Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2002-02-01 → 2002-02-28 |
| MCL | Health-based | Resolved | 2002-02-01 → 2002-02-28 |
| MR | Monitoring | Resolved | 2000-01-01 → 2000-12-01 |
| MR | Monitoring | Resolved | 2000-01-01 → 2000-12-01 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Arsenic | 8.3955 µg/L 84% of the EPA limit 10 µg/L
worst single sample: 13.8 µg/L | 650/650 | SYR4 | 2012–2019 |
| TTHM | 51.86 µg/L 65% of the EPA limit 80 µg/L
worst single sample: 66.8 µg/L | 103/103 | SYR4 | 2013–2019 |
| Bromodichloromethane | 13.895 µg/L No EPA limit set
worst single sample: 18 µg/L | 102/103 | SYR4 | 2013–2019 |
| Dibromochloromethane | 18.14 µg/L No EPA limit set
worst single sample: 21.7 µg/L | 102/103 | SYR4 | 2013–2019 |
| Bromoform | 8.7095 µg/L No EPA limit set
worst single sample: 13.7 µg/L | 100/103 | SYR4 | 2013–2019 |
| Chloroform | 17.32 µg/L No EPA limit set
worst single sample: 21.2 µg/L | 89/103 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 16.27 µg/L 27% of the EPA limit 60 µg/L
worst single sample: 20.1 µg/L | 84/103 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 5.396 µg/L No EPA limit set
worst single sample: 13.4 µg/L | 77/103 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 7.1865 µg/L No EPA limit set
worst single sample: 10 µg/L | 68/103 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 4.612 µg/L No EPA limit set
worst single sample: 6.68 µg/L | 53/103 | SYR4 | 2013–2019 |
| Nitrate | 1900 µg/L 19% of the EPA limit 10000 µg/L | 50/160 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 28/28 | LCR | 2024 |
| Fluoride | 380 µg/L 9.5% of the EPA limit 4000 µg/L
worst single sample: 390 µg/L | 26/26 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 0.9645 µg/L 19% of the EPA limit 5 µg/L
worst single sample: 0.9900 µg/L | 18/93 | SYR4 | 2012–2019 |
| Barium | 170 µg/L 8.5% of the EPA limit 2000 µg/L | 14/26 | SYR4 | 2012–2019 |
| Combined Uranium | 3.2184 µg/L 11% of the EPA limit 30 µg/L
worst single sample: 3.278 µg/L | 9/12 | SYR4 | 2014–2019 |
| Monochloroacetic Acid | 4.8875 µg/L No EPA limit set
worst single sample: 4.98 µg/L | 6/103 | SYR4 | 2013–2019 |
| Monobromoacetic Acid | 2.161 µg/L No EPA limit set
worst single sample: 2.32 µg/L | 4/103 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 399785 µg/L 3998% of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 470000 µg/L | 4/17 | SYR4 | 2014–2019 |
| Gross Beta Particle Activity | 3.785 pCi/L No EPA limit set
worst single sample: 3.8 pCi/L | 2/2 | SYR4 | 2017 |
88 contaminants tested, none detected
Utility contact
Frequently asked questions about Lakewood - City, Water Dept.
Is Lakewood - City, Water Dept. tap water safe to drink?
EPA monitoring detected 22 contaminants in Lakewood - City, Water Dept.'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Lakewood - City, Water Dept.'s water?
EPA monitoring detected Arsenic, TTHM, Bromodichloromethane, Dibromochloromethane, Bromoform, and others. The full list with the level and data source for each is above.
How many people does Lakewood - City, Water Dept. serve?
Lakewood - City, Water Dept. reports serving 66,135 people in California, per its EPA record.
Has Lakewood - City, Water Dept. had any water quality violations?
The EPA has 4 violations on file for Lakewood - City, Water Dept., of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.