← California

Tap water quality report

Burbank-City, Water Dept.

EPA monitoring tested this supplier for 111 contaminants and detected 33. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

111
contaminants tested
33
detected
105,603
people served
2
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Los Angeles

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

2
health-based violations
16
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 1993-01-01 → 1993-01-31
MCL Health-based Resolved 1993-01-01 → 1993-01-31
MR Monitoring Resolved 2022-09-01 → 2022-09-30
MR Monitoring Resolved 2022-09-01 → 2022-09-30
MON Monitoring Resolved 2022-09-01 → 2022-09-30
MON Monitoring Resolved 2022-09-01 → 2022-09-30
MR Monitoring Resolved 2022-09-01 → 2022-09-30
MR Monitoring Resolved 2022-09-01 → 2022-09-30
MR Monitoring Resolved 2022-09-01 → 2022-09-30
MR Monitoring Resolved 2022-09-01 → 2022-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0081 µg/L 4/4 2025
Pfpea 0.0102 µg/L 4/4 2025
Pfhxa 0.0044 µg/L 3/4 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
9944 µg/L 99%
of the EPA limit 10000 µg/L
worst single sample: 12000 µg/L
3302/3302 SYR4 2012–2019
Trichloroethylene
99 µg/L 1980%
of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 200 µg/L
1129/4630 SYR4 2012–2019
Tetrachloroethylene
190 µg/L 3800%
of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 410 µg/L
1128/4630 SYR4 2012–2019
1,1-Dichloroethylene
4 µg/L 57%
of the EPA limit 7 µg/L
worst single sample: 7.9 µg/L
963/4632 SYR4 2012–2019
Carbon Tetrachloride
1.1 µg/L 22%
of the EPA limit 5 µg/L
worst single sample: 1.6 µg/L
713/4630 SYR4 2012–2019
TTHM
23.95 µg/L 30%
of the EPA limit 80 µg/L
worst single sample: 120 µg/L
462/1553 SYR4 2012–2019
Bromoform
10 µg/L
No EPA limit set
worst single sample: 14 µg/L
378/1815 SYR4 2012–2019
Dibromochloromethane
7.545 µg/L
No EPA limit set
worst single sample: 30 µg/L
372/1813 SYR4 2012–2019
Bromodichloromethane
7.225 µg/L
No EPA limit set
worst single sample: 37 µg/L
296/1815 SYR4 2012–2019
cis-1,2-Dichloroethylene
2.7 µg/L 3.9%
of the EPA limit 70 µg/L
worst single sample: 3.7 µg/L
266/4632 SYR4 2012–2019
Fluoride
630 µg/L 16%
of the EPA limit 4000 µg/L
worst single sample: 670 µg/L
217/217 SYR4 2012–2019
Chloroform
10 µg/L
No EPA limit set
worst single sample: 47 µg/L
155/1487 SYR4 2012–2019
Dibromoacetic Acid
3.16 µg/L
No EPA limit set
worst single sample: 7.4 µg/L
149/255 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
7.65 µg/L 13%
of the EPA limit 60 µg/L
worst single sample: 27 µg/L
131/256 SYR4 2012–2019
Chromium
16.4 µg/L 16%
of the EPA limit 100 µg/L
worst single sample: 31 µg/L
113/1616 SYR4 2012–2019
Barium
130 µg/L 6.5%
of the EPA limit 2000 µg/L
worst single sample: 150 µg/L
93/125 SYR4 2012–2019
1,1,2-Trichloroethane
1.48 µg/L 30%
of the EPA limit 5 µg/L
worst single sample: 2.6 µg/L
53/4632 SYR4 2012–2019
Trichloroacetic Acid
4.8 µg/L
No EPA limit set
worst single sample: 16 µg/L
41/256 SYR4 2012–2019
Nitrate-Nitrite
9860 µg/L 99%
of the EPA limit 10000 µg/L
worst single sample: 11000 µg/L
40/40 SYR4 2016–2019
Dichloroacetic Acid
6.65 µg/L
No EPA limit set
worst single sample: 11 µg/L
31/256 SYR4 2012–2019
Combined Uranium
25.33 µg/L 84%
of the EPA limit 30 µg/L
worst single sample: 26.82 µg/L
24/24 SYR4 2012–2019
Lead
0.00080 mg/L 5.3%
of the EPA limit 0.0150 mg/L
19/19 LCR 2026
Gross Beta Particle Activity
9.475 pCi/L
No EPA limit set
worst single sample: 10 pCi/L
16/16 SYR4 2012–2019
Monobromoacetic Acid
4.06 µg/L
No EPA limit set
worst single sample: 4.7 µg/L
9/256 SYR4 2012–2019
Dichloromethane
1.945 µg/L 39%
of the EPA limit 5 µg/L
worst single sample: 2.4 µg/L
8/2286 SYR4 2012–2019
Arsenic
5.45 µg/L 55%
of the EPA limit 10 µg/L
worst single sample: 5.9 µg/L
4/126 SYR4 2012–2019
Ethylbenzene
1.643 µg/L 0.2%
of the EPA limit 700 µg/L
worst single sample: 1.7 µg/L
2/2286 SYR4 2012–2019
Xylenes, Total
5.885 µg/L 0.1%
of the EPA limit 10000 µg/L
worst single sample: 6.1 µg/L
2/2285 SYR4 2012–2019
1,2-Dichloroethane
0.5200 µg/L 10%
of the EPA limit 5 µg/L
1/4632 SYR4 2012–2019
Nitrite
1.7 µg/L 0.2%
of the EPA limit 1000 µg/L
1/788 SYR4 2012–2019
78 contaminants tested, none detected
1,1,1-Trichloroethane1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCopperCyanideCadmiumCarbofuranChlordaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoLeadMercuryMethoxychlorMonochloroacetic AcidNetfosaaNfdhaNmefosaaOxamylPFBSPfdaPfdoaPfeesaPfhpaPfhpsPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneVinyl ChlorideLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
WILSON, RICHARD
Phone
818-238-3558
Email
[email protected]

Frequently asked questions about Burbank-City, Water Dept.

Is Burbank-City, Water Dept. tap water safe to drink?

EPA monitoring detected 33 contaminants in Burbank-City, Water Dept.'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Burbank-City, Water Dept.'s water?

EPA monitoring detected Nitrate, Trichloroethylene, Tetrachloroethylene, 1,1-Dichloroethylene, Carbon Tetrachloride, and others. The full list with the level and data source for each is above.

How many people does Burbank-City, Water Dept. serve?

Burbank-City, Water Dept. reports serving 105,603 people in California, per its EPA record.

Has Burbank-City, Water Dept. had any water quality violations?

The EPA has 16 violations on file for Burbank-City, Water Dept., of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.