← Idaho

Tap water quality report

Teton Springs Water and Sewer Company

EPA monitoring tested this supplier for 79 contaminants and detected 12. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

79
contaminants tested
12
detected
924
people served
1
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Teton

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

1
health-based violations
21
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2007-07-01 → 2007-07-31
MON Monitoring Resolved 2018-08-01 → 2018-08-31
MON Monitoring Resolved 2018-08-01 → 2018-08-31
MON Monitoring Resolved 2018-08-01 → 2018-08-31
MR Monitoring Archived 2018-07-01 → 2018-09-30
MR Monitoring Archived 2018-07-01 → 2018-09-30
MON Monitoring Archived 2017-02-01 → 2017-02-28
MON Monitoring Archived 2017-02-01 → 2017-02-28
MR Monitoring Resolved 2017-01-01 → 2017-03-31
MR Monitoring Resolved 2017-01-01 → 2017-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.0030 mg/L 20%
of the EPA limit 0.0150 mg/L
10/10 LCR 2025
Barium
55.8 µg/L 2.8%
of the EPA limit 2000 µg/L
worst single sample: 57 µg/L
3/3 SYR4 2013–2019
Fluoride
1480 µg/L 37%
of the EPA limit 4000 µg/L
worst single sample: 1600 µg/L
3/3 SYR4 2013–2019
Arsenic
4.9 µg/L 49%
of the EPA limit 10 µg/L
worst single sample: 5 µg/L
2/3 SYR4 2013–2019
Combined Radium (-226 And -228)
1.29865 pCi/L 26%
of the EPA limit 5 pCi/L
worst single sample: 1.36 pCi/L
2/2 SYR4 2016
Combined Uranium
0.5175 µg/L 1.7%
of the EPA limit 30 µg/L
worst single sample: 0.5200 µg/L
2/2 SYR4 2016
Gross Alpha, Excl. Radon And U
1.4275 pCi/L 9.5%
of the EPA limit 15 pCi/L
worst single sample: 1.47 pCi/L
2/2 SYR4 2016
Gross Beta Particle Activity
1.3625 pCi/L
No EPA limit set
worst single sample: 1.38 pCi/L
2/2 SYR4 2016
Nitrate
3340 µg/L 33%
of the EPA limit 10000 µg/L
2/34 SYR4 2012–2019
Nitrate-Nitrite
120 µg/L 1.2%
of the EPA limit 10000 µg/L
1/5 SYR4 2016–2019
Nitrite
120 µg/L 12%
of the EPA limit 1000 µg/L
1/5 SYR4 2016–2019
Selenium
2 µg/L 4%
of the EPA limit 50 µg/L
1/3 SYR4 2013–2019
67 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromodichloromethaneBromoformChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChloroformChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDibromochloromethaneDichloroacetic AcidDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidOxamylPentachlorophenolPicloramSimazineStyreneTTHMTetrachloroethyleneThallium, TotalTolueneTotal Haloacetic Acids (HAA5)Total Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
PINARDI, JON
Phone
208-354-0256
Email
[email protected]

Frequently asked questions about Teton Springs Water and Sewer Company

Is Teton Springs Water and Sewer Company tap water safe to drink?

EPA monitoring detected 12 contaminants in Teton Springs Water and Sewer Company's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Teton Springs Water and Sewer Company's water?

EPA monitoring detected Lead, Barium, Fluoride, Arsenic, Combined Radium (-226 And -228), and others. The full list with the level and data source for each is above.

How many people does Teton Springs Water and Sewer Company serve?

Teton Springs Water and Sewer Company reports serving 924 people in Idaho, per its EPA record.

Has Teton Springs Water and Sewer Company had any water quality violations?

The EPA has 21 violations on file for Teton Springs Water and Sewer Company, of which 1 is health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.