← Louisiana

Tap water quality report

Tallulah Water

EPA monitoring tested this supplier for 112 contaminants and detected 25. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

112
contaminants tested
25
detected
8,601
people served
162
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Madison Parish

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

162
health-based violations
247
violations on file
36
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2026-01-01 → 2026-03-31
TT Health-based Unaddressed 2024-02-29
TT Health-based Unaddressed 2024-02-29
TT Health-based Unaddressed 2024-02-29
TT Health-based Resolved 2024-02-29
TT Health-based Resolved 2024-02-29
TT Health-based Resolved 2024-02-29
TT Health-based Resolved 2024-02-29
TT Health-based Resolved 2024-02-29
TT Health-based Resolved 2024-02-29

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Arsenic
13 µg/L 130%
of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 15 µg/L
55/55 SYR4 2013–2019
Chloroform
60.64 µg/L
No EPA limit set
worst single sample: 65.5 µg/L
34/34 SYR4 2013–2019
TTHM
92.575 µg/L 116%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 106 µg/L
34/34 SYR4 2013–2019
Bromodichloromethane
22.35 µg/L
No EPA limit set
worst single sample: 26 µg/L
32/34 SYR4 2013–2019
Dichloroacetic Acid
19.46 µg/L
No EPA limit set
worst single sample: 21.4 µg/L
32/34 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
48.805 µg/L 81%
of the EPA limit 60 µg/L
worst single sample: 56.8 µg/L
32/34 SYR4 2013–2019
Barium
1000 µg/L 50%
of the EPA limit 2000 µg/L
30/34 SYR4 2013–2019
Dibromochloromethane
10.48 µg/L
No EPA limit set
worst single sample: 14.2 µg/L
28/34 SYR4 2013–2019
Lead
4 µg/L 27%
of the EPA limit 15 µg/L
worst single sample: 6 µg/L
28/54 SYR4 2014–2019
Trichloroacetic Acid
19.98 µg/L
No EPA limit set
worst single sample: 21.2 µg/L
25/34 SYR4 2013–2019
Dibromoacetic Acid
3.115 µg/L
No EPA limit set
worst single sample: 3.4 µg/L
20/34 SYR4 2013–2019
Nitrate-Nitrite
1000 µg/L 10%
of the EPA limit 10000 µg/L
16/42 SYR4 2012–2019
Lead
0.0020 mg/L 13%
of the EPA limit 0.0150 mg/L
14/14 LCR 2026
Monochloroacetic Acid
14.94 µg/L
No EPA limit set
worst single sample: 17.1 µg/L
13/34 SYR4 2013–2019
Fluoride
300 µg/L 7.5%
of the EPA limit 4000 µg/L
12/12 SYR4 2013–2018
Bromoform
2.85 µg/L
No EPA limit set
worst single sample: 3 µg/L
11/34 SYR4 2013–2019
Copper
100 µg/L 7.7%
of the EPA limit 1300 µg/L
7/54 SYR4 2014–2019
Di(2-ethylhexyl) Phthalate
1.558 µg/L 26%
of the EPA limit 6 µg/L
worst single sample: 1.9 µg/L
7/12 SYR4 2013–2018
Gross Beta Particle Activity
3.922 pCi/L
No EPA limit set
worst single sample: 4 pCi/L
7/12 SYR4 2013–2018
Chromium
4.35 µg/L 4.4%
of the EPA limit 100 µg/L
worst single sample: 4.5 µg/L
4/18 SYR4 2013–2019
Combined Radium (-226 And -228)
2.2935 pCi/L 46%
of the EPA limit 5 pCi/L
worst single sample: 2.37 pCi/L
4/8 SYR4 2016–2018
Monobromoacetic Acid
0.3375 µg/L
No EPA limit set
worst single sample: 0.3400 µg/L
2/34 SYR4 2013–2019
Lithium
17.5 µg/L
No EPA limit set
2/2 UCMR-5 2024
Cadmium
0.6400 µg/L 13%
of the EPA limit 5 µg/L
1/18 SYR4 2013–2019
Endrin
0.0160 µg/L 0.8%
of the EPA limit 2 µg/L
1/12 SYR4 2013–2018
87 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCarbofuranCarbon TetrachlorideChlordaneCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndothallEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
LEWIS, YVONNE
Phone
318-574-0964
Email
[email protected]

Frequently asked questions about Tallulah Water

Is Tallulah Water tap water safe to drink?

EPA monitoring detected 25 contaminants in Tallulah Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Tallulah Water's water?

EPA monitoring detected Arsenic, Chloroform, TTHM, Bromodichloromethane, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does Tallulah Water serve?

Tallulah Water reports serving 8,601 people in Louisiana, per its EPA record.

Has Tallulah Water had any water quality violations?

The EPA has 247 violations on file for Tallulah Water, of which 162 are health-based (a contaminant limit or required treatment was breached) and 36 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.