Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2020-12-01 → 2020-12-31 |
| MCL | Health-based | Resolved | 2020-12-01 → 2020-12-31 |
| MCL | Health-based | Resolved | 2020-12-01 → 2020-12-31 |
| MCL | Health-based | Resolved | 2020-12-01 → 2020-12-31 |
| MCL | Health-based | Resolved | 2020-12-01 → 2020-12-31 |
| MCL | Health-based | Resolved | 2015-01-01 → 2015-01-31 |
| MCL | Health-based | Resolved | 2015-01-01 → 2015-01-31 |
| MCL | Health-based | Resolved | 2015-01-01 → 2015-01-31 |
| MCL | Health-based | Resolved | 2015-01-01 → 2015-01-31 |
| MCL | Health-based | Resolved | 2014-01-01 → 2014-03-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chlorite | 859.2 µg/L 86% of the EPA limit 1000 µg/L
worst single sample: 1050 µg/L | 168/168 | SYR4 | 2014–2019 |
| Fluoride | 1103 µg/L 28% of the EPA limit 4000 µg/L
worst single sample: 1190 µg/L | 78/80 | SYR4 | 2012–2019 |
| Bromodichloromethane | 7.39 µg/L No EPA limit set
worst single sample: 8.6 µg/L | 63/63 | SYR4 | 2012–2019 |
| Chloroform | 84.38 µg/L No EPA limit set
worst single sample: 128 µg/L | 63/63 | SYR4 | 2012–2019 |
| Copper | 394 µg/L 30% of the EPA limit 1300 µg/L
worst single sample: 588 µg/L | 53/61 | SYR4 | 2013–2019 |
| TTHM | 93.8 µg/L 117% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 130 µg/L | 53/53 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 27.585 µg/L No EPA limit set
worst single sample: 70.8 µg/L | 52/52 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 60.32 µg/L 101% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 150 µg/L | 52/52 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 26.535 µg/L No EPA limit set
worst single sample: 74.6 µg/L | 52/52 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 5.58 µg/L No EPA limit set
worst single sample: 9.3 µg/L | 37/52 | SYR4 | 2012–2019 |
| Lead | 99.95 µg/L 666% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 359 µg/L | 16/70 | SYR4 | 2012–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2025 |
| Nitrate-Nitrite | 180 µg/L 1.8% of the EPA limit 10000 µg/L | 12/20 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.1 µg/L No EPA limit set | 11/70 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 2.11 µg/L No EPA limit set
worst single sample: 2.2 µg/L | 4/52 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 3.2 pCi/L No EPA limit set | 1/10 | SYR4 | 2012–2019 |
92 contaminants tested, none detected
Utility contact
Frequently asked questions about Mena Water Department
Is Mena Water Department tap water safe to drink?
EPA monitoring detected 16 contaminants in Mena Water Department's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Mena Water Department's water?
EPA monitoring detected Chlorite, Fluoride, Bromodichloromethane, Chloroform, Copper, and others. The full list with the level and data source for each is above.
How many people does Mena Water Department serve?
Mena Water Department reports serving 5,604 people in Arkansas, per its EPA record.
Has Mena Water Department had any water quality violations?
The EPA has 61 violations on file for Mena Water Department, of which 54 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.