: 2500 µg/L
45/63 SYR4 2012–2018
Dibromochloromethane
25.3 µg/L
No EPA limit set
worst single sample: 27.4 µg/L
41/41 SYR4 2013–2019
TTHM
87 µg/L 109%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 88.6 µg/L
41/41 SYR4 2013–2019
Bromoform
13.42 µg/L
No EPA limit set
worst single sample: 14.3 µg/L
40/41 SYR4 2013–2019
Chloroform
34.68 µg/L
No EPA limit set
worst single sample: 43.5 µg/L
40/41 SYR4 2013–2019
Bromodichloromethane
21.66 µg/L
No EPA limit set
worst single sample: 25.2 µg/L
39/41 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
31.425 µg/L 52%
of the EPA limit 60 µg/L
worst single sample: 34.2 µg/L
36/41 SYR4 2013–2019
Trichloroacetic Acid
12.34 µg/L
No EPA limit set
worst single sample: 13.8 µg/L
33/41 SYR4 2013–2019
Dichloroacetic Acid
10.55 µg/L
No EPA limit set
worst single sample: 11 µg/L
31/41 SYR4 2013–2019
Dibromoacetic Acid
8.385 µg/L
No EPA limit set
worst single sample: 8.8 µg/L
28/41 SYR4 2013–2019
Monochloroacetic Acid
6.79 µg/L
No EPA limit set
worst single sample: 8.16 µg/L
21/41 SYR4 2013–2019
Monobromoacetic Acid
1.35 µg/L
No EPA limit set
worst single sample: 1.4 µg/L
11/41 SYR4 2013–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
9/9 LCR 2024
Fluoride
322.5 µg/L 8.1%
of the EPA limit 4000 µg/L
worst single sample: 330 µg/L
6/6 SYR4 2014–2017
Combined Radium (-226 And -228)
0.8775 pCi/L 18%
of the EPA limit 5 pCi/L
worst single sample: 0.8860 pCi/L
3/3 SYR4 2017
Dalapon
1.05 µg/L 0.5%
of the EPA limit 200 µg/L
3/6 SYR4 2014–2017
Di(2-ethylhexyl) Phthalate
0.8050 µg/L 13%
of the EPA limit 6 µg/L
worst single sample: 0.8300 µg/L
3/6 SYR4 2014–2017
Pentachlorophenol
0.0600 µg/L 6%
of the EPA limit 1 µg/L
3/6 SYR4 2014–2017
Barium
8.1 µg/L 0.4%
of the EPA limit 2000 µg/L
1/6 SYR4 2014–2017
Gross Beta Particle Activity
4.45 pCi/L
No EPA limit set
1/6 SYR4 2014–2017
Toluene
1.1 µg/L 0.1%
of the EPA limit 1000 µg/L
1/6 SYR4 2014–2017
88 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitrate-NitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
MCQUEEN, PHILIP E.
Phone
318-322-3741
Email
[email protected]

Frequently asked questions about Kiroli Darbonne Ws

Is Kiroli Darbonne Ws tap water safe to drink?

EPA monitoring detected 22 contaminants in Kiroli Darbonne Ws's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Kiroli Darbonne Ws's water?

EPA monitoring detected Lead, Copper, Dibromochloromethane, TTHM, Bromoform, and others. The full list with the level and data source for each is above.

How many people does Kiroli Darbonne Ws serve?

Kiroli Darbonne Ws reports serving 9,210 people in Louisiana, per its EPA record.