Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-17 |
| MCL | Health-based | Resolved | 2023-01-01 → 2023-03-31 |
| MCL | Health-based | Resolved | 2023-01-01 → 2023-03-31 |
| MCL | Health-based | Resolved | 2023-01-01 → 2023-03-31 |
| MCL | Health-based | Resolved | 2023-01-01 → 2023-03-31 |
| MCL | Health-based | Resolved | 2023-01-01 → 2023-03-31 |
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
| MCL | Health-based | Resolved | 2022-10-01 → 2022-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 423.62 µg/L 530% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 466.1 µg/L | 52/52 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 88.11 µg/L 147% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 96 µg/L | 50/52 | SYR4 | 2012–2019 |
| Bromodichloromethane | 37.9 µg/L No EPA limit set
worst single sample: 46.5 µg/L | 46/52 | SYR4 | 2012–2019 |
| Chloroform | 136.5 µg/L No EPA limit set
worst single sample: 148 µg/L | 46/52 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 58.475 µg/L No EPA limit set
worst single sample: 61.2 µg/L | 46/52 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 25.825 µg/L No EPA limit set
worst single sample: 35.1 µg/L | 44/52 | SYR4 | 2012–2019 |
| Dibromochloromethane | 157.35 µg/L No EPA limit set
worst single sample: 182 µg/L | 40/52 | SYR4 | 2012–2019 |
| Lead | 6 µg/L 40% of the EPA limit 15 µg/L
worst single sample: 90 µg/L | 26/65 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 69.6 µg/L No EPA limit set
worst single sample: 77.1 µg/L | 23/52 | SYR4 | 2012–2019 |
| Bromoform | 269.4 µg/L No EPA limit set
worst single sample: 280 µg/L | 22/52 | SYR4 | 2012–2019 |
| Copper | 500 µg/L 38% of the EPA limit 1300 µg/L
worst single sample: 1100 µg/L | 21/65 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 8.05 µg/L No EPA limit set
worst single sample: 8.2 µg/L | 16/52 | SYR4 | 2012–2019 |
| Lead | 0.0010 mg/L 6.7% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2024 |
| Monochloroacetic Acid | 10.075 µg/L No EPA limit set
worst single sample: 12 µg/L | 6/52 | SYR4 | 2012–2019 |
| Barium | 14.4 µg/L 0.7% of the EPA limit 2000 µg/L
worst single sample: 15 µg/L | 5/6 | SYR4 | 2013–2019 |
| Fluoride | 652 µg/L 16% of the EPA limit 4000 µg/L
worst single sample: 660 µg/L | 5/5 | SYR4 | 2013–2019 |
| Arsenic | 1.475 µg/L 15% of the EPA limit 10 µg/L
worst single sample: 1.5 µg/L | 2/6 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 1.22375 pCi/L 24% of the EPA limit 5 pCi/L
worst single sample: 1.236 pCi/L | 2/5 | SYR4 | 2016–2019 |
| Gross Beta Particle Activity | 3.476 pCi/L No EPA limit set
worst single sample: 3.55 pCi/L | 2/6 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 28 µg/L 0.3% of the EPA limit 10000 µg/L | 2/18 | SYR4 | 2012–2019 |
| 1,2-Dichloroethane | 1.6 µg/L 32% of the EPA limit 5 µg/L | 1/6 | SYR4 | 2013–2019 |
| Cyanide | 3.5 µg/L 1.8% of the EPA limit 200 µg/L | 1/6 | SYR4 | 2013–2019 |
| Di(2-ethylhexyl) Phthalate | 0.7000 µg/L 12% of the EPA limit 6 µg/L | 1/6 | SYR4 | 2013–2019 |
59 contaminants tested, none detected
Utility contact
Frequently asked questions about Better Waterworks Water
Is Better Waterworks Water tap water safe to drink?
EPA monitoring detected 23 contaminants in Better Waterworks Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Better Waterworks Water's water?
EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, Chloroform, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Better Waterworks Water serve?
Better Waterworks Water reports serving 2,160 people in Louisiana, per its EPA record.
Has Better Waterworks Water had any water quality violations?
The EPA has 325 violations on file for Better Waterworks Water, of which 185 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.