Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 1979-10-28 → 1980-04-27 |
| MR | Monitoring | Archived | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2012-01-01 → 2012-03-31 |
| MR | Monitoring | Resolved | 2012-01-01 → 2012-03-31 |
| MR | Monitoring | Resolved | 2012-01-01 → 2012-03-31 |
| MR | Monitoring | Resolved | 2012-01-01 → 2012-03-31 |
| MR | Monitoring | Resolved | 2008-11-01 → 2008-11-30 |
| MR | Monitoring | Resolved | 2008-11-01 → 2008-11-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 41 µg/L 51% of the EPA limit 80 µg/L
worst single sample: 63 µg/L | 253/253 | SYR4 | 2012–2019 |
| Bromodichloromethane | 7.405 µg/L No EPA limit set
worst single sample: 23 µg/L | 252/253 | SYR4 | 2012–2019 |
| Dibromochloromethane | 16.45 µg/L No EPA limit set
worst single sample: 28 µg/L | 252/253 | SYR4 | 2012–2019 |
| Bromoform | 15 µg/L No EPA limit set
worst single sample: 20 µg/L | 249/253 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 9.775 µg/L 16% of the EPA limit 60 µg/L
worst single sample: 18 µg/L | 246/248 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 5.995 µg/L No EPA limit set
worst single sample: 7.2 µg/L | 242/248 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 4.5 µg/L No EPA limit set
worst single sample: 7.9 µg/L | 159/248 | SYR4 | 2012–2019 |
| Chloroform | 7.74 µg/L No EPA limit set
worst single sample: 16 µg/L | 137/253 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 34/34 | LCR | 2025 |
| Trichloroacetic Acid | 5.935 µg/L No EPA limit set
worst single sample: 7 µg/L | 32/248 | SYR4 | 2012–2019 |
| Nitrate | 2712 µg/L 27% of the EPA limit 10000 µg/L | 28/52 | SYR4 | 2012–2019 |
| Combined Uranium | 16.4719 µg/L 55% of the EPA limit 30 µg/L
worst single sample: 17.88 µg/L | 10/10 | SYR4 | 2012–2019 |
| Fluoride | 345 µg/L 8.6% of the EPA limit 4000 µg/L
worst single sample: 380 µg/L | 8/11 | SYR4 | 2012–2019 |
| Selenium | 33.3 µg/L 67% of the EPA limit 50 µg/L
worst single sample: 39 µg/L | 7/11 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 712500 µg/L 7125% of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 720000 µg/L | 6/7 | SYR4 | 2014–2019 |
| Arsenic | 3.95 µg/L 40% of the EPA limit 10 µg/L
worst single sample: 4.1 µg/L | 4/11 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 2.94 µg/L No EPA limit set
worst single sample: 3 µg/L | 4/248 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 3.31 pCi/L No EPA limit set
worst single sample: 3.4 pCi/L | 3/5 | SYR4 | 2014–2019 |
| Copper | 97.55 µg/L 7.5% of the EPA limit 1300 µg/L
worst single sample: 100 µg/L | 2/11 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 8.99 µg/L No EPA limit set
worst single sample: 9.3 µg/L | 2/248 | SYR4 | 2012–2019 |
| Barium | 120 µg/L 6% of the EPA limit 2000 µg/L | 1/11 | SYR4 | 2012–2019 |
92 contaminants tested, none detected
Utility contact
Frequently asked questions about Ventura Wwd No. 8 - Simi Valley
Is Ventura Wwd No. 8 - Simi Valley tap water safe to drink?
EPA monitoring detected 21 contaminants in Ventura Wwd No. 8 - Simi Valley's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Ventura Wwd No. 8 - Simi Valley's water?
EPA monitoring detected TTHM, Bromodichloromethane, Dibromochloromethane, Bromoform, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Ventura Wwd No. 8 - Simi Valley serve?
Ventura Wwd No. 8 - Simi Valley reports serving 94,738 people in California, per its EPA record.
Has Ventura Wwd No. 8 - Simi Valley had any water quality violations?
The EPA has 8 violations on file for Ventura Wwd No. 8 - Simi Valley, of which 1 is health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.