← California

Tap water quality report

Los Angeles-City, Dept. of Water & Power

EPA monitoring tested this supplier for 109 contaminants and detected 28. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
28
detected
3,875,566
people served
14
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Los Angeles

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

14
health-based violations
18
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2018-01-01 → 2018-01-31
TT Health-based Resolved 2018-01-01 → 2018-01-31
TT Health-based Resolved 2016-01-01 → 2016-01-31
TT Health-based Resolved 2016-01-01 → 2016-01-31
MCL Health-based Resolved 2014-06-01 → 2014-06-30
MCL Health-based Resolved 2014-06-01 → 2014-06-30
TT Health-based Resolved 1993-06-01 → 1993-06-30
TT Health-based Resolved 1993-06-01 → 1993-06-30
TT Health-based Resolved 1993-06-01 → 1993-06-30
TT Health-based Resolved 1993-06-01 → 1993-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
7210 µg/L 72%
of the EPA limit 10000 µg/L
worst single sample: 14125 µg/L
22996/23830 SYR4 2012–2019
TTHM
59.945 µg/L 75%
of the EPA limit 80 µg/L
worst single sample: 214.08 µg/L
9616/12015 SYR4 2012–2019
Fluoride
807.2 µg/L 20%
of the EPA limit 4000 µg/L
worst single sample: 1560 µg/L
7397/7398 SYR4 2012–2019
Trichloroethylene
26.5 µg/L 530%
of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 322 µg/L
6302/12921 SYR4 2012–2019
Tetrachloroethylene
19.6 µg/L 392%
of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 67.3 µg/L
3104/12926 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
52.59 µg/L 88%
of the EPA limit 60 µg/L
worst single sample: 85 µg/L
1576/1578 SYR4 2012–2019
1,1-Dichloroethylene
9.116 µg/L 130%
of the EPA limit, at the 95th percentile of samples — 7 µg/L
worst single sample: 15.9 µg/L
1029/12923 SYR4 2012–2019
Arsenic
10.875 µg/L 109%
of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 20.2 µg/L
726/1201 SYR4 2012–2019
cis-1,2-Dichloroethylene
3.29 µg/L 4.7%
of the EPA limit 70 µg/L
worst single sample: 7.46 µg/L
553/4404 SYR4 2012–2019
Combined Uranium
22.8074 µg/L 76%
of the EPA limit 30 µg/L
worst single sample: 30.9473 µg/L
412/424 SYR4 2012–2019
Carbon Tetrachloride
2.32 µg/L 46%
of the EPA limit 5 µg/L
worst single sample: 2.96 µg/L
147/12925 SYR4 2012–2019
Nitrate-Nitrite
642000 µg/L 6420%
of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 980000 µg/L
129/241 SYR4 2012–2019
Chromium
171.5 µg/L 172%
of the EPA limit, at the 95th percentile of samples — 100 µg/L
worst single sample: 348 µg/L
127/1307 SYR4 2012–2019
Barium
186.6 µg/L 9.3%
of the EPA limit 2000 µg/L
worst single sample: 218 µg/L
118/324 SYR4 2012–2019
Gross Beta Particle Activity
10.05 pCi/L
No EPA limit set
worst single sample: 14 pCi/L
80/159 SYR4 2012–2019
1,1,1-Trichloroethane
1.896 µg/L 0.9%
of the EPA limit 200 µg/L
worst single sample: 2.13 µg/L
57/4406 SYR4 2012–2019
Selenium
19.44 µg/L 39%
of the EPA limit 50 µg/L
worst single sample: 22.4 µg/L
53/324 SYR4 2012–2019
Copper
79.54 µg/L 6.1%
of the EPA limit 1300 µg/L
worst single sample: 167 µg/L
25/342 SYR4 2012–2019
Lead
0.0039 mg/L 26%
of the EPA limit 0.0150 mg/L
25/25 LCR 2023
Lithium
100 µg/L
No EPA limit set
16/16 UCMR-5 2024
Nitrite
0.0259 µg/L 0%
of the EPA limit 1000 µg/L
worst single sample: 0.0284 µg/L
11/596 SYR4 2012–2019
1,2-Dichloroethane
0.5758 µg/L 12%
of the EPA limit 5 µg/L
worst single sample: 0.6030 µg/L
9/4402 SYR4 2012–2019
Bromate
11.5 µg/L 115%
of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 11.9 µg/L
9/144 SYR4 2012–2019
Lead
31.9 µg/L 213%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 42.1 µg/L
6/347 SYR4 2012–2019
Combined Radium (-226 And -228)
1.2135 pCi/L 24%
of the EPA limit 5 pCi/L
worst single sample: 1.26 pCi/L
4/7 SYR4 2018
Cadmium
1.2 µg/L 24%
of the EPA limit 5 µg/L
1/324 SYR4 2012–2019
Toluene
0.5220 µg/L 0.1%
of the EPA limit 1000 µg/L
1/4404 SYR4 2012–2019
Xylenes, Total
1.89 µg/L 0%
of the EPA limit 10000 µg/L
1/4405 SYR4 2012–2019
81 contaminants tested, none detected
1,1,2-Trichloroethane1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromodichloromethaneBromoformChlorobenzeneCyanideCarbofuranChlordaneChloroformDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromochloromethaneDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneThallium, TotalTotal Polychlorinated Biphenyls (PCB)ToxapheneVinyl ChlorideO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
LEUNG, JONATHAN
Phone
800-342-5397
Email
[email protected]

Frequently asked questions about Los Angeles-City, Dept. of Water & Power

Is Los Angeles-City, Dept. of Water & Power tap water safe to drink?

EPA monitoring detected 28 contaminants in Los Angeles-City, Dept. of Water & Power's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Los Angeles-City, Dept. of Water & Power's water?

EPA monitoring detected Nitrate, TTHM, Fluoride, Trichloroethylene, Tetrachloroethylene, and others. The full list with the level and data source for each is above.

How many people does Los Angeles-City, Dept. of Water & Power serve?

Los Angeles-City, Dept. of Water & Power reports serving 3,875,566 people in California, per its EPA record.

Has Los Angeles-City, Dept. of Water & Power had any water quality violations?

The EPA has 18 violations on file for Los Angeles-City, Dept. of Water & Power, of which 14 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.