← Colorado

Tap water quality report

Olympic Village

EPA monitoring tested this supplier for 78 contaminants and detected 16. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

78
contaminants tested
16
detected
75
people served
0
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Grand

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
876
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Resolved 2022-10-01
MR Monitoring Resolved 2022-10-01
MR Monitoring Resolved 2022-10-01
MR Monitoring Resolved 2022-04-01 → 2022-06-30
MR Monitoring Resolved 2022-04-01 → 2022-06-30
MR Monitoring Resolved 2022-04-01 → 2022-06-30
MR Monitoring Resolved 2022-04-01 → 2022-06-30
MR Monitoring Resolved 2022-04-01 → 2022-06-30
MR Monitoring Resolved 2022-04-01 → 2022-06-30
MR Monitoring Resolved 2022-04-01 → 2022-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
238 µg/L 2.4%
of the EPA limit 10000 µg/L
worst single sample: 260 µg/L
32/34 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
20/20 LCR 2025
Arsenic
2.8 µg/L 28%
of the EPA limit 10 µg/L
worst single sample: 3.1 µg/L
13/13 SYR4 2012–2019
Barium
100 µg/L 5%
of the EPA limit 2000 µg/L
13/13 SYR4 2012–2019
Fluoride
276 µg/L 6.9%
of the EPA limit 4000 µg/L
worst single sample: 300 µg/L
13/13 SYR4 2012–2019
Selenium
4.66 µg/L 9.3%
of the EPA limit 50 µg/L
worst single sample: 4.9 µg/L
13/13 SYR4 2012–2019
Dibromochloromethane
1.75 µg/L
No EPA limit set
worst single sample: 1.8 µg/L
11/11 SYR4 2012–2019
Bromodichloromethane
0.9120 µg/L
No EPA limit set
worst single sample: 0.9300 µg/L
10/11 SYR4 2012–2019
Bromoform
1.455 µg/L
No EPA limit set
worst single sample: 1.5 µg/L
10/11 SYR4 2012–2019
TTHM
3.655 µg/L 4.6%
of the EPA limit 80 µg/L
worst single sample: 3.7 µg/L
10/10 SYR4 2012–2019
Combined Radium (-226 And -228)
2.15 pCi/L 43%
of the EPA limit 5 pCi/L
worst single sample: 2.3 pCi/L
4/4 SYR4 2012–2019
Combined Uranium
3.21 µg/L 11%
of the EPA limit 30 µg/L
worst single sample: 3.3 µg/L
4/4 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
7.84735 pCi/L 52%
of the EPA limit 15 pCi/L
worst single sample: 8.191 pCi/L
4/4 SYR4 2012–2019
Antimony, Total
2.1 µg/L 35%
of the EPA limit 6 µg/L
1/13 SYR4 2012–2019
Gross Beta Particle Activity
1.8 pCi/L
No EPA limit set
1/1 SYR4 2012
Nitrate-Nitrite
170 µg/L 1.7%
of the EPA limit 10000 µg/L
1/1 SYR4 2019
62 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChloroformChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDichloroacetic AcidDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Haloacetic Acids (HAA5)Total Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
KENNEDY, CY
Phone
970-726-7161
Email
[email protected]

Frequently asked questions about Olympic Village

Is Olympic Village tap water safe to drink?

EPA monitoring detected 16 contaminants in Olympic Village's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Olympic Village's water?

EPA monitoring detected Nitrate, Lead, Arsenic, Barium, Fluoride, and others. The full list with the level and data source for each is above.

How many people does Olympic Village serve?

Olympic Village reports serving 75 people in Colorado, per its EPA record.

Has Olympic Village had any water quality violations?

The EPA has 876 violations on file for Olympic Village, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.