Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2015-02-01 → 2015-02-28 |
| MCL | Health-based | Resolved | 2015-02-01 → 2015-02-28 |
| MCL | Health-based | Resolved | 2015-02-01 → 2015-02-28 |
| MCL | Health-based | Resolved | 2015-02-01 → 2015-02-28 |
| MCL | Health-based | Resolved | 2014-09-01 → 2014-09-30 |
| MCL | Health-based | Resolved | 2014-09-01 → 2014-09-30 |
| MCL | Health-based | Resolved | 2014-09-01 → 2014-09-30 |
| MCL | Health-based | Resolved | 2014-09-01 → 2014-09-30 |
| MCL | Health-based | Resolved | 2014-09-01 → 2014-09-30 |
| MCL | Health-based | Resolved | 2014-07-01 → 2014-07-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Fluoride | 1150 µg/L 29% of the EPA limit 4000 µg/L
worst single sample: 1370 µg/L | 171/174 | SYR4 | 2012–2019 |
| Copper | 342 µg/L 26% of the EPA limit 1300 µg/L
worst single sample: 490 µg/L | 57/90 | SYR4 | 2013–2019 |
| Dibromochloromethane | 6.5 µg/L No EPA limit set
worst single sample: 7.1 µg/L | 39/45 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 5.9 pCi/L No EPA limit set
worst single sample: 6.2 pCi/L | 31/39 | SYR4 | 2012–2019 |
| Chloroform | 7.32 µg/L No EPA limit set
worst single sample: 7.8 µg/L | 29/33 | SYR4 | 2012–2019 |
| Bromodichloromethane | 7.865 µg/L No EPA limit set
worst single sample: 8 µg/L | 28/33 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 6.025 µg/L 10% of the EPA limit 60 µg/L
worst single sample: 6.4 µg/L | 28/30 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 2.85 µg/L No EPA limit set
worst single sample: 3.3 µg/L | 27/30 | SYR4 | 2012–2019 |
| TTHM | 22.37 µg/L 28% of the EPA limit 80 µg/L
worst single sample: 24 µg/L | 27/29 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.775 µg/L No EPA limit set
worst single sample: 1.9 µg/L | 26/30 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 1.685 µg/L No EPA limit set
worst single sample: 1.8 µg/L | 24/30 | SYR4 | 2012–2019 |
| Bromoform | 2.5 µg/L No EPA limit set
worst single sample: 2.9 µg/L | 23/33 | SYR4 | 2012–2019 |
| Lead | 7.05 µg/L 47% of the EPA limit 15 µg/L
worst single sample: 8 µg/L | 20/96 | SYR4 | 2013–2019 |
| Lead | 0.0010 mg/L 6.7% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2025 |
| Nitrate-Nitrite | 388 µg/L 3.9% of the EPA limit 10000 µg/L
worst single sample: 400 µg/L | 7/19 | SYR4 | 2012–2019 |
| Lithium | 32.7 µg/L No EPA limit set | 6/6 | UCMR-5 | 2024 |
| Barium | 399 µg/L 20% of the EPA limit 2000 µg/L
worst single sample: 400 µg/L | 3/6 | SYR4 | 2013–2019 |
| Monobromoacetic Acid | 2.62 µg/L No EPA limit set
worst single sample: 2.7 µg/L | 2/30 | SYR4 | 2012–2019 |
| Nitrate | 310 µg/L 3.1% of the EPA limit 10000 µg/L | 2/2 | SYR4 | 2016 |
90 contaminants tested, none detected
Utility contact
Frequently asked questions about Grand Prairie Regional Water
Is Grand Prairie Regional Water tap water safe to drink?
EPA monitoring detected 19 contaminants in Grand Prairie Regional Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Grand Prairie Regional Water's water?
EPA monitoring detected Fluoride, Copper, Dibromochloromethane, Gross Beta Particle Activity, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Grand Prairie Regional Water serve?
Grand Prairie Regional Water reports serving 15,204 people in Arkansas, per its EPA record.
Has Grand Prairie Regional Water had any water quality violations?
The EPA has 32 violations on file for Grand Prairie Regional Water, of which 25 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.