← Louisiana

Tap water quality report

City of Shreveport Water

EPA monitoring tested this supplier for 112 contaminants and detected 22. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

112
contaminants tested
22
detected
192,378
people served
108
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Caddo Parish

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

108
health-based violations
143
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2026-01-01 → 2026-01-31
TT Health-based Resolved 2026-01-01 → 2026-01-31
TT Health-based Resolved 2026-01-01 → 2026-01-31
TT Health-based Resolved 2026-01-01 → 2026-01-31
MCL Health-based Archived 2026-01-01 → 2026-03-31
MCL Health-based Archived 2025-10-01 → 2025-12-31
MCL Health-based Archived 2025-10-01 → 2025-12-31
MCL Health-based Archived 2025-10-01 → 2025-12-31
MCL Health-based Archived 2025-07-01 → 2025-09-30
MCL Health-based Archived 2025-07-01 → 2025-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0075 µg/L 3/4 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
15.3 µg/L
No EPA limit set
worst single sample: 60 µg/L
269/271 SYR4 2012–2019
Chloroform
75.18 µg/L
No EPA limit set
worst single sample: 178 µg/L
269/271 SYR4 2012–2019
TTHM
92.625 µg/L 116%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 218 µg/L
268/268 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
64.9 µg/L 108%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 188 µg/L
262/262 SYR4 2012–2019
Dichloroacetic Acid
50 µg/L
No EPA limit set
worst single sample: 169 µg/L
261/262 SYR4 2012–2019
Trichloroacetic Acid
12.46 µg/L
No EPA limit set
worst single sample: 27 µg/L
238/262 SYR4 2012–2019
Dibromochloromethane
7.88 µg/L
No EPA limit set
worst single sample: 31 µg/L
233/271 SYR4 2012–2019
Dibromoacetic Acid
5.64 µg/L
No EPA limit set
worst single sample: 8.2 µg/L
167/262 SYR4 2012–2019
Monochloroacetic Acid
10.97 µg/L
No EPA limit set
worst single sample: 32 µg/L
104/262 SYR4 2012–2019
Bromoform
7.375 µg/L
No EPA limit set
worst single sample: 24.1 µg/L
46/271 SYR4 2012–2019
Lead
5.6 µg/L 37%
of the EPA limit 15 µg/L
worst single sample: 11 µg/L
45/157 SYR4 2013–2019
Lead
0.00092 mg/L 6.1%
of the EPA limit 0.0150 mg/L
16/16 LCR 2025
Copper
650 µg/L 50%
of the EPA limit 1300 µg/L
worst single sample: 1200 µg/L
12/157 SYR4 2013–2019
Nitrate-Nitrite
80 µg/L 0.8%
of the EPA limit 10000 µg/L
10/18 SYR4 2012–2019
Fluoride
930 µg/L 23%
of the EPA limit 4000 µg/L
worst single sample: 950 µg/L
9/9 SYR4 2012–2019
Monobromoacetic Acid
1.72 µg/L
No EPA limit set
worst single sample: 2 µg/L
8/262 SYR4 2012–2019
Arsenic
1.775 µg/L 18%
of the EPA limit 10 µg/L
worst single sample: 2 µg/L
6/9 SYR4 2012–2019
Barium
63 µg/L 3.2%
of the EPA limit 2000 µg/L
worst single sample: 64 µg/L
5/9 SYR4 2012–2019
Dalapon
35.7602 µg/L 18%
of the EPA limit 200 µg/L
worst single sample: 38.255 µg/L
4/13 SYR4 2012–2019
Di(2-ethylhexyl) Phthalate
0.9560 µg/L 16%
of the EPA limit 6 µg/L
worst single sample: 1.01 µg/L
4/15 SYR4 2012–2019
Gross Beta Particle Activity
1.7365 pCi/L
No EPA limit set
worst single sample: 1.74 pCi/L
2/9 SYR4 2012–2019
90 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined Radium (-226 And -228)Combined UraniumDichloromethaneDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ARCENEAUX, TOM
Phone
318-673-5050
Email
[email protected]

Frequently asked questions about City of Shreveport Water

Is City of Shreveport Water tap water safe to drink?

EPA monitoring detected 22 contaminants in City of Shreveport Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in City of Shreveport Water's water?

EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Total Haloacetic Acids (HAA5), Dichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does City of Shreveport Water serve?

City of Shreveport Water reports serving 192,378 people in Louisiana, per its EPA record.

Has City of Shreveport Water had any water quality violations?

The EPA has 143 violations on file for City of Shreveport Water, of which 108 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.