← Louisiana

Tap water quality report

Village of Grayson Water

EPA monitoring tested this supplier for 82 contaminants and detected 19. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

82
contaminants tested
19
detected
1,461
people served
37
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Caldwell Parish

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

37
health-based violations
66
violations on file
20
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2025-04-01 → 2025-06-30
MCL Health-based Archived 2025-04-01 → 2025-06-30
MCL Health-based Archived 2025-04-01 → 2025-06-30
MCL Health-based Archived 2025-01-01 → 2025-03-31
MCL Health-based Archived 2025-01-01 → 2025-03-31
MCL Health-based Archived 2025-01-01 → 2025-03-31
TT Health-based Resolved 2024-10-17
TT Health-based Unaddressed 2023-12-11
TT Health-based Unaddressed 2023-12-11
TT Health-based Unaddressed 2023-12-11

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
700 µg/L 54%
of the EPA limit 1300 µg/L
worst single sample: 800 µg/L
30/36 SYR4 2012–2019
Lead
2 µg/L 13%
of the EPA limit 15 µg/L
worst single sample: 4 µg/L
24/36 SYR4 2012–2019
Bromodichloromethane
15.93 µg/L
No EPA limit set
worst single sample: 17.4 µg/L
15/15 SYR4 2012–2019
Bromoform
12.09 µg/L
No EPA limit set
worst single sample: 18.6 µg/L
15/15 SYR4 2012–2019
Chloroform
7.79 µg/L
No EPA limit set
worst single sample: 10.1 µg/L
15/15 SYR4 2012–2019
Dibromochloromethane
19.97 µg/L
No EPA limit set
worst single sample: 20.6 µg/L
15/15 SYR4 2012–2019
TTHM
51.44 µg/L 64%
of the EPA limit 80 µg/L
worst single sample: 60.4 µg/L
15/15 SYR4 2012–2019
Nitrate-Nitrite
1000 µg/L 10%
of the EPA limit 10000 µg/L
10/28 SYR4 2012–2019
Fluoride
476 µg/L 12%
of the EPA limit 4000 µg/L
worst single sample: 500 µg/L
9/9 SYR4 2013–2019
Lead
0.00081 mg/L 5.4%
of the EPA limit 0.0150 mg/L
8/8 LCR 2025
Barium
50.75 µg/L 2.5%
of the EPA limit 2000 µg/L
worst single sample: 51 µg/L
6/9 SYR4 2013–2019
Dibromoacetic Acid
4.7 µg/L
No EPA limit set
worst single sample: 5.1 µg/L
6/15 SYR4 2012–2019
Dichloroacetic Acid
4.675 µg/L
No EPA limit set
worst single sample: 5.3 µg/L
6/15 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
12.975 µg/L 22%
of the EPA limit 60 µg/L
worst single sample: 14.3 µg/L
6/15 SYR4 2012–2019
Trichloroacetic Acid
3.6 µg/L
No EPA limit set
worst single sample: 3.9 µg/L
6/15 SYR4 2012–2019
Gross Beta Particle Activity
2.5495 pCi/L
No EPA limit set
worst single sample: 2.65 pCi/L
4/9 SYR4 2013–2019
Hexachlorobenzene
0.1116 µg/L 11%
of the EPA limit 1 µg/L
worst single sample: 0.1140 µg/L
3/9 SYR4 2013–2019
Combined Radium (-226 And -228)
1.26 pCi/L 25%
of the EPA limit 5 pCi/L
worst single sample: 1.313 pCi/L
2/6 SYR4 2016–2019
Di(2-ethylhexyl) Phthalate
0.5085 µg/L 8.5%
of the EPA limit 6 µg/L
worst single sample: 0.5100 µg/L
2/9 SYR4 2013–2019
63 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,3,7,8-TCDD2,4,5-TP2,4-DAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
STOWE, WANDA
Phone
318-649-7148
Email
[email protected]

Frequently asked questions about Village of Grayson Water

Is Village of Grayson Water tap water safe to drink?

EPA monitoring detected 19 contaminants in Village of Grayson Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Village of Grayson Water's water?

EPA monitoring detected Copper, Lead, Bromodichloromethane, Bromoform, Chloroform, and others. The full list with the level and data source for each is above.

How many people does Village of Grayson Water serve?

Village of Grayson Water reports serving 1,461 people in Louisiana, per its EPA record.

Has Village of Grayson Water had any water quality violations?

The EPA has 66 violations on file for Village of Grayson Water, of which 37 are health-based (a contaminant limit or required treatment was breached) and 20 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.