Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2013-02-02 |
| TT | Health-based | Resolved | 2013-02-02 |
| TT | Health-based | Resolved | 2013-02-02 |
| MR | Monitoring | Unaddressed | 2023-11-18 |
| Other | Monitoring | Resolved | 2023-07-01 |
| Other | Monitoring | Resolved | 2023-07-01 |
| MR | Monitoring | Resolved | 2018-01-01 |
| MR | Monitoring | Resolved | 2018-01-01 |
| MR | Monitoring | Resolved | 2018-01-01 |
| MR | Monitoring | Resolved | 2018-01-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 1185 µg/L 91% of the EPA limit 1300 µg/L
worst single sample: 1400 µg/L | 84/96 | SYR4 | 2013–2019 |
| Lead | 13.9 µg/L 93% of the EPA limit 15 µg/L
worst single sample: 22 µg/L | 52/96 | SYR4 | 2013–2019 |
| Bromodichloromethane | 14.805 µg/L No EPA limit set
worst single sample: 16.3 µg/L | 14/14 | SYR4 | 2013–2019 |
| Bromoform | 9.265 µg/L No EPA limit set
worst single sample: 10.5 µg/L | 14/14 | SYR4 | 2013–2019 |
| Chloroform | 9.745 µg/L No EPA limit set
worst single sample: 10.2 µg/L | 14/14 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 5.345 µg/L No EPA limit set
worst single sample: 5.8 µg/L | 14/14 | SYR4 | 2013–2019 |
| Dibromochloromethane | 16.545 µg/L No EPA limit set
worst single sample: 17 µg/L | 14/14 | SYR4 | 2013–2019 |
| TTHM | 48.805 µg/L 61% of the EPA limit 80 µg/L
worst single sample: 50.3 µg/L | 14/14 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 14.765 µg/L 25% of the EPA limit 60 µg/L
worst single sample: 17.3 µg/L | 14/14 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 5.82 µg/L No EPA limit set
worst single sample: 7.2 µg/L | 13/14 | SYR4 | 2013–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2023 |
| Trichloroacetic Acid | 2.07 µg/L No EPA limit set
worst single sample: 2.4 µg/L | 12/14 | SYR4 | 2013–2019 |
| Fluoride | 333 µg/L 8.3% of the EPA limit 4000 µg/L
worst single sample: 340 µg/L | 8/8 | SYR4 | 2014–2018 |
| Barium | 147.5 µg/L 7.4% of the EPA limit 2000 µg/L
worst single sample: 150 µg/L | 6/8 | SYR4 | 2014–2018 |
| Nitrate-Nitrite | 43 µg/L 0.4% of the EPA limit 10000 µg/L | 6/32 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 4.596 pCi/L No EPA limit set
worst single sample: 4.79 pCi/L | 5/8 | SYR4 | 2014–2018 |
| Monobromoacetic Acid | 2.04 µg/L No EPA limit set
worst single sample: 2.2 µg/L | 5/14 | SYR4 | 2013–2019 |
| Chromium | 19 µg/L 19% of the EPA limit 100 µg/L
worst single sample: 20 µg/L | 3/8 | SYR4 | 2014–2018 |
| Arsenic | 0.9805 µg/L 9.8% of the EPA limit 10 µg/L
worst single sample: 1 µg/L | 2/8 | SYR4 | 2014–2018 |
| Cadmium | 0.6555 µg/L 13% of the EPA limit 5 µg/L
worst single sample: 0.6600 µg/L | 2/8 | SYR4 | 2014–2018 |
| Combined Radium (-226 And -228) | 2.16995 pCi/L 43% of the EPA limit 5 pCi/L
worst single sample: 2.2 pCi/L | 2/6 | SYR4 | 2016–2018 |
| Monochloroacetic Acid | 9.565 µg/L No EPA limit set
worst single sample: 10 µg/L | 2/14 | SYR4 | 2013–2019 |
| Dalapon | 1.72 µg/L 0.9% of the EPA limit 200 µg/L | 1/8 | SYR4 | 2014–2018 |
| Di(2-ethylhexyl) Phthalate | 0.6500 µg/L 11% of the EPA limit 6 µg/L | 1/8 | SYR4 | 2014–2018 |
| Xylenes, Total | 1.3 µg/L 0% of the EPA limit 10000 µg/L | 1/8 | SYR4 | 2014–2018 |
57 contaminants tested, none detected
Utility contact
Frequently asked questions about Village of Columbia Water
Is Village of Columbia Water tap water safe to drink?
EPA monitoring detected 25 contaminants in Village of Columbia Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Village of Columbia Water's water?
EPA monitoring detected Copper, Lead, Bromodichloromethane, Bromoform, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Village of Columbia Water serve?
Village of Columbia Water reports serving 945 people in Louisiana, per its EPA record.
Has Village of Columbia Water had any water quality violations?
The EPA has 24 violations on file for Village of Columbia Water, of which 3 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.