Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2009-11-01 → 2009-11-30 |
| MCL | Health-based | Resolved | 2009-11-01 → 2009-11-30 |
| MCL | Health-based | Resolved | 2009-11-01 → 2009-11-30 |
| MCL | Health-based | Resolved | 2009-11-01 → 2009-11-30 |
| RPT | Monitoring | Unaddressed | 2025-07-02 |
| Other | Monitoring | Resolved | 2022-07-01 |
| Other | Monitoring | Resolved | 2022-07-01 |
| MR | Monitoring | Resolved | 2010-07-01 → 2010-09-30 |
| MR | Monitoring | Resolved | 2010-07-01 → 2010-09-30 |
| MR | Monitoring | Resolved | 2010-07-01 → 2010-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 10.83 µg/L No EPA limit set
worst single sample: 13.6 µg/L | 39/39 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 8.59 µg/L No EPA limit set
worst single sample: 14.5 µg/L | 39/39 | SYR4 | 2012–2019 |
| Dibromochloromethane | 30.15 µg/L No EPA limit set
worst single sample: 51.2 µg/L | 39/39 | SYR4 | 2012–2019 |
| TTHM | 78.04 µg/L 98% of the EPA limit 80 µg/L
worst single sample: 125.4 µg/L | 39/39 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 18.68 µg/L 31% of the EPA limit 60 µg/L
worst single sample: 21.5 µg/L | 39/39 | SYR4 | 2012–2019 |
| Bromoform | 37.055 µg/L No EPA limit set
worst single sample: 72.3 µg/L | 38/39 | SYR4 | 2012–2019 |
| Chloroform | 3.34 µg/L No EPA limit set
worst single sample: 6.7 µg/L | 37/39 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 4.185 µg/L No EPA limit set
worst single sample: 6.7 µg/L | 32/39 | SYR4 | 2012–2019 |
| Copper | 400 µg/L 31% of the EPA limit 1300 µg/L
worst single sample: 600 µg/L | 27/44 | SYR4 | 2014–2018 |
| Lead | 3.7 µg/L 25% of the EPA limit 15 µg/L
worst single sample: 5 µg/L | 27/44 | SYR4 | 2014–2018 |
| Trichloroacetic Acid | 3.21 µg/L No EPA limit set
worst single sample: 4.2 µg/L | 22/39 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 11.9 µg/L No EPA limit set
worst single sample: 12.1 µg/L | 11/39 | SYR4 | 2012–2019 |
| Lead | 0.0030 mg/L 20% of the EPA limit 0.0150 mg/L | 7/7 | LCR | 2023 |
| Fluoride | 247.5 µg/L 6.2% of the EPA limit 4000 µg/L
worst single sample: 250 µg/L | 6/6 | SYR4 | 2013–2018 |
| Barium | 270 µg/L 14% of the EPA limit 2000 µg/L | 4/6 | SYR4 | 2013–2018 |
| Combined Radium (-226 And -228) | 0.6042 pCi/L 12% of the EPA limit 5 pCi/L
worst single sample: 0.6090 pCi/L | 2/4 | SYR4 | 2016–2018 |
| Di(2-ethylhexyl) Phthalate | 0.9625 µg/L 16% of the EPA limit 6 µg/L
worst single sample: 0.9700 µg/L | 2/6 | SYR4 | 2013–2018 |
| Gross Beta Particle Activity | 2.821 pCi/L No EPA limit set
worst single sample: 2.84 pCi/L | 2/6 | SYR4 | 2013–2018 |
| Monochloroacetic Acid | 2.8965 µg/L No EPA limit set
worst single sample: 2.97 µg/L | 2/39 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 100 µg/L 1% of the EPA limit 10000 µg/L | 2/24 | SYR4 | 2012–2019 |
| Lithium | 24.2 µg/L No EPA limit set | 2/2 | UCMR-5 | 2025 |
| P-Dichlorobenzene | 0.3080 µg/L 0.4% of the EPA limit 75 µg/L
worst single sample: 0.3100 µg/L | 2/6 | SYR4 | 2013–2018 |
| Mercury | 1.1 µg/L 55% of the EPA limit 2 µg/L | 1/8 | SYR4 | 2013–2018 |
87 contaminants tested, none detected
Utility contact
Frequently asked questions about Jeff Davis Water and Sewer Commission 1
Is Jeff Davis Water and Sewer Commission 1 tap water safe to drink?
EPA monitoring detected 23 contaminants in Jeff Davis Water and Sewer Commission 1's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Jeff Davis Water and Sewer Commission 1's water?
EPA monitoring detected Bromodichloromethane, Dibromoacetic Acid, Dibromochloromethane, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Jeff Davis Water and Sewer Commission 1 serve?
Jeff Davis Water and Sewer Commission 1 reports serving 9,780 people in Louisiana, per its EPA record.
Has Jeff Davis Water and Sewer Commission 1 had any water quality violations?
The EPA has 29 violations on file for Jeff Davis Water and Sewer Commission 1, of which 4 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.