← Louisiana

Tap water quality report

Bayou Des Cannes Water

EPA monitoring tested this supplier for 110 contaminants and detected 22. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

110
contaminants tested
22
detected
4,578
people served
31
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Evangeline Parish

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

31
health-based violations
38
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2013-04-01 → 2013-04-30
MCL Health-based Resolved 2013-04-01 → 2013-04-30
MCL Health-based Resolved 2013-04-01 → 2013-04-30
MCL Health-based Resolved 2013-04-01 → 2013-04-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
630 µg/L 48%
of the EPA limit 1300 µg/L
worst single sample: 700 µg/L
35/64 SYR4 2012–2019
Dibromochloromethane
5.92 µg/L
No EPA limit set
worst single sample: 6.2 µg/L
15/15 SYR4 2012–2019
TTHM
14.51 µg/L 18%
of the EPA limit 80 µg/L
worst single sample: 15 µg/L
15/15 SYR4 2012–2019
Bromodichloromethane
3.345 µg/L
No EPA limit set
worst single sample: 3.8 µg/L
14/15 SYR4 2012–2019
Bromoform
3.935 µg/L
No EPA limit set
worst single sample: 4 µg/L
14/15 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
9.3 µg/L 16%
of the EPA limit 60 µg/L
worst single sample: 11.7 µg/L
13/15 SYR4 2012–2019
Dibromoacetic Acid
2.3 µg/L
No EPA limit set
11/15 SYR4 2012–2019
Chloroform
1.755 µg/L
No EPA limit set
worst single sample: 1.8 µg/L
10/15 SYR4 2012–2019
Lead
0.0010 mg/L 6.7%
of the EPA limit 0.0150 mg/L
9/9 LCR 2024
Lead
6.6 µg/L 44%
of the EPA limit 15 µg/L
worst single sample: 7 µg/L
9/64 SYR4 2012–2019
Monochloroacetic Acid
8.86 µg/L
No EPA limit set
worst single sample: 10 µg/L
7/15 SYR4 2012–2019
Arsenic
1.875 µg/L 19%
of the EPA limit 10 µg/L
worst single sample: 2 µg/L
6/6 SYR4 2013–2019
Fluoride
257.5 µg/L 6.4%
of the EPA limit 4000 µg/L
worst single sample: 260 µg/L
6/6 SYR4 2013–2019
Trichloroacetic Acid
0.8925 µg/L
No EPA limit set
worst single sample: 0.9100 µg/L
6/15 SYR4 2012–2019
Dichloroacetic Acid
1.9 µg/L
No EPA limit set
worst single sample: 2 µg/L
5/15 SYR4 2012–2019
Di(2-ethylhexyl) Phthalate
1.087 µg/L 18%
of the EPA limit 6 µg/L
worst single sample: 1.1 µg/L
3/6 SYR4 2013–2019
Monobromoacetic Acid
2.24 µg/L
No EPA limit set
worst single sample: 2.3 µg/L
3/15 SYR4 2012–2019
Barium
170 µg/L 8.5%
of the EPA limit 2000 µg/L
2/6 SYR4 2013–2019
Gross Beta Particle Activity
3.762 pCi/L
No EPA limit set
worst single sample: 3.86 pCi/L
2/6 SYR4 2013–2019
Nitrate-Nitrite
60 µg/L 0.6%
of the EPA limit 10000 µg/L
2/24 SYR4 2012–2019
Lithium
11.5 µg/L
No EPA limit set
2/2 UCMR-5 2023
Combined Radium (-226 And -228)
0.9010 pCi/L 18%
of the EPA limit 5 pCi/L
1/4 SYR4 2016–2019
88 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
WALL, THOMAS MIKE
Phone
337-457-7171
Email
[email protected]

Frequently asked questions about Bayou Des Cannes Water

Is Bayou Des Cannes Water tap water safe to drink?

EPA monitoring detected 22 contaminants in Bayou Des Cannes Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Bayou Des Cannes Water's water?

EPA monitoring detected Copper, Dibromochloromethane, TTHM, Bromodichloromethane, Bromoform, and others. The full list with the level and data source for each is above.

How many people does Bayou Des Cannes Water serve?

Bayou Des Cannes Water reports serving 4,578 people in Louisiana, per its EPA record.

Has Bayou Des Cannes Water had any water quality violations?

The EPA has 38 violations on file for Bayou Des Cannes Water, of which 31 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.