Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2006-06-01 → 2006-06-30 |
| MCL | Health-based | Resolved | 2006-06-01 → 2006-06-30 |
| Other | Monitoring | Resolved | 2016-02-11 |
| Other | Monitoring | Resolved | 2016-02-11 |
| MR | Monitoring | Resolved | 2016-01-01 → 2016-01-31 |
| MR | Monitoring | Resolved | 2016-01-01 → 2016-01-31 |
| MR | Monitoring | Resolved | 2015-04-01 → 2015-04-30 |
| MR | Monitoring | Resolved | 2015-04-01 → 2015-04-30 |
| MR | Monitoring | Resolved | 2008-01-01 → 2008-03-31 |
| MR | Monitoring | Resolved | 2008-01-01 → 2008-03-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 9040 µg/L 90% of the EPA limit 10000 µg/L
worst single sample: 18000 µg/L | 7724/7792 | SYR4 | 2012–2019 |
| Trichloroethylene | 4.3 µg/L 86% of the EPA limit 5 µg/L
worst single sample: 23 µg/L | 2384/3865 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 6.3 µg/L 126% of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 12 µg/L | 1414/3834 | SYR4 | 2012–2019 |
| TTHM | 18 µg/L 23% of the EPA limit 80 µg/L
worst single sample: 22 µg/L | 127/158 | SYR4 | 2012–2019 |
| Dibromochloromethane | 6.875 µg/L No EPA limit set
worst single sample: 8.7 µg/L | 126/158 | SYR4 | 2012–2019 |
| Bromoform | 6.9 µg/L No EPA limit set
worst single sample: 9.3 µg/L | 125/158 | SYR4 | 2012–2019 |
| Bromodichloromethane | 3.3 µg/L No EPA limit set
worst single sample: 4.1 µg/L | 110/158 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.5 µg/L No EPA limit set
worst single sample: 2.9 µg/L | 94/132 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 2.6 µg/L 4.3% of the EPA limit 60 µg/L
worst single sample: 3.6 µg/L | 94/132 | SYR4 | 2012–2019 |
| Fluoride | 1200 µg/L 30% of the EPA limit 4000 µg/L
worst single sample: 1400 µg/L | 51/51 | SYR4 | 2012–2019 |
| Lead | 0.0019 mg/L 13% of the EPA limit 0.0150 mg/L | 41/41 | LCR | 2025 |
| Combined Uranium | 8.493 µg/L 28% of the EPA limit 30 µg/L
worst single sample: 8.94 µg/L | 25/27 | SYR4 | 2012–2019 |
| Chloroform | 1.8 µg/L No EPA limit set
worst single sample: 1.9 µg/L | 21/158 | SYR4 | 2012–2019 |
| 1,1-Dichloroethylene | 0.6925 µg/L 9.9% of the EPA limit 7 µg/L
worst single sample: 0.7100 µg/L | 8/461 | SYR4 | 2012–2019 |
| Chromium | 19.75 µg/L 20% of the EPA limit 100 µg/L
worst single sample: 21 µg/L | 6/52 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 11500 µg/L 115% of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 12000 µg/L | 6/7 | SYR4 | 2017 |
| Arsenic | 5.685 µg/L 57% of the EPA limit 10 µg/L
worst single sample: 5.7 µg/L | 4/51 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 1.285 µg/L No EPA limit set
worst single sample: 1.3 µg/L | 2/132 | SYR4 | 2012–2019 |
| Copper | 76 µg/L 5.8% of the EPA limit 1300 µg/L | 1/35 | SYR4 | 2012–2018 |
| Di(2-ethylhexyl) Phthalate | 6.6 µg/L 110% of the EPA limit, at the 95th percentile of samples — 6 µg/L | 1/81 | SYR4 | 2012–2018 |
| Gross Beta Particle Activity | 2.3 pCi/L No EPA limit set | 1/1 | SYR4 | 2018 |
| Lead | 15 µg/L 100% of the EPA limit 15 µg/L | 1/20 | SYR4 | 2012–2018 |
87 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Arcadia
Is City of Arcadia tap water safe to drink?
EPA monitoring detected 24 contaminants in City of Arcadia's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Arcadia's water?
EPA monitoring detected Nitrate, Trichloroethylene, Tetrachloroethylene, TTHM, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does City of Arcadia serve?
City of Arcadia reports serving 51,361 people in California, per its EPA record.
Has City of Arcadia had any water quality violations?
The EPA has 17 violations on file for City of Arcadia, of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.