← Louisiana

Tap water quality report

Egan Water Corporation

EPA monitoring tested this supplier for 110 contaminants and detected 22. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

110
contaminants tested
22
detected
5,337
people served
95
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Acadia Parish

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

95
health-based violations
132
violations on file
23
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-11-29
TT Health-based Resolved 2024-11-29
TT Health-based Resolved 2024-11-29
TT Health-based Resolved 2024-11-29
TT Health-based Resolved 2024-11-29
TT Health-based Resolved 2024-11-29
TT Health-based Addressed 2024-11-29
TT Health-based Addressed 2024-11-29
TT Health-based Addressed 2024-11-29
TT Health-based Resolved 2024-11-29

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
1145 µg/L 88%
of the EPA limit 1300 µg/L
worst single sample: 1700 µg/L
58/64 SYR4 2013–2019
Lead
4.5 µg/L 30%
of the EPA limit 15 µg/L
worst single sample: 21 µg/L
51/64 SYR4 2013–2019
Bromodichloromethane
17.9 µg/L
No EPA limit set
worst single sample: 19.2 µg/L
41/41 SYR4 2012–2019
Bromoform
36.2 µg/L
No EPA limit set
worst single sample: 41.7 µg/L
41/41 SYR4 2012–2019
Dibromochloromethane
44.1 µg/L
No EPA limit set
worst single sample: 47.1 µg/L
41/41 SYR4 2012–2019
TTHM
93.9 µg/L 117%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 103.7 µg/L
41/41 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
22.5 µg/L 38%
of the EPA limit 60 µg/L
worst single sample: 27.1 µg/L
41/41 SYR4 2012–2019
Chloroform
5.14 µg/L
No EPA limit set
worst single sample: 6 µg/L
40/41 SYR4 2012–2019
Dibromoacetic Acid
11.93 µg/L
No EPA limit set
worst single sample: 15.7 µg/L
40/41 SYR4 2012–2019
Dichloroacetic Acid
4.57 µg/L
No EPA limit set
worst single sample: 4.7 µg/L
34/41 SYR4 2012–2019
Trichloroacetic Acid
2.51 µg/L
No EPA limit set
worst single sample: 2.8 µg/L
30/41 SYR4 2012–2019
Monobromoacetic Acid
10.51 µg/L
No EPA limit set
worst single sample: 10.9 µg/L
14/41 SYR4 2012–2019
Barium
1000 µg/L 50%
of the EPA limit 2000 µg/L
10/12 SYR4 2012–2018
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
7/7 LCR 2023
Monochloroacetic Acid
13.4 µg/L
No EPA limit set
worst single sample: 14 µg/L
7/41 SYR4 2012–2019
Fluoride
237.5 µg/L 5.9%
of the EPA limit 4000 µg/L
worst single sample: 240 µg/L
6/6 SYR4 2012–2018
Gross Beta Particle Activity
4.025 pCi/L
No EPA limit set
worst single sample: 4.28 pCi/L
4/6 SYR4 2012–2018
Nitrate-Nitrite
600 µg/L 6%
of the EPA limit 10000 µg/L
4/26 SYR4 2012–2019
Combined Radium (-226 And -228)
1.0732 pCi/L 21%
of the EPA limit 5 pCi/L
worst single sample: 1.1 pCi/L
3/5 SYR4 2015–2018
Di(2-ethylhexyl) Phthalate
0.6200 µg/L 10%
of the EPA limit 6 µg/L
2/6 SYR4 2012–2018
Lithium
20 µg/L
No EPA limit set
2/2 UCMR-5 2023
Glyphosate
10.1 µg/L 1.4%
of the EPA limit 700 µg/L
1/6 SYR4 2012–2018
88 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
FAUL, MARK
Phone
337-788-2889
Email
[email protected]

Frequently asked questions about Egan Water Corporation

Is Egan Water Corporation tap water safe to drink?

EPA monitoring detected 22 contaminants in Egan Water Corporation's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Egan Water Corporation's water?

EPA monitoring detected Copper, Lead, Bromodichloromethane, Bromoform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Egan Water Corporation serve?

Egan Water Corporation reports serving 5,337 people in Louisiana, per its EPA record.

Has Egan Water Corporation had any water quality violations?

The EPA has 132 violations on file for Egan Water Corporation, of which 95 are health-based (a contaminant limit or required treatment was breached) and 23 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.