← Connecticut

Tap water quality report

Meriden Water Division

EPA monitoring tested this supplier for 110 contaminants and detected 33. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

110
contaminants tested
33
detected
58,441
people served
18
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
New Haven

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

18
health-based violations
114
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2018-01-01 → 2018-03-31
TT Health-based Resolved 1993-07-01
TT Health-based Resolved 1993-07-01
TT Health-based Resolved 1993-07-01
TT Health-based Resolved 1993-07-01
TT Health-based Resolved 1993-07-01
TT Health-based Resolved 1993-07-01
TT Health-based Resolved 1993-07-01

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFBS 0.0037 µg/L 3/19 2024
PFOS 0.0095 µg/L 3/19 2024
PFOA 0.0061 µg/L 2/19 2024
Pfba 0.0050 µg/L 1/19 2024
Pfhxa 0.0058 µg/L 1/19 2024
PFHXS 0.0040 µg/L 1/19 2024
Pfpea 0.0048 µg/L 1/19 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
363.4 µg/L 28%
of the EPA limit 1300 µg/L
worst single sample: 972 µg/L
453/509 SYR4 2012–2019
Bromodichloromethane
13 µg/L
No EPA limit set
worst single sample: 18 µg/L
388/452 SYR4 2012–2019
Chloroform
58.65 µg/L
No EPA limit set
worst single sample: 98 µg/L
388/452 SYR4 2012–2019
Dibromochloromethane
4.5 µg/L
No EPA limit set
worst single sample: 7.2 µg/L
349/452 SYR4 2012–2019
TTHM
72.225 µg/L 90%
of the EPA limit 80 µg/L
worst single sample: 110.3 µg/L
346/349 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
50 µg/L 83%
of the EPA limit 60 µg/L
worst single sample: 88 µg/L
344/349 SYR4 2012–2019
Trichloroacetic Acid
27 µg/L
No EPA limit set
worst single sample: 59 µg/L
343/349 SYR4 2012–2019
Dichloroacetic Acid
21 µg/L
No EPA limit set
worst single sample: 29 µg/L
341/349 SYR4 2012–2019
Barium
520.55 µg/L 26%
of the EPA limit 2000 µg/L
worst single sample: 664 µg/L
124/124 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
120/120 LCR 2026
Nitrate
3406 µg/L 34%
of the EPA limit 10000 µg/L
worst single sample: 3970 µg/L
114/152 SYR4 2012–2019
Nitrate-Nitrite
3516 µg/L 35%
of the EPA limit 10000 µg/L
worst single sample: 4120 µg/L
99/146 SYR4 2012–2019
Lead
6.625 µg/L 44%
of the EPA limit 15 µg/L
worst single sample: 16 µg/L
66/509 SYR4 2012–2019
Fluoride
986.5 µg/L 25%
of the EPA limit 4000 µg/L
worst single sample: 1140 µg/L
48/131 SYR4 2012–2019
Bromoform
0.9920 µg/L
No EPA limit set
worst single sample: 2.9 µg/L
39/452 SYR4 2012–2019
Dibromoacetic Acid
2.5 µg/L
No EPA limit set
26/349 SYR4 2012–2019
Monochloroacetic Acid
3.925 µg/L
No EPA limit set
worst single sample: 5.1 µg/L
26/349 SYR4 2012–2019
Combined Radium (-226 And -228)
1.61 pCi/L 32%
of the EPA limit 5 pCi/L
worst single sample: 1.7 pCi/L
7/17 SYR4 2014–2019
Arsenic
5.5 µg/L 55%
of the EPA limit 10 µg/L
worst single sample: 6 µg/L
3/124 SYR4 2012–2019
Chromium
1.9 µg/L 1.9%
of the EPA limit 100 µg/L
worst single sample: 2 µg/L
3/124 SYR4 2012–2019
Nitrite
12.85 µg/L 1.3%
of the EPA limit 1000 µg/L
worst single sample: 13 µg/L
2/76 SYR4 2012–2019
Cyanide
5 µg/L 2.5%
of the EPA limit 200 µg/L
1/124 SYR4 2012–2019
Combined Uranium
2 µg/L 6.7%
of the EPA limit 30 µg/L
1/17 SYR4 2014–2019
Monobromoacetic Acid
4.5 µg/L
No EPA limit set
1/349 SYR4 2012–2019
Selenium
1 µg/L 2%
of the EPA limit 50 µg/L
1/124 SYR4 2012–2019
Trichloroethylene
0.5400 µg/L 11%
of the EPA limit 5 µg/L
1/131 SYR4 2012–2019
77 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndrinEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfdaPfdoaPfeesaPfhpaPfhpsPfmbaPfmpaPFNAPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneVinyl Chloridecis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
PETER, ROBERT F
Phone
203-630-4256
Email
[email protected]

Frequently asked questions about Meriden Water Division

Is Meriden Water Division tap water safe to drink?

EPA monitoring detected 33 contaminants in Meriden Water Division's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Meriden Water Division's water?

EPA monitoring detected Copper, Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, and others. The full list with the level and data source for each is above.

How many people does Meriden Water Division serve?

Meriden Water Division reports serving 58,441 people in Connecticut, per its EPA record.

Has Meriden Water Division had any water quality violations?

The EPA has 114 violations on file for Meriden Water Division, of which 18 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.