Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2024-01-01 → 2024-03-31 |
| MCL | Health-based | Resolved | 2024-01-01 → 2024-03-31 |
| MCL | Health-based | Resolved | 2024-01-01 → 2024-03-31 |
| MCL | Health-based | Resolved | 2015-01-01 → 2015-03-31 |
| MCL | Health-based | Resolved | 2015-01-01 → 2015-03-31 |
| MCL | Health-based | Resolved | 2015-01-01 → 2015-03-31 |
| MCL | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
| MCL | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
| MCL | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
| MCL | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 81.6 µg/L 102% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 102.8 µg/L | 101/101 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 69.3 µg/L 116% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 138.5 µg/L | 101/101 | SYR4 | 2012–2019 |
| Copper | 306.2 µg/L 24% of the EPA limit 1300 µg/L
worst single sample: 1010 µg/L | 19/20 | SYR4 | 2017 |
| Nitrate | 591 µg/L 5.9% of the EPA limit 10000 µg/L | 16/18 | SYR4 | 2012–2019 |
| Lead | 0.0114 mg/L 76% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2023 |
| Fluoride | 700.7 µg/L 18% of the EPA limit 4000 µg/L
worst single sample: 707 µg/L | 8/8 | SYR4 | 2012–2019 |
| Atrazine | 0.4370 µg/L 15% of the EPA limit 3 µg/L
worst single sample: 0.5000 µg/L | 7/31 | SYR4 | 2012–2019 |
| Lead | 18.975 µg/L 127% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 24 µg/L | 6/20 | SYR4 | 2017 |
| Arsenic | 2.09 µg/L 21% of the EPA limit 10 µg/L
worst single sample: 2.2 µg/L | 3/8 | SYR4 | 2012–2019 |
| Chloroform | 30.42 µg/L No EPA limit set
worst single sample: 30.7 µg/L | 3/3 | SYR4 | 2012–2014 |
| Antimony, Total | 0.4000 µg/L 6.7% of the EPA limit 6 µg/L | 2/8 | SYR4 | 2012–2019 |
| Barium | 175.757 µg/L 8.8% of the EPA limit 2000 µg/L
worst single sample: 185 µg/L | 2/8 | SYR4 | 2012–2019 |
| Bromodichloromethane | 3.055 µg/L No EPA limit set
worst single sample: 3.1 µg/L | 2/3 | SYR4 | 2012–2014 |
| Nitrate-Nitrite | 577.45 µg/L 5.8% of the EPA limit 10000 µg/L
worst single sample: 591 µg/L | 2/2 | SYR4 | 2016–2019 |
| Bromoform | 5.7 µg/L No EPA limit set | 1/3 | SYR4 | 2012–2014 |
| Chromium | 2 µg/L 2% of the EPA limit 100 µg/L | 1/8 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 0.9000 µg/L 15% of the EPA limit 6 µg/L | 1/31 | SYR4 | 2012–2019 |
| Dibromochloromethane | 0.5000 µg/L No EPA limit set | 1/3 | SYR4 | 2012–2014 |
| Gross Beta Particle Activity | 3.4 pCi/L No EPA limit set | 1/1 | SYR4 | 2017 |
| Methoxychlor | 0.6500 µg/L 1.6% of the EPA limit 40 µg/L | 1/28 | SYR4 | 2012–2019 |
| Selenium | 1.4 µg/L 2.8% of the EPA limit 50 µg/L | 1/8 | SYR4 | 2012–2019 |
87 contaminants tested, none detected
Utility contact
Frequently asked questions about Huntingburg Municipal Water
Is Huntingburg Municipal Water tap water safe to drink?
EPA monitoring detected 21 contaminants in Huntingburg Municipal Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Huntingburg Municipal Water's water?
EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Copper, Nitrate, Lead, and others. The full list with the level and data source for each is above.
How many people does Huntingburg Municipal Water serve?
Huntingburg Municipal Water reports serving 6,526 people in Indiana, per its EPA record.
Has Huntingburg Municipal Water had any water quality violations?
The EPA has 195 violations on file for Huntingburg Municipal Water, of which 17 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.