Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2015-10-01 |
| MR | Monitoring | Resolved | 2015-10-01 |
| MR | Monitoring | Resolved | 1993-06-30 → 2000-03-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromate | 9.44 µg/L 94% of the EPA limit 10 µg/L
worst single sample: 18 µg/L | 53/68 | SYR4 | 2012–2019 |
| Arsenic | 4.655 µg/L 47% of the EPA limit 10 µg/L
worst single sample: 5.8 µg/L | 30/51 | SYR4 | 2012–2019 |
| Fluoride | 795.5 µg/L 20% of the EPA limit 4000 µg/L
worst single sample: 910 µg/L | 30/47 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 27/27 | LCR | 2025 |
| Nitrate | 4286.09 µg/L 43% of the EPA limit 10000 µg/L
worst single sample: 4859 µg/L | 24/106 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 920000 µg/L 9200% of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 1000000 µg/L | 9/26 | SYR4 | 2012–2019 |
| Barium | 158 µg/L 7.9% of the EPA limit 2000 µg/L
worst single sample: 160 µg/L | 5/51 | SYR4 | 2012–2019 |
| Dichloromethane | 3.12 µg/L 62% of the EPA limit 5 µg/L
worst single sample: 3.4 µg/L | 5/38 | SYR4 | 2012–2019 |
| Copper | 289.2 µg/L 22% of the EPA limit 1300 µg/L
worst single sample: 320 µg/L | 3/51 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 37.46 pCi/L No EPA limit set
worst single sample: 41 pCi/L | 3/5 | SYR4 | 2014–2019 |
| Bromoform | 2.725 µg/L No EPA limit set
worst single sample: 2.8 µg/L | 2/6 | SYR4 | 2012–2017 |
| Cyanide | 1.575 µg/L 0.8% of the EPA limit 200 µg/L
worst single sample: 1.6 µg/L | 2/50 | SYR4 | 2012–2019 |
| Chromium | 29 µg/L 29% of the EPA limit 100 µg/L
worst single sample: 30 µg/L | 2/51 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 0.3845 µg/L 6.4% of the EPA limit 6 µg/L
worst single sample: 0.3900 µg/L | 2/39 | SYR4 | 2012–2019 |
| Lead | 2.73 µg/L 18% of the EPA limit 15 µg/L
worst single sample: 2.8 µg/L | 2/51 | SYR4 | 2012–2019 |
| TTHM | 3.845 µg/L 4.8% of the EPA limit 80 µg/L
worst single sample: 3.9 µg/L | 2/6 | SYR4 | 2012–2017 |
| Asbestos | 0.2000 MFL 2.9% of the EPA limit 7 MFL | 1/24 | SYR4 | 2012–2017 |
| Cadmium | 1.6 µg/L 32% of the EPA limit 5 µg/L | 1/51 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 0.1600 pCi/L 3.2% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2019 |
| Di(2-ethylhexyl) Adipate | 0.2100 µg/L 0.1% of the EPA limit 400 µg/L | 1/39 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.1 µg/L No EPA limit set | 1/6 | SYR4 | 2012–2017 |
| Selenium | 7.6 µg/L 15% of the EPA limit 50 µg/L | 1/51 | SYR4 | 2012–2019 |
86 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Martinez
Is City of Martinez tap water safe to drink?
EPA monitoring detected 22 contaminants in City of Martinez's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Martinez's water?
EPA monitoring detected Bromate, Arsenic, Fluoride, Lead, Nitrate, and others. The full list with the level and data source for each is above.
How many people does City of Martinez serve?
City of Martinez reports serving 30,997 people in California, per its EPA record.
Has City of Martinez had any water quality violations?
The EPA has 3 violations on file for City of Martinez, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.